background image

Model F1FR-FS5 LO Quick Response Pendent Sprinkler

Installation Wrench: 

Model D Sprinkler Wrench

Installation Data:

Sprinkler Type

Standard–Pendent (SSP)

Deflectors Marked to Indicate Position

K Factor 

Sprinkler

Height

Approval

Organizations

US

Metric

(20mm) Standard Orifice with R1/2 Thread

8.0

115

58mm 

VdS

Pendent

Application

Model F1FR-FS LO Flat Spray Sprinkler is used in con-

cealed spaces, suspended open ceiling and in racks in 
accordance with CEA 4001 Sprinkler System Planning) 
and EN 12845 (Automatic Sprinkler Systems - Design In-
stallation and Maintenance). 

Installation

Model F1FR-FS LO Flat Spray Sprinklers are quick re-

sponse sprinklers intended for installation as  specified in 
CEA 4001 and EN 12845. They must also be installed with 
the Model D Sprinkler Wrench specifically designed by 
Reliable for use with these sprinklers.

Note:

 A leak tight ½” NPT sprinkler joint can be obtained 

with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).  Do not tight-
en sprinklers over maximum recommended torque.  It may 
cause leakage or impairment of the sprinklers.

Ordering Information 

Specify: 
1.  Sprinkler Model 
2.  Sprinkler Type 
3.  Orifice Size 
4.  Deflector Type
5.  Temperature Rating
       - Specify Bulb Size when ordering 
6.  Sprinkler Finish - Bronze only

Maintenance

 The Model F1FR-FS LO Pendent should be inspected 

quarterly. Do not clean sprinklers with soap and water, am-
monia or any other cleaning fluid.  Remove any sprinkler 
which has been painted (other than factory applied) or 
damaged in any way.  A stock of spare sprinklers should 
be maintained to allow quick replacement of damaged or 
operated sprinklers.  Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until 
used to minimize the potential for damage to sprinklers 
that would cause improper operation or non-operation.

Temperature Ratings

Classification

Sprinkler

Temperature

Max. Ambient 

Temp.

Bulb

Color

°C

°F

Ordinary
Ordinary
Intermediate 
Intermediate 
High 

57   
68  
79  
93 

141 

135 
155 
175 
200 
286 

100°F (38°C)
100°F (38°C)
150°F (66°C)
150°F (66°C)

225°F (107°C)

Orange

Red

Yellow
Green

Blue

The Reliable Automatic Sprinkler Co., Inc.

(800)431–1588 

           

Sales Offices

(800)848–6051 

           

Sales Fax

(914)829–2042 

           

Corporate Offices

www.reliablesprinkler.com 

Internet Address

Manufactured by

Recycled

Paper

EG. Printed in U.S.A. 11/17

P/N 9999970415

The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research 
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable 
sprinkler contractors located throughout the United States, Canada and foreign countries.

Revision lines indicate updated or new data

Отзывы: