Maintenance

Model DH80 Quick-Response Dry Sprinklers should be 

inspected and the sprinkler system maintained in accordance 
with NFPA 25.  Do not remove the factory applied thermally 

sensitive wax fillet between the bulb supporting cup and the 

wrenching boss.  Do not replace this wax with a substitute 
substance.  An alternate substance may interfere with 
proper operation of the sprinkler.  Do not clean sprinklers 
with soap and water, ammonia or any other cleaning fluids.  
Remove dust by gentle vacuuming.  Replace any sprinkler 
which has been painted (other than factory applied) or 
damaged in any way.  A stock of spare sprinklers should 

be  maintained  to  allow  quick  replacement  of  damaged  or 

operated sprinklers.  Prior to installation, sprinklers should 
be maintained in their original cartons and packaging until 
used to minimize the potential for damage to sprinklers that 
would cause improper operation or non-operation.

Model DH80 Dry Quick-Response
Extended Coverage Horizontal

Sidewall Sprinkler Specification

Sprinklers  shall  be  cULus  Listed  quick-response 

extended coverage horizontal sidewall sprinklers for light 
hazard occupancies.  Sprinklers to be of bronze frame 
construction with a special deflector capable of providing a 
discharge over a coverage area of 28 ft. (8.5 m) wide, and 
14  ft. (4.3 m) long horizontal throw. Sprinklers shall have 

[standard  escutcheons][extended  escutcheons][recessed 
escutcheons][conical concealed cover plates] produced by 

the manufacturer of the sprinklers and cULus Listed for use 
with the sprinklers. Water seal assembly shall consist of a 
PTFE coated Belleville spring washer. Sprinklers should be 
cULus Listed to permit deflectors to be positioned 4“ (102 
mm) to 12” (305 mm) below the ceiling.  Sprinklers shall 

have a nominal K-Factor of 8.0 (115 metric), and [1” NPT]
[ISO  7-1R1]  threads.    Sprinkler  temperature  rating  shall 
be  [155°F  (68°C)][175°F  (79°C)][200°F  (93°C)].    Rated 

working pressure shall be 175 psi (12 bar).  Sprinkler and 

escutcheon finish shall be [white polyester][black polyester]
[chrome][bronze/brass][Special Application - Note: Specify 
based  on  Finishes  table].  [Conical  concealed  cover  plate 
finish  shall  be  [white  paint][Special  Application  -  Note: 
Specify based on Finishes table].] [Sprinklers shall be cULus 
Listed  as  Corrosion  Resistant  (Note:  available  with  white 
polyester, black polyester, and ENT finishes only) (Note: not 
available with sprinklers using the Model SWC cover plate)]. 

Quick-response extended coverage horizontal sidewall dry 
sprinklers shall be Reliable Model DH80 Dry, SIN RA5532 
(Bulletin 055). 

Step 3

Step 2

Step 1

Fig. 3 - XLO2 Wrench

Fig. 2 - F3R Wrench

Installation Data:

Escutcheon or

Cover Plate Option

Recommended

Hole Diameter

Installation

Wrench

Standard escutcheon

2-1/8” (54 mm)

F3R

HB extended escutcheon

2-1/2” (64 mm)

F3R

FP recessed escutcheon

2-5/8” (67 mm)

XLO2

SWC  cover plate

2-1/8” (54 mm)

XLO2

Содержание DH80 Dry

Страница 1: ...Light Hazard occupancies Patents US Patent No 7 841 418 Products Description The Model DH80 Dry sprinkler is a quick response extended coverage horizontal sidewall sprinkler for use in Light Hazard ap...

Страница 2: ...ate occurs when the solder melts due to an increase in the surrounding temperature allowing the cover plate to fall away and exposing the Model DH80 Dry sprinkler Model SWC cover plates are available...

Страница 3: ...al throw Sprinklers shall have standard escutcheons extended escutcheons recessed escutcheons conical concealed cover plates produced by the manufacturer of the sprinklers and cULus Listed for use wit...

Страница 4: ...ot less than 4 102 mm or more than 12 305 mm from the finished ceiling A hole must be cut in the wall directly in line with the outlet of the tee See the Installation Data table for the recommended ho...

Страница 5: ...Stainless Steel Bronze Laquered Brass Chrome Polished Stainless Steel White Polyester 1 White Polyester 4 Black Polyester 1 Black Polyester 4 Custom Color Polyester 1 Custom Color Polyester 4 Electrol...

Страница 6: ...Sprinkler Escutcheon 2 3 Bronze Chrome Chrome Chrome White Polyester 1 White Polyester Black Polyester 1 Black Polyester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Stain...

Страница 7: ...ite Polyester 2 White Polyester Black Polyester 2 Black Polyester Custom Color Polyester 2 Custom Color Polyester Electroless Nickel PTFE 2 Stainless Steel Notes 1 Cup for FP Recessed is unfinished ga...

Страница 8: ...r 1 connections Finish Combinations SWC Concealed Cover Plate Sprinkler 1 Cover Plate 2 Bronze White Polyester Chrome Bright Chrome Dull Bright Brass Unfinished Bronze Black Plate Custom Color Notes 1...

Страница 9: ...Fig 8 9...

Страница 10: ...10 Fig 9...

Страница 11: ...11 Fig 11...

Страница 12: ...property for almost 100 years Ordering Information Specify 1 Sprinkler Model DH80 Dry 2 Escutcheon Cover Plate Model Standard escutcheon Model HB extended escutcheon Model FP recessed escutcheon Model...

Отзывы: