background image

Installation (General)

Dry sprinklers connected to wet pipe systems must be installed as 
indicated in Figure 6 and as required by NFPA 13 with the Exposed 
Minimum Barrel Length located in a heated area.

Reliable Model DH56 dry sidewall sprinklers may be installed in
ductile or malleable cast iron threaded tees, or CPVC tees and

adapters upon verification that the sprinkler inlet fitting does not
interfere with the interior of the fitting (see Figure 7).

DO NOT install Reliable Model DH56 dry sidewall sprinklers into
elbows or couplings, welded outlets, mechanical tees, or gasket

sealed CPVC fittings.

 

DH56 HSW with Standard Escutcheon

Cut a 2-1/8” (54mm) diameter hole in the wall as shown in Fig. 
2. Apply a PTFE based sealant to the sprinkler threads before 

installing into the fitting. Use the Model F3R installation wrench 

(see Fig. 8) on the square boss to tighten the sprinkler until 

it is secured in the sprinkler fitting. Installation is completed 

by removing the orange glass bulb protector and sliding the 

escutcheon over the finished sleeve until tight to the finished 

surface.

DH56 HSW with HB Escutcheon

Cut a 2-1/2” (64mm) diameter hole in the wall as shown in Fig. 
3. Apply a PTFE based sealant to the sprinkler threads before 

installing into the fitting. Use the Model F3R installation wrench 

(see Fig. 8) on the square boss to tighten the sprinkler until it 

is secured in the sprinkler fitting. Installation is completed by 

removing the orange glass bulb protector and sliding the skirt 

over the finished sleeve until tight to the finished suface.

DH56 HSW with FP Recessed Escutcheon 

Cut a 2-5/8” (67mm) diameter hole in the wall as shown in Fig. 
4. Apply a PTFE based sealant to the sprinkler threads before 

installing into the fitting. Use the Model F3R installation wrench 

(see Fig. 8) on the square boss to tighten the sprinkler until 

it is secured in the sprinkler fitting. Installation is completed 

by removing the orange glass bulb protector and pushing (or 
threading) the FP escutcheon into the threaded cup. Final 
adjustment is made by turning the FP escutcheon clockwise until 
the flange makes full contact with the wall surface.

DH56 HSW SWC Concealed Cover Plate

Cut a 2-5/8” (67mm) diameter hole in the wall as shown in Fig. 
5. Apply a PTFE based sealant to the sprinkler threads before 

installing into the fitting. Use the Model F3R installation wrench 

(see Fig. 8) on the square boss to tighten the sprinkler until 

it is secured in the sprinkler fitting. Installation is completed 

by removing the orange glass bulb protector and pushing (or 
threading) the SWC cover plate into the threaded cup. Final 
adjustment is made by turning the cover plate clockwise until the 

cover plate flange makes full contact with the finished surface.

Note:

 

1.  The Model XLO2 installation wrench for FP Recessed 

and SWC Concealed installations has a open side to 
accommodate the sprinkler deflector and can only be 
inserted in one way (see Figure 8). Care must be taken not to 
damage the deflector during installation.

2. 

Do not over-tighten sprinklers into fittings. It is recommended 

that Reliable dry sprinklers be installed using the wrench 
referenced in this bulletin. A pipe wrench may also be used 
to install dry sprinklers provided that it only engages the 
outer tube (steel pipe) of the assembly. Note that a pipe 

wrench will impart a large amount of torque into the final 

assembly. This torque will need to be matched or exceeded 
to remove the sprinkler at a later date. A leak free joint can 
normally be obtained by installing the sprinkler to a minimum 
torque of 22 ft-lb (30 N-m) after applying an appropriate 
thread sealant. 

3.  Glass bulb sprinklers have orange bulb protectors to 

minimize bulb damage during shipping, handling, and 
installation. Reliable installation wrenches are designed to 
install sprinklers while bulb protectors are in place. REMOVE 

THE PROTECTORS AT THE TIME THE SPRINKLER SYSTEM 
IS PLACED INTO SERVICE. Removal of the protectors before 

this time may leave the glass bulb vulnerable to damage.  
Remove protectors by undoing the clasp by hand. DO NOT 
USE TOOLS TO REMOVE THE PROTECTORS.

4. 

Do not remove the wax fillet in the gap between the cup that 

supports the bulb and the wrenching boss.

Step 3

Step 2

Step 1

Figure 8

XLO2 Installation Procedure

Bulletin 016
March 2022

Page 9 of 10

www.reliablesprinkler.com

Содержание DH56 Dry

Страница 1: ...ngth of barrel inside the face of the wall or insulation is provided to offset conduction of potentially freezing temperatures from the unconditioned sprinkler end along the barrel See Figure 6 for gu...

Страница 2: ...Deflector Bronze Alloy Load Screw Brass Alloy Sprinkler Finishes See finish combination tables on following pages Sensitivity Quick Response Temperature Ratings 155 F 68 C 175 F 79 C 200 F 93 C Recess...

Страница 3: ...n 2 to 48 50mm to 1200mm Finish Combinations Standard Escutcheon Sprinkler Escutcheon 2 3 Bronze Polished Stainless Steel Bronze Laquered Brass Chrome Polished Stainless Steel White Polyester 1 White...

Страница 4: ...Adjustment 1 15 16 49mm 5 8 16 mm Sprinkler Can Inlet Fitting Escutcheon 1 1 4 32mm Nominal Projection 1 1 4 32mm Wall Ceiling 016HB Finish Combinations HB Escutcheon Sprinkler Escutcheon 2 3 Bronze...

Страница 5: ...Sprinkler 1 Escutcheon 3 4 Bronze Brass Chrome Chrome White Polyester 2 White Polyester Black Polyester 2 Black Polyester Custom Color Polyester 2 Custom Color Polyester Electroless Nickel PTFE 2 Stai...

Страница 6: ...2 5 8 67mm Dia Hole in Wall 3 7 32 Dia 82mm Sprinkler Cup 016SWC Wall Ceiling Finish Combinations SWC Concealed Cover Plate Sprinkler 1 Cover Plate 2 Bronze White Polyester Chrome Bright Chrome Dull...

Страница 7: ...Bulletin 016 March 2022 Page 7 of 10 www reliablesprinkler com Figure 6...

Страница 8: ...Bulletin 016 March 2022 Page 8 of 10 www reliablesprinkler com Figure 7...

Страница 9: ...scutcheon clockwise until the flange makes full contact with the wall surface DH56 HSW SWC Concealed Cover Plate Cut a 2 5 8 67mm diameter hole in the wall as shown in Fig 5 Apply a PTFE based sealant...

Страница 10: ...operated sprinklers Failure to properly maintain sprinklers may result in inadvertent operation or non operation during a fire event Guarantee For the Reliable Automatic Sprinkler Co Inc guarantee te...

Отзывы: