Reliable F156-300 Series Скачать руководство пользователя страница 3

3.

Installation

Model F156-300 EC sprinklers are standard response 

sprinklers intended for installation as specified in NFPA 13.  
They must be installed with the Model D Sprinkler Wrench 
specifically designed by Reliable for use with these sprin-
klers.

The Model F156-300 EC Recessed Sprinklers are to 

be installed with a maximum recess of ¾” (19mm).  The 
Model F1, F2, and FP escutcheons illustrated are the only 
recessed escutcheons to be used with Model F156-300 
EC Pendent Sprinklers.  The use of any other recessed es-
cutcheon will void all approvals and negate all warranties.  
When installing Model F156-300 EC Recessed Pendent 
sprinklers, use the Model GFR2 Sprinkler Wrench. Any 
other type of wrench may damage these sprinklers.

Glass bulb sprinklers have orange bulb protectors to 

minimize bulb damage during shipping, handling and 
installation. REMOVE THIS PROTECTION AT THE TIME 
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR 
FIRE PROTECTION. Removal of the protectors before this 
time may leave the bulb vulnerable to damage. RASCO 
wrenches are designed to install sprinklers when covers 
are in place. REMOVE PROTECTORS BY UNDOING THE 
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE 
THE PROTECTORS.

Maintenance 

The Models F156-300 EC Pendent and Recessed EC 

Pendent Sprinklers should be inspected quarterly and the 
sprinkler system maintained in accordance with NFPA 25.  
Do not clean sprinklers with soap and water, ammonia or 
any other cleaning fluid.  Remove any sprinkler that has 
been painted (other than factory applied) or damaged in 
any way.  A stock of spare sprinklers should be maintained 
to allow quick replacement of damaged or non-operated 
sprinklers.  Prior to installation, sprinklers should be main-
tained in the original cartons and packaging until used to 
minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Finishes 

(1)

Standard Finishes

Sprinkler

Escutcheon

Bronze
Chrome Plated
White or Black Polyester Coated

Brass
Chrome Plated
White Painted

Special Application Finishes
Sprinkler

Escutcheon

Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Lead Plated 

(2)

Wax Coated 

(2)

Wax Over Lead 

(2)

Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Lead Plated
Wax Coated
Wax Over Lead

(1)

 Other colors and finishes are available on special order. Consult factory 

for details.

(2)

 155°F (68°C) Rating Only.

Note:

 Paint or any other coating applied over the factory finish will void 

approvals and waranties. 

Ordering Information

Specify:

Sprinkler Model
Sprinkler Type 
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish (where applicable)

Note:

  When Model F156-300 EC Recessed Pendent Sprinklers are 

ordered, the sprinklers and escutcheons are packaged sepa-
rately.  

1.
2.
3.
4.
5.
6.
7.

Escutcheon Data

Escutcheon

Model

Adjustment

“A”

Dimension

Face of Fitting to 

Ceiling or Wall

Dimension

F1

Max Recessed

Min Recessed

1

1

/

2

” (38.1mm)

3

/

4

” (19.1mm)

3

/

16

” - 

15

/

16

(5m - 24mm)

F2

Max Recessed

Min Recessed

1

1

/

2

” (38.1mm) 

1” (25mm)

3

/

16

” - 

11

/

16

(5m - 17mm)

FP Push-on/ 

Thread-off

Max Recessed

Min Recessed

7

/

16

” (11mm) 

15

/

16

” (24mm)

1

1

/

2

” (38.1mm)

1” (25mm)

Temperature Rating

Classi

fi

 cation

Sprinkler

Temperature

Maximum

Ambient

Temperature

Bulb 

Color

°F

°C

°F

°C

Ordinary
Ordinary

135
155

57
68

100
100

38
38

Orange
Red

Maximum Working Pressure

300 psi (20.7 bar)
100% Factory tested hydrostatically to 600 psi (41.4 bar)