background image

Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify the following when ordering:

        

Sprinkler

 

•  Model: F1-56SS Pendent, F1-56SS Upright, 

 

    F1-80SS Pendent, F1-80SS Upright

 

•  Temperature Rating: 135°F (57°C), 155°F (68°C),      

 

    175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F    

 

    (182°C), 500°F (260°C) 

 

•  Threads: NPT or ISO7-1

 

•  Finish: None, White Polyester, Black Polyester

                  Custom Color Polyester

        

Escutcheon (Pendent Only)

 

•  Model: F1 recessed stainless steel, F2 recessed   

 

   stainless steel, FP recessed stainless steel, B stain

                  less steel

      

  Sprinkler Wrench

 

•  Model W2 (pendent, upright)

 

•  Model GFR2 (recessed pendent)

Maintenance

Model F1-SS series sprinklers should be inspected and the 
sprinkler system maintained in accordance with NFPA 25. 
Do not clean sprinklers with soap and water, ammonia or any 
other cleaning fluids. Remove dust by gentle vacuuming. Re-
place any sprinkler which has been painted (other than factory 
applied) or damaged in any way. A stock of spare sprinklers 
should be maintained to allow quick replacement of damaged 
or operated sprinklers. Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until used 
to minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Bulletin 064 
December 2019

Page 6 of 6

www.reliablesprinkler.com

Listings and Approvals

• 

Listed by Underwriters Laboratories, Inc. and UL Certified 
for Canada (cULus) - Guide Number VNIV.EX454 - 
Sprinklers, Automatic and Open

• 

FM Approved

P/N 9999970521

Installation

Glass bulb sprinklers have orange bulb protectors to minimize 
bulb damage during shipping, handling, and installation. Reliable 
sprinkler installation wrenches are designed to install sprinklers 
with bulb protectors in place. Remove the bulb protector at the 
time when the sprinkler system is placed in service for fire protec-
tion. Removal of the bulb protector before this time may leave the 
bulb vulnerable to damage. Remove bulb protectors by undoing 
the clasp by hand. Do not use tools to remove bulb protectors. 

Model F1-SS series sprinklers must be installed with the Reliable 
sprinkler installation wrench identified in this Bulletin. Any other 
wrench may damage the sprinkler. Recommended installation 
torque is 8 to 18 lb/ft (11 to 24 N/m) for 1/2” NPT and ISO7-1R1/2 
sprinklers or 14 to 20 lb/ft (19 to 27 N/m) for 3/4” NPT and ISO7-
1R3/4 sprinklers. Do not tighten sprinklers over the maximum rec-
ommended installation torque. Exceeding the maximum recom-
mended installation torque may cause leakage or impairment of 
the sprinkler. 

Recessed pendent sprinklers are to be installed as shown in Fig. 2 
or Fig 5., as applicable to the specific model being installed. Mod-
el F1-SS series recessed pendent sprinklers may only be installed 
with the Reliable Model F1 stainless steel, Model F2 Stainless 
Steel, or Model FP stainless steel recessed escutcheon. The use 
of any other recessed escutcheon will void all approvals and ne-
gate all warranties. The Reliable Model FP escutcheon may not be 
used in ceilings having positive pressure with respect to the space 
below. Ensure that the openings in the Model FP escutcheon/can 
assembly are unobstructed following installation. 

Application

Model F1-SS series sprinklers are standard spray, standard-re-
sponse sprinklers intended for installation in accordance with 
NFPA 13 and the requirements of applicable Authorities Hav-
ing Jurisdiction. Model F1-SS series sprinklers are cULus List-
ed and FM Approved as Corrosion Resistant sprinklers. Verify 
compatibility with the environment where the sprinkler will be 
located prior to installation.

 Wrench                                                                                                                    

Model W2 (upright, pendent)

Model GFR2 (recessed pendent)

(original)

(updated)

Sprinkler Finishes

Escutcheon Finishes

None

  White Polyester

  Black Polyester

  Custom Color Polyester

None

White Polyester
 Chrome Plated

Brass Plated

Table B

Finishes

Отзывы: