RelaDyne LubriMist DXT Скачать руководство пользователя страница 6

 

77740212 REV 2   August 2020 

 

CAUTION 
Maximum discharge temperature is 160° F.  If temperature rises to 155° 
F open the air pressure bleed valve and reduce the air blower discharge 
pressure. 

 
7) When return header vacuum assist is used, close the vacuum vent gate valve to 
achieve the desired return header setting.  Monitor the user provided instrument 
while making adjustments to the desired setting. 
 
 

WARNING 

If return header vacuum assist is utilized, mist venting may become 
restricted if the blower operation ceases.  Manual bypass and venting 
configurations should be devised by the user for emergency use if mist 
venting becomes inadequate when blower operation stops. 

 
8) If the reclaimed oil is to be re-supplied to the Oil Mist Generator having an 
automatic bulk fill feature, turn on the air supply to the oil pump and adjust the air 
pressure regulator to read 40 - 55 PSIG.  If the reclaimed oil is to be disposed, 
manually turn on and adjust the air supply each time the reservoir is to be emptied. 
 
9) Once the Unit is in operation and stable, no further adjustments are necessary. 
 

Operation: 

Once commissioned, the daily operation of the DXT requires no additional 
adjustment.  Except for systems operating with vacuum assist, the DXT reservoir is 
designed to provide unrestricted venting should the blower cease operation. 
 
See the Oil Mist Generator O&M manual for system operation. 
 

Trouble Shooting 

1.Normal operation is indicated with the air blower discharge temperature at less 
than 160° F and no visible mist escaping from the air vent located through the oil 
filter end cap. 
2. If discharge temperature increases above 155 - 160° F, readjust the discharge 
pressure bypass valve to lower the discharge pressure.  Decrease discharge 
pressure incrementally and allow the temperature to decrease and stabilize.  If 
temperature cannot be lowered without creating a visible mist emission, the filter 
element has become loaded with particulate and must be changed.  Filter elements 
in units using vacuum assist may become loaded with particulate at intervals sooner 
that the recommended filter replacement interval. 
3. If over a period of use, small amounts of oil mist become visible in the air exhaust, 
close the discharge pressure bypass valve.  Monitor the discharge pressure to 
insure that the discharge temperature does not exceed 155 to 160° F. 
 
 
 
 

Содержание LubriMist DXT

Страница 1: ...odel DXT Oil Mist Generating System Installation and Operating Manual Revision History Rev 1 1 Added Vacuum assists as standard 2 Updated drawings and BOM 235 273 is not in M2M replaced by 77500843 fa...

Страница 2: ...on is prohibited except as allow under the copyright laws The information contained in this document is subject to change without notice The manufacturer makes no warranty of any kind with regard to t...

Страница 3: ...s the bulk oil supply necessary to maintain the proper working oil level in the oil mist generator It is equipped with an oil level gauge for monitoring the reservoir oil level in the demisting tank r...

Страница 4: ...4 NPT If the Oil Mist Generator has been pre mounted to the DXT a common inlet air supply may be provided Inspect the unit and locate the inlet air supply connection The pump oil discharge connection...

Страница 5: ...nerator fill the reservoir with quality oil suitable for oil mist lubrication WARNING Maximum DXT reservoir charge volume is 55 US gallons Do NOT Overfill 4 Ensure that the vacuum vent gate valve is i...

Страница 6: ...re necessary Operation Once commissioned the daily operation of the DXT requires no additional adjustment Except for systems operating with vacuum assist the DXT reservoir is designed to provide unres...

Страница 7: ...77740212 REV 2 August 2020 6 Model DXT Parts List...

Страница 8: ...77740212 REV 2 August 2020 7 Model DXT Dimensions...

Отзывы: