Finish

(1)

UL, ULC and FM approved. UL and ULC listed corrosion

resistant sprinkler.

(2)

FP Push on-thread off escutcheon.

Sprinkler

Escutcheon

White Polyester Coated

(1)(2)

White Painted

Model F1 56 & F1 56 Recessed Sprinklers
Application

Model F1 56 and F1 56 Recessed sprinklers are used in

fixed fire protection systems: Wet, Dry, Deluge or Preaction.
Care must exercised that the orifice size, temperature rating,
deflector style and sprinkler type are in accordance with the
latest published standards of the National Fire Protection
Association or the approving Authority Having Jurisdiction
Installation.

Installation

Model F1 56 sprinklers are standard response sprinklers

intended for installation as specified in NFPA 13. They must
also be installed with the Model D Sprinkler Wrench
specifically designed by Reliable for use with these
sprinklers.

The Model F1 56 Recessed Sprinklers are to be installed

with a maximum recess of ¾ inch (19mm). The Model F1 56
Escutcheon illustrated is the only recessed escutcheon to be
used with the Model F1 56 Pendent Sprinklers. The use of
any other recessed escutcheon will void all approvals and
negate all warranties. When installing Model F1 56
Recessed Pendent use the Model GFR2 Sprinkler Wrench.
Any other type of wrench may damage these sprinklers.

Note:

A leak tight ½" NPT (R1/2) sprinkler joint can be

obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.

Glass bulb sprinklers have orange covers to protect the

bulb during the installation process. REMOVE THIS
PROTECTION ONLY AFTER THE SYSTEM HAS BEEN
HYDROSTATICALLY TESTED AND, WHEN APPLICABLE,
THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers are
in place.

Temperature Ratings

Classification

Sprinkler

Temperature

Max. Ambient

Temp.

Bulb

Color

°C

°F

Ordinary
Ordinary
Intermediate
Intermediate
High

(1)

Extra High

(1)

57
68
79
93

141
182

135
155
175
200
286
360

100

°

F (38

°

C)

100

°

F (38

°

C)

150

°

F (66

°

C)

150

°

F (66

°

C)

225

°

F (107

°

C)

300

°

F (149

°

C)

Orange

Red

Yellow
Green

Blue

Mauve

(1)

Not available for F1 Recessed.

Ordering Information

Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating:

- Specify Bulb Size when ordering
- Model F1 EC HSW Sprinkler

6. Sprinkler Finish
7. Escutcheon Finish (where applicable)

Maintenance

The Models F1 56 and F1 56 Recessed Sprinklers

should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluid. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated
sprinklers.

Prior to installation, sprinklers should be

maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.

Note:

When Model F1FR 56 Recessed Sprinklers are

ordered, the sprinklers and escutcheons are packaged
separately.

Escutcheon

Model

Approvals

Adjustment

"A"

Dimension

Face of Fitting to

Ceiling or Wall

Dimension

F1

1, 2

Max Recessed

Min Recessed

1

1

2

"

(38.1mm)

8

4

"

(19.1mm)

3

16

" -

11

16

"

(5mm - 24mm)

F2

1, 2, 3

Max Recessed

Min Recessed

1

1

2

"

(38.1mm)

1"

(25mm)

3

16

" -

11

16

"

(5mm - 24mm)

FP Push-on/

Thread-off

1, 2

Max Recessed

7

19

"

(11mm)

1

1

2

"

(38.1mm)

1, 2

Min Recessed

15

16

"

(24mm)

1"

(25mm)

Escutcheon Data

No Dimensional Figure for FP