background image

www.reliablesprinkler.com

Features

• 

Coverage for DD80 spans up to 70 ft (21 m) with one row 
of sprinklers

• 

Coverage for DD80 spans up to 100 ft (30.5 m) with three 
rows of sprinklers

• 

All models use a 212°F (100°C) temperature rated fusible-
link operating element

• 

150 square foot per sprinkler protection using GP56 and 
AH Series sprinklers

Product Description

Reliable Attic Sprinklers are cULus Listed Specific Application 
sprinklers. The sprinklers are available for protection of 
combustible and non-combustible light hazard concealed 
spaces with roof/ceiling slopes of 4:12 to 8:12. Reliable 
Attic Sprinklers are upright sprinklers listed for use on 
wet-pipe or dry-pipe sprinkler systems. All Reliable Attic 
sprinklers use a 212°F (100°C) temperature rated fusible-
link operating element that is Listed for installation where the 
maximum ceiling temperature is up to 150°F (66°C). Table A 
provides a summary of available Reliable Attic sprinklers.

Application

Reliable Attic Sprinklers are listed for installation in 
accordance with this bulletin and NFPA 13, “Standard for the 
Installation of Fire Sprinklers.”  The sprinklers are classified 
as Special Sprinklers by NFPA 13, and are intended for 
installation within combustible or noncombustible roof 
structures, including those with wooden trusses.  Coverage 
area, spacing requirements, and design flow and pressure 
for each sprinkler are provided in tables B-I on the individual 
sprinkler data sheets in this bulletin.  Example sprinkler 
layouts and hydraulic design criteria are provided in Figures 
9 through 25. Please note that the example sprinkler layouts 
are intended as design aids only, and do not necessarily 

Model DS56

Model GP56

Model AH56 

(Model AH42 similar)

Model DD56 

(Model DD80 similar)

Attic Sprinkler Summary

Table A

Sprinkler

Model

K-Factor

gpm/psi

1/2

(L/min/bar

1/2

)

Thread Size

NPT or
ISO7-1

Max. Coverage Area

(Measured on Floor)

ft x ft (m x m)

Roof Slope

Design Criteria

Sprinkler 

Identification 

Number (SIN)

DD56-6

5.6 (80)

½

6 x 40 (1.8 x 12)

4:12 to <6:12

Table B

RA5624

DD56-27

5.6 (80)

½

6 x 40 (1.8 x 12)

6:12 to 8:12

Table C

RA5694

DD80-6

8.0 (115)

¾

6 x 66 or 5 x 70

(1.8 x 20 or 1.5 x 21) 

4:12 to <6:12

Table D

RA5622

DD80-27

8.0 (115)

¾

6 x 66 or 5 x 70

(1.8 x 20 or 1.5 x 21) 

6:12 to 8:12

Table E

RA5692

DS56

5.6 (80)

½

6 x 40 (1.8 x 12)

4:12 to 8:12

Table F

RA5625

GP56

5.6 (80)

½

10 x 15 (3.0 x 4.6)

4:12 to 8:12

Table G

RA5695

AH42

4.2 (60)

½

10 x 15 (3.0 x 4.6)

4:12 to 8:12

Table H

RA5623

AH56

5.6 (80)

½

10 x 15 (3.0 x 4.6)

4:12 to 8:12

Table I

RA5626

reflect all possible construction methods. In some cases, 
a combination of layouts may be required.  The Authority 
Having Jurisdiction should be consulted for situations 
that are not specifically addressed within this bulletin.

Special Note Regarding Insulation

Noncombustible insulation, properly secured with wire 
netting to prevent sagging onto sprinklers may be used at 
the roof deck.  Attic sprinklers have not been evaluated and 
are not listed for use with spray foam insulation.  Use of attic 
sprinklers with spray foam insulation should be evaluated on 
a case by case basis with the Authority Having Jurisdiction.

cULus Listed

Models DD56-6, DD56-27, DD80-6, DD80-27, 

DS56, GP56,  AH42, & AH56 Sprinklers

Specific Application Sprinklers for Attic Spaces

Bulletin 056 February 2020

Содержание AH42

Страница 1: ...ovided in Figures 9 through 25 Please note that the example sprinkler layouts are intended as design aids only and do not necessarily Model DS56 Model GP56 Model AH56 Model AH42 similar Model DD56 Model DD80 similar Attic Sprinkler Summary Table A Sprinkler Model K Factor gpm psi1 2 L min bar1 2 Thread Size NPT or ISO7 1 Max Coverage Area Measured on Floor ft x ft m x m Roof Slope Design Criteria ...

Страница 2: ...s cULus Listed Hazard Classification Light Hazard System Types Wet pipe with steel or Listed CPVC pipe Dry pipe with steel pipe Installation Criteria Sprinkler Spacing Minimum 4 ft 1 2 m maximum 6 ft 1 8m between sprinklers along ridge Minimum 26 ft 7 9 m down the roof slope toward eave to nearest sprinkler measured parallel to the roof deck Horizontal Distance from Face of Truss Min 6 inches 150 ...

Страница 3: ...rtical Distance of Deflector Above Scissor Truss Min 18 inches 450 mm Horizontal Distance from Center line of Ridge Max 6 inches 150 mm Vertical Distance of Top of Deflector Below Peak Ridge or Deck Min 17 inches 430 mm Max 21 inches 530 mm Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless St...

Страница 4: ... 18 inches 450 mm Horizontal Distance from Center line of Ridge Max 6 inches 150 mm Vertical Distance of Top of Deflector Below Peak Ridge or Deck Min 17 inches 430 mm Max 21 inches 530 mm Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless Steel Sealing Assembly Nickel Alloy with PTFE Load Scr...

Страница 5: ... Min 18 inches 450 mm Horizontal Distance from Center line of Ridge Max 6 inches 150 mm Vertical Distance of Top of Deflector Below Peak Ridge or Deck Min 17 inches 430 mm Max 21 inches 530 mm Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless Steel Sealing Assembly Nickel Alloy with PTFE Load...

Страница 6: ...of Draft Curtain Min 8 inches 200 mm Vertical Distance of Deflector Above Scissor Truss Min 18 inches 450 mm Distance from Top of Deflector to Roof Deck measured perpendicular to roof deck Min 9 inches 230 mm Max 13 inches 330 mm Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Brass Alloy Frame Body Brass Alloy Frame Arms Brass Alloy Yoke Copper Alloy Sealing Assembly Nickel...

Страница 7: ...e to nearest sprinkler measured parallel to roof deck Distance from Top of Deflector to Roof Deck measured perpendicular to roof deck Min 9 inches 230 mm Max 13 inches 330 mm Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless Steel Sealing Assembly Nickel Alloy with PTFE Load Screw Bronze Allo...

Страница 8: ...ottom of the protected space Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless Steel Sealing Assembly Nickel Alloy with PTFE Load Screw Bronze Alloy Deflector CHROME PLATED Bronze Alloy Model AH42 Sprinkler Components and Dimensions Figure 7 Model AH42 Minimum Required Flow and Residual Press...

Страница 9: ...m Orientation Frame arms are to be oriented parallel to the eave at the bottom of the protected space Material Specifications Thermal Sensor Nickel Alloy Solder Link Levers Stainless Steel Sprinkler Frame Brass Alloy Button Copper Alloy Button Clip Stainless Steel Sealing Assembly Nickel Alloy with PTFE Load Screw Bronze Alloy Deflector Bronze Alloy Model AH56 Minimum Required Flow and Residual Pr...

Страница 10: ...Model DD Series Sprinkler Example Layout Not to Scale Figure 9 Model DS56 Sprinkler Example Layout Not to Scale Figure 10 Bulletin 056 February 2020 Page 10 of 27 www reliablesprinkler com ...

Страница 11: ...6 Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 11 Model DS56 Sprinklers at Ridge with Model DS56 Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 12 Bulletin 056 February 2020 Page 11 of 27 www reliablesprinkler com ...

Страница 12: ...s Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 13 Model DS56 Sprinklers at Ridge with Model GP56 or AH Series Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 14 Bulletin 056 February 2020 Page 12 of 27 www reliablesprinkler com ...

Страница 13: ...Model DD Series Sprinklers at Ridge with Model GP56 or AH Series Sprinklers in Dormers Example Layout Not to Scale Figure 15 Bulletin 056 February 2020 Page 13 of 27 www reliablesprinkler com ...

Страница 14: ...Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Dormer or Cross Example Layout Not to Scale Figure 16 Bulletin 056 February 2020 Page 14 of 27 www reliablesprinkler com ...

Страница 15: ...17 Model DD Series Sprinklers at Ridge with Model GP56 or AH Series Sprinklers at Eave Example Layout Not to Scale Figure 18 Note if necessary a baffle may be added between the Model DD sprinklers and the Model GP56 sprinklers to prevent cold solder Bulletin 056 February 2020 Page 15 of 27 www reliablesprinkler com ...

Страница 16: ...19 Model DD Series Sprinklers at Ridge with DS56 Sprinklers at Hip or Ell Example Layout Not to Scale Figure 20 Note if necessary a baffle may be added between the Model DS sprinklers and the Model GP56 or AH Series sprinklers to prevent cold solder Bulletin 056 February 2020 Page 16 of 27 www reliablesprinkler com ...

Страница 17: ...inklers at Hip or Ell Example Layout Not to Scale Figure 21 Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Hip or Ell Example Layout Not to Scale Figure 22 Bulletin 056 February 2020 Page 17 of 27 www reliablesprinkler com ...

Страница 18: ...Model DS56 Sprinklers at Ridge with Standard Spray Sprinklers at Hip or Ell Example Layout Not to Scale Figure 23 Bulletin 056 February 2020 Page 18 of 27 www reliablesprinkler com ...

Страница 19: ...Model DD Series Sprinklers at Ridge and Model AH Sprinklers at Hip and Ell Example Layout Not to Scale Figure 24 Bulletin 056 February 2020 Page 19 of 27 www reliablesprinkler com ...

Страница 20: ...Model DS56 Sprinklers at Ridge and Model AH Sprinklers at Hip and Ell Example Layout Not to Scale Figure 25 Bulletin 056 February 2020 Page 20 of 27 www reliablesprinkler com ...

Страница 21: ...nklers at Ridge and DS56 Sprinklers in Attic Plan View Figure 26 Model AH Series Sprinklers at Ridge and DS56 Sprinklers in Attic Cross Section Figure 26A Bulletin 056 February 2020 Page 21 of 27 www reliablesprinkler com ...

Страница 22: ...dditional sprinklers not required below horizontal obstruction 4 0 1 2 m or less in width Additional sprinklers required below horizontal obstruction greater than 4 0 1 2 m in width Additional sprinklers not required beyond horizontal obstruction more than 6 from bottom of rafter Additional sprinkler required beyond horizontal obstruction less than 6 150 mm from bottom of rafter Additional sprinkl...

Страница 23: ...le Attic sprinklers may be installed directly on pipe up to 2 1 2 NPS For 3 NPS and larger pipe the obstruction rules for Extended Coverage Upright Spray Sprinklers shall be followed Bulletin 056 February 2020 Page 23 of 27 www reliablesprinkler com ...

Страница 24: ...s with the deflector parallel to the roof deck and the arrow on the deflector pointing down the roof slope Install Model AH Series sprinklers with the deflector parallel to the roof and frame arms parallel with the lower eave of the protected space Model GP56 and AH Series Installation Install Reliable Attic Sprinklers only in the orientation indicated in Figure 28 Figure 29 provides additional se...

Страница 25: ... must be protected with a minimum 6 150 mm thickness of noncombustible insulation e g fiberglass A maximum of 10 0 3 m of a vertical sprig may extend above the insulation to supply Model GP56 sprinklers Note Where Reliable Attic Sprinklers are installed on wet pipe sprinkler systems with CPVC pipe the CPVC pipe must be protected in accordance with the pipe manufacturer s installation instruction a...

Страница 26: ... Series sprinklers Branch lines over joists must be protected with a minimum 6 150mm thickness of noncombustible insulation e g fiberglass either within the joist bay or on top of the joists A vertical sprig of any length may extend above the insulation to supply Model AH Series sprinklers Caution 1 Insulation required by Figures 30 and 31 is for fire protection purposes and not for freeze protect...

Страница 27: ...system maintained in accordance with NFPA 25 as well as the requirements of any Authorities Having Jurisdiction Prior to installation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do not clean sprinklers with soap and water ammonia liquid or any other cleaning ...

Отзывы: