3.
Finish
(1)
UL, ULC and FM approved. UL and ULC listed corrosion
resistant sprinkler.
(2)
FP Push on-thread off escutcheon.
Sprinkler
Escutcheon
White Polyester Coated
(1)(2)
White Painted
Model F1 56 & F1 56 Recessed Sprinklers
Application
Model F1 56 and F1 56 Recessed sprinklers are used in
fixed fire protection systems: Wet, Dry, Deluge or Preaction.
Care must exercised that the orifice size, temperature rating,
deflector style and sprinkler type are in accordance with the
latest published standards of the National Fire Protection
Association or the approving Authority Having Jurisdiction
Installation.
Installation
Model F1 56 sprinklers are standard response sprinklers
intended for installation as specified in NFPA 13. They must
also be installed with the Model D Sprinkler Wrench
specifically designed by Reliable for use with these
sprinklers.
The Model F1 56 Recessed Sprinklers are to be installed
with a maximum recess of ¾ inch (19mm). The Model F1 56
Escutcheon illustrated is the only recessed escutcheon to be
used with the Model F1 56 Pendent Sprinklers. The use of
any other recessed escutcheon will void all approvals and
negate all warranties. When installing Model F1 56
Recessed Pendent use the Model GFR2 Sprinkler Wrench.
Any other type of wrench may damage these sprinklers.
Note:
A leak tight ½" NPT (R1/2) sprinkler joint can be
obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS
PROTECTION ONLY AFTER THE SYSTEM HAS BEEN
HYDROSTATICALLY TESTED AND, WHEN APPLICABLE,
THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers are
in place.
Temperature Ratings
Classification
Sprinkler
Temperature
Max. Ambient
Temp.
Bulb
Color
°C
°F
Ordinary
Ordinary
Intermediate
Intermediate
High
(1)
Extra High
(1)
57
68
79
93
141
182
135
155
175
200
286
360
100
°
F (38
°
C)
100
°
F (38
°
C)
150
°
F (66
°
C)
150
°
F (66
°
C)
225
°
F (107
°
C)
300
°
F (149
°
C)
Orange
Red
Yellow
Green
Blue
Mauve
(1)
Not available for F1 Recessed.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating:
- Specify Bulb Size when ordering
- Model F1 EC HSW Sprinkler
6. Sprinkler Finish
7. Escutcheon Finish (where applicable)
Maintenance
The Models F1 56 and F1 56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluid. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated
sprinklers.
Prior to installation, sprinklers should be
maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Note:
When Model F1FR 56 Recessed Sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
Escutcheon
Model
Approvals
Adjustment
"A"
Dimension
Face of Fitting to
Ceiling or Wall
Dimension
F1
1, 2
Max Recessed
Min Recessed
1
1
2
"
(38.1mm)
8
4
"
(19.1mm)
3
16
" -
11
16
"
(5mm - 24mm)
F2
1, 2, 3
Max Recessed
Min Recessed
1
1
2
"
(38.1mm)
1"
(25mm)
3
16
" -
11
16
"
(5mm - 24mm)
FP Push-on/
Thread-off
1, 2
Max Recessed
7
19
"
(11mm)
1
1
2
"
(38.1mm)
1, 2
Min Recessed
15
16
"
(24mm)
1"
(25mm)
Escutcheon Data
No Dimensional Figure for FP