Reliable DDX-LP PrePak Скачать руководство пользователя страница 4

4.

that exceed the working pressure of the valve and trim kit for 
the two-hour test period. 

The valve and applicable trim kit have been tested, ap-

proved and listed under these conditions and as such, hy-
drostatic testing in accordance with NFPA 13 is acceptable. 
In addition, the clapper can remain in the closed position 
and the trim kit need not be isolated, as each has been de-
signed to withstand hydrostatic testing as required by NFPA 
13. 

Subjecting the valve and trim to pressures higher than 

their rating is limited to the hydrostatic test as referenced 
by NFPA13. It does not address the occurrence of a “wa-
ter hammer” effect, which may damage the valve. A “water 
hammer” in the water supply piping of the valve can cre-
ate pressures in excess of the rated pressure and should 
be avoided by all necessary means. This condition may be 
created from improper fire pump settings, underground con-
struction work, or an improper venting of trapped air in the 
water supply piping. 

System Supervisory Pressure Requirements 

The DDX-LP PrePak includes gauges indicating the air/

nitrogen  and water pressures on the Model DDX-LP sys-
tem. Table A specifies the air or nitrogen pressure to be 
maintained in the sprinkler system piping based on the wa-
ter supply pressure.  The factory installed Pressure Mainte-
nance Device in the unit automatically regulates makeup air 
or nitrogen flow to maintain pressure with normal leakage 
from system piping, while restricting the flow of makeup air 
or nitrogen to the system.  Please note that when the optional 
Model B1 Accelerator is to be utilized to expedite water-de-
livery time, the air or nitrogen pressure must be not less than 
15 psi (1.0 bar). 

Table A

Water Pressure

psi (bar)

Supervisory Air or Nitrogen Pressure in 

Sprinkler System, psi (bar)

Maximum

Not Less Than

Not More Than

  20    (1.4)

10   (0.7)

14   (0.9)

 50    (3.4)

12   (0.8)

16   (1.1)

 75    (5.2)

13   (0.9)

17   (1.2)

100    (6.9)

15   (1.0)

19   (1.3)

125    (8.6)

16   (1.1)

20   (1.4)

150    (10.3)

17   (1.2)

21   (1.4)

175    (12.1)

18   (1.2)

22   (1.5)

200    (13.8)

19   (1.3)

23   (1.6)

225    (15,5)

21   (1.5)

25   (1.7)

250    (17.2)

22   (1.5)

26   (1.8)

Note:

 During system setup, a higher pneumatic pressure 

may be required in order to properly set the Model LP Dry 
Pilot Actuator.

The dew point of the air supply must be maintained below 

the lowest ambient temperature to which the dry system will 
be exposed. Introduction of moisture into the system piping 
exposed to freezing temperatures can create ice blockage 
which could prevent proper system operation. As a mini-
mum, the air supply should be taken from the area of lowest 
temperature within the protected area. The air supply sys-
tem must be carefully designed to prevent plugging by frost 
deposits. Special requirements, such as those in FME&R’s 

“Installation Guidelines for Refrigerated Storage” may need 
to be incorporated. 

Nitrogen used in refrigerated area systems minimizes the 

possibility of ice build-up and blockage inside the system 
piping that could inhibit proper system operation. The dew-
point of nitrogen compressed to 20 psig (1.4 bar) pressure 
is -46°F (-43.3°C), and -52°F (-46.7°C) when compressed 
to 10 psig (0.7 bar). High-pressure nitrogen cylinders can 
typically be rented from a local source, with rental fees vary-
ing by supplier and cylinder sizes. The calculated nitrogen 
supply in lbs (kg) to pressurize various system capacities to 
10 psi (0.7 bar) at different freezer temperatures is shown in 
Table B.  

If the Reliable DDX-LP PrePak is to be used with Nitrogen, 

a Nitrogen kit is available as an option.  A pressure switch is 
used to monitor the nitrogen supply; the electrical contacts 
on the pressure switch close when the nitrogen supply falls 
to 100 psi (6,9 bar).  The nitrogen source should be replaced 
promptly upon operation of the pressure switch. If the nitro-
gen supply  is not replaced, make-up air will come solely 
from the unit’s air compressor (if installed).  Compressed air 
is not considered dry air, and may create ice plugs in the 
sprinkler system piping.

Table B

System 

Capacity 

Gal. (L)

Freezer Temperature

Approx.

Fill Time

(min.)*

20°F

(-6.7°C)

0°F

(-18°C)

-20°F

(-29°C)

-40°F

(-40°C)

-60°F

(-51°C)

250

(946)

1.90 

(.86)

 1.90 

(.86)

2.00 

(.90)

2.10 

(.95)

2.20 

(1.00)

1

500

(1891)

3.64 

(1.65)

3.80 

(1.72)

4.00 

(1.81)

4.20 

(1.91)

4.40 

(2.00)

2

750

(2840)

5.50 

(2.50)

5.70 

(2.60)

6.00 

(2.72)

6.30 

(2.86)

6.60 

(3.00)

3

1,000 

(3785)

7.30 

(3.30)

7.60 

(3.44)

8.00 

(3.62)

8.33 

(3.78)

8.80 

(4.00)

4

Note:

 To obtain required nitrogen supply (lbs.) for 15 psi (1.0 

bar) or 22 psi (1.5 bar), multiply the tabulated values by 
a factor of 1.5 or 2.2 respectively. 
(1 bar = 100 kPa) 

* When filled with the Rapid Air – Fill Shutoff Valve open.

If the air compressor in the Model DDX-LP PrePak is to 

be used to initially fill the sprinkler system with air, the steel 
enclosure door should remain open in order to provide maxi-
mum intake air flow to the air compressor. The air compres-
sor is connected to a storage tank. This tank functions as 
a reservoir, providing make-up air to compensate for small, 
intermittent leaks in the sprinkler system. It should be not-
ed that significant leaks may overburden this storage tank, 
thereby causing the air compressor to continuously cycle 
on and off. 

The factory-installed system low air pressure switch may 

need on-site adjustment to correspond with the air pressure 
values found in Table A.  Adjustment, if required, should be 
made according to Potter Bulletin 5401564 included with the 

Содержание DDX-LP PrePak

Страница 1: ...le Automatic Sprinkler Company website www reli ablesprinkler com The heart of the Reliable Model DDX LP PrePak is the Model DDX LP Dry Pipe Valve The Reliable Model DDX LP Dry Pipe Valve is a hydraulically operated differential type valve designed for use as a primary control valve in a low pressure dry pipe valve system The trim set used with the Model DDX LP Dry Pipe Valve contains the Reliable...

Страница 2: ...mm 32 8 ft 17 7 m 6 150 mm 54 7 ft 21 8 m 8 200 mm 79 3 ft 24 2 m The equivalent length in the table above includes the Model DDX LP PrePak valve supply manifold tee sup ply side control valve and the section of pipe above the Model DDX LP PrePak valve 3 Shipping Weight System Size Weight 2 50 mm 2 65 mm 3 80 mm 554 lb 252 kg 4 100 mm 710 lbs 322 kg 6 150 mm 800 lbs 363 kg 8 200mm 1350 lbs 531kg 4...

Страница 3: ...3 Fig 1 ...

Страница 4: ...rotected area The air supply sys tem must be carefully designed to prevent plugging by frost deposits Special requirements such as those in FME R s Installation Guidelines for Refrigerated Storage may need to be incorporated Nitrogen used in refrigerated area systems minimizes the possibility of ice build up and blockage inside the system piping that could inhibit proper system operation The dew p...

Страница 5: ...nk to drain any condensate ac cumulation Reliable Technical Bulletins 338 and 519 pro vide additional information for maintaining the Model DDX LP PrePak Deluge Valve System Setup Refer to Figure 2 1 Close the main valve controlling water supply to the Model DDX LP PrePak deluge valve Also close the two valves supplying air or nitrogen to the system 2 Close the pushrod chamber supply valve 3 Open ...

Страница 6: ...r and Model B Manual Emergency Sta tion for leakage Also verify that tubing drain lines from releasing devices are not pinched or crushed which could prevent proper releasing of the deluge valve 7 Testing alarms Open the alarm test valve permit ting water from the supply to flow to the alarm pressure switch and to the mechanical sprinkler alarm if pres ent After testing close this valve completely...

Страница 7: ...Fig 2 7 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity ...

Страница 8: ...8 Fig 3 ...

Страница 9: ...9 Fig 4 ...

Страница 10: ...e P N are required to be 0 None 2 Not Used 3 Air Compressor sizing may differ if specified sprinkler system has an uncommon volume capacity DDX LP PrePak Valve Size System Side Control Valve U Trim Type 3 Solenoid Valve 0 Releasing Control Panel 0 Air Compressor 3 Y System Air Devices Z 2 2 0 None 0 None 0 None 0 None 0 2 1 2 1 1 2 HP 115 VAC systems up to 3 in size 1 Nitrogen Supply Kit 3 3 3 Pre...

Отзывы: