background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model F1FR-FS LO
Large Orifice
Quick Response
Flat Spray Sprinkler
With 

1

/

2

” 

Connection Thread

Bulletin 037 Rev

. B

Bulletin 037 Rev. B

Model F1FR-FS LO Large Orifice Flat Spray 
Sprinkler Types

Standard Pendent

Listings & Approvals

• 

VdS Schadenverhütung GmbH: Certificate

• 

EC-Certificate: EC Certificate: 0786-CPD-40284 

Product Description

The F1FR-FS LO Flat Spray Sprinklers are designed for 

installation in accordance with CEA 4001 or EN 12845 
(Automatic Sprinkler Systems - Design, Installation and 
Maintenance). The spray pattern created by this sprin-
kler makes this an excellent choice for applications with 
lower clearance above the suspended open ceilings and 
in racks.

The F1FR-FS LO Flat Spray Sprinkler utilizes a frangible 

3.0mm glass bulb. The glass bulb consists of an accurate-
ly controlled amount of special fluid hermetically sealed 
inside of a precisely manufactured glass capsule. This 
glass bulb is specially constructed to provide fast thermal 
response.

At normal temperatures, the glass bulb contains the fluid 

in both the liquid phase and in the vapor phase. The vapor 
phase can be seen as a small bubble. As heat is applied, 
the liquid expands forcing the bubble smaller and smaller 
as the liquid pressure increases. Continued heating forces 
the liquid to push out against the bulb, causing the glass 
to shatter, opening the waterway and allowing the deflec-
tor to distribute the discharging water.

The F1FR-FS LO Flat Spray Sprinkler temperature rating 

is identified by the color of the glass bulb capsule.

Pendent

Отзывы: