Models F1FR-FS56, F1FR-FS42 Pendent 
Sprinklers, F1FR-FS56 and F1FR-FS42 
Pendent Sprinklers with shield
Application

Models F1FR-FS56 and F1FR-FS42 Flat Spray Sprinklers 

are used in concealed spaces, suspended open ceiling 
and in racks in accordance with CEA 4001 Sprinkler 

System Planning) and EN 12845 (Automatic Sprinkler 
Systems - Design Installation and Maintenance). 

Installation

Models F1FR-FS56 and F1FR-FS42 Flat Spray Sprinklers 

are quick response sprinklers intended for installation as  

specified in CEA 4001 and EN 12845. They must also be 
installed with the Model W2 Sprinkler Wrench specifically 
designed by Reliable for use with these sprinklers.

When installing Models F1FR-FS56 and F1FR-FS42 

Pendent with shield use the Model W4 Sprinkler Wrench. 

Any other type of wrench may damage these sprinklers.

Note:

 A leak tight ½” NPT sprinkler joint can be obtained 

with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).  Do not 

tighten sprinklers over maximum recommended torque.  It 
may cause leakage or impairment of the sprinklers.

Ordering Information 

Specify: 

1.  Sprinkler Model 
2. 

Sprinkler Type 

3. 

Orifice Size 

4. 

Deflector Type

5.  Temperature Rating

       - Specify Bulb Size when ordering 

6. 

Sprinkler Finish - Bronze only

Note:

 When Models F1FR-FS56 and F1FR-FS42 

Pendent Sprinklers with shield are ordered, the 

sprinklers and shields are packaged separately.

Maintenance

 The Models F1FR-FS56, F1FR-FS42 Pendent, F1FR-

FS56 and F1FR-FS42 Pendent Sprinklers with shield 

should be inspected quarterly. Do not clean sprinklers 
with soap and water, ammonia or any other cleaning fluid.  
Remove any sprinkler which has been painted (other than 
factory applied) or damaged in any way.  A stock of spare 

sprinklers should be maintained to allow quick replacement 
of damaged or operated sprinklers.  Prior to installation, 
sprinklers should be maintained in the original cartons and 
packaging until used to minimize the potential for damage 
to sprinklers that would cause improper operation or non-
operation.

Temperature Ratings

Classification

Sprinkler

Temperature

Max. Ambient 

Temp.

Bulb

Color

°C

°F

Ordinary
Ordinary

Intermediate 
Intermediate 
High 

57   
68  
79  
93 

141 

135 
155 
175 
200 
286 

100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)

225°F (107°C)

Orange

Red

Yellow
Green

Blue

Finish

Sprinkler

Shield

Bronze

Galvanized

The Reliable Automatic Sprinkler Co., Inc.

(800)431–1588 

           

Sales Offices

(800)848–6051 

           

Sales Fax

(914)829–2042 

           

Corporate Offices

www.reliablesprinkler.com 

Internet Address

Manufactured by

Recycled

Paper

EG. Printed in U.S.A. 08/21

P/N 9999970360

The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, 

or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

Products manufactured and distributed by Reliable have been protecting life and property for over 100 years, and are installed and serviced by the most highly qualified and reputable sprinkler 

contractors located throughout the United States, Canada and foreign countries.

Revision lines indicate updated or new data

Отзывы: