5.6 Parameterization
Normally the configuration program provides an input box for the IO-Controler with
which the user can enter parameter data or select from a list. The structure of the
input box is stored in the device master file.
●
Danger of death, serious physical injury and/or damage to property
due to malfunction, caused by incorrect parameterization!
The system manufacturer must ensure correct functioning by carrying
out a protected test run during commissioning and after each parameter
change.
5.6.1 F-Parameters (F_Par)
The F-Parameters supported by the measuring system are listed below.
Byte order = Big Endian
Byte
Parameter
Type
Description
Page
X+0
-
Bit
Bit 0 = 0: not used
-
F_Check_iPar
Bit
Bit 1 = 0: No check
F_SIL
Bit range
Bit 3-2
00: SIL1
01: SIL2
10: SIL3 [default]
11: no SIL
F_CRC_Length
Bit range
Bit 5-4
00: 3-Byte-CRC
X+1
F_Block_ID
Bit range
Bit 5-3
001: 1
F_Par_Version
Bit range
Bit 7-6
01: V2-Mode
X+2
F_Source_Add
Unsigned16
Source address, Default = 1
Range: 1-65534
X+4
F_Dest_Add
Unsigned16
Destination address,
Default = 1
Range: 1-99
X+6
F_WD_Time
Unsigned16
Watchdog time, Default = 125
Range: 125-10000
X+8
F_iPar_CRC
Unsigned32
CRC of i-Parameters,
Default = 1132081116
Range: 0-4294967295
X+12 F_Par_CRC
Unsigned16
CRC of F-Parameters,
Default = 17033
Range: 0-65535
5.6.1.1 F_Check_iPar
The parameter is set to "NoCheck" and cannot be changed. This means the check
sum value is not evaluated about the iParameters.