5.5

Vacuum pipe

Laying pipes in adjacent rooms (e.g. cellar, 
garage) can be done via mounting on the 
surface under the ceiling or on the wall. 
Use a surface mounted suction socket for 
this.

Laying in screed is not permissible, as it 
can shorten due to the temperature and 
impact sound insulation. This could cause 
leaks at the transition point of the vacuum 
pipe from the screed to the masonry.

Laying in the outer insulation of a building 
is not permissible.

Install vacuum pipes DN 50 in wall slots of 
at least 80 x 80 mm.

Take static requirements of the masonry, 
especially for horizontal slots, into account 
during planning and execution.

Make wall slots in such a way that the 
pipeline can be laid without being 
tensioned.

Before plastering in, surround pipes and 
fittings on all sides with flexible materials 
such as corrugated cardboard, mineral or 
glass wool or commercial insulation tubes.

Protect pipes and fittings from the effects 
of high temperatures with appropriate 
measures (insulation) at points where 
temperatures over 100 °C are reached 
due to external influences.

When laying the pipes and fittings, ensure 
that the sleeves point against the direction 
of flow.

If installed in a suspended ceiling, check 
whether it runs through an inhabited area. 
If this is the case, attach additional 
insulation.

Laying in concrete

The static condition may not be impaired by 
laying in concrete.

Ask a professional for advice before 
starting the work.

If cementing in is permissible, secure the 
pipe sections in such a way that a change 
in position is prevented during cementing.

To prevent penetration of cement slurry, 
close the sleeve gaps with tape.

Close pipe openings.

The total weight of the cement may not be 
supported by the pipeline. We strongly 
advise being very careful when committing 
the pipes and fittings to a position, e.g. during 
cementing.

Make provisions for the dissipation of the 
load in accordance with technical 
guidelines, e.g. spacers for reinforced 
steels, carrying boxes (folded sheet-metal 
edges), consoles etc.

Fig. 5-12:

Installation diagram for laying in concrete

Warning!

Risk of death!

Disregarding the fire-protection 
regulations and measures risks death and 
severe burns to users/tenants. 

Observe fire-protection regulations and 
building codes of practice/regulations.

Observe the national regulations for 
cut-outs and slots in the masonry.

REHAU recommend acoustically 
decoupling the line from the main 
structure with commercially available, 
moisture-protective impact-sound 
insulation (S > 4 mm).

Use joints for the transition into the wall 
slot.

1

Wall

2

Unfinished floor

3

Insulation

4

Screed

5

Carpet

5

4

3

2

5

123
100
ø70

1

Содержание VACUCLEAN 2000

Страница 1: ...dfsdfdsfdsf REHAU VACUCLEAN The Central Vacuum Cleaner System Technical information 885 600 Ex e Valid as from April 2005 Subject to technical modifications...

Страница 2: ...2...

Страница 3: ...8 5 9 Operation via control cable 29 5 9 1 System components 29 5 9 2 Installation information 30 5 9 2 1 Control cable 30 5 9 2 2 Vacuum pipe 30 5 9 2 3 Suction socket 32 5 9 2 4 Floor socket 33 5 9...

Страница 4: ...4...

Страница 5: ...t and the cutting tool Never put your hands near the area where the tool is cutting or on moving parts When performing service maintenance and conversion work and when changing the installation site a...

Страница 6: ...6...

Страница 7: ...lters This is important for those with dust allergies and asthma who would immediately notice the difference with common vacuuming methods The air full of debris is transported from the individual suc...

Страница 8: ...tral vacuum unit with the ON button of the radio sender unit Sweep waste to be sucked up into the Vac Pan Switch off central vacuum unit with the OFF button of the radio sender unit Close Vac Pan 1 3...

Страница 9: ...ets in the overlap areas shaded green see Fig 2 2 If two circles overlap Install a suction socket in each overlap area For optimal use of the working radius of the suction hose Select the final positi...

Страница 10: ...xhaust gas silencer Suction pipe 15 0 m Exhaust air pipe 3 0 m 45 bend 3 5 m seven pc 0 5 m equivalent length each 90 bend 1 0 m one pc 1 0 m equivalent length Branch 0 5 m one pc Design length 23 0 m...

Страница 11: ...vacuum unit is provided for each flat in a multi family dwelling All central vacuum units can be installed on the cellar level The exhaust air pipes of the individual central vacuum units can be combi...

Страница 12: ...lated from the average cleaning performance A 200 m2 h the area to be cleaned F and the specified cleaning time t R F t x A Select central vacuum units taking into account the distance to the furthest...

Страница 13: ...igned for vacuuming household dust in buildings When using REHAU VACUCLEAN in commercial buildings or multi family dwellings with larger areas or several floors please contact our applications departm...

Страница 14: ...14...

Страница 15: ...hotocopier toner printer toner or soot Toner and soot may be electrically conductive Explosion and fire hazard Do not use the system for cleaning up lit cigarettes hot ash lit matches or similar mater...

Страница 16: ...ot Secure mounting frame vertically in the wall Reinsert suction socket adapter Fig 5 2 Installed mounting frame Fig 5 3 Mounting frame with plaster cover In order to plaster attach the plaster cover...

Страница 17: ...ox 30 cm above the finished floor Fig 5 5 Installation in solid walls 1 Solid wall 2 Plaster 3 Mounting frame 4 Suction socket adapter 5 Suction socket 6 Suction socket connecting bend DN 50 90 with s...

Страница 18: ...ightweight walls variation 2 1 Lightweight wall 2 Chip board 3 Gypsum plate 4 Mounting frame 5 Suction socket adapter 6 Suction socket 7 Suction socket connecting bend DN 50 90 with suction socket ada...

Страница 19: ...d see Fig 5 8 Fig 5 8 Connection of vacuum pipe with access from the front Position Vac Pan Attach accompanying pipe bend align it and fit it to the pipeline Screw in Vac Pan with cover blind at the i...

Страница 20: ...her it runs through an inhabited area If this is the case attach additional insulation Laying in concrete The static condition may not be impaired by laying in concrete Ask a professional for advice b...

Страница 21: ...pass through expansion and building joints Use joints for the transition The pipe sleeve rests on the expansion joint Fig 5 14 Installation diagram for building joints 1 Wall 2 Unfinished floor 3 Insu...

Страница 22: ...the rest of the pipe use two 45 bends or 45 branches with less flow resistance see Fig 5 15 Fig 5 15 Installation example Shorten pipes with a fine tooth saw and a mitre box for a right angle cut Debu...

Страница 23: ...er unit behind steel doors If this cannot be avoided the radio receiver unit must be installed at a site with favourable reception outside the room with the steel door Do not install radio receiver un...

Страница 24: ...NO Plus DN 75 to the exhaust air port on the central vacuum unit see Fig 5 24 Install an exhaust air silencer in each exhaust air pipe between the central vacuum unit and the wall duct see Fig 5 23 an...

Страница 25: ...showing central vacuum unit types 2000 and 3000 Fig 5 24 Mounting example showing central vacuum unit type 4000 A Recommended spacing A Recommended spacing A 1 8 m min 2 m max 5 m max 10 m 2 2 A 1 8...

Страница 26: ...the appliance switch see Fig 5 27 Connect the central vacuum unit s mains plug to the radio receiver unit socket When the red LED lights up on the radio receiver unit press the OFF button on the radio...

Страница 27: ...of an extension cable into a socket near the radio receiver unit Hold the repeater against the housing of the radio receiver unit so that it makes contact with it see Fig 5 29 and plug it into the ex...

Страница 28: ...entral vacuum unit can no longer be switched on Fig 5 30 Deleting the radio sender unit at the radio receiver unit Deleting the radio sender unit at the repeater Procedure see Deleting the radio sende...

Страница 29: ...75 mm2 Length 15 m VACUCLEAN control module 249900 002 Material ABS Colour Grey VACUCLEAN Basic suction set K 246290 001 Consists of Suction hose 8 meters Hand tube with suction air regulation Telesco...

Страница 30: ...especially for horizontal slots into account during planning and execution Make wall slots in such a way that the pipeline can be laid without being tensioned Before plastering in surround pipes and f...

Страница 31: ...ot lie in a separate cable conduit ensure permanent strain relief for the control cable by forming loops At low temperatures RAU PP mineral reinforced becomes brittle like any other material and is th...

Страница 32: ...ble Item No 243472 001 project approx 20 cm see Fig 5 35 In order to plaster attach the plaster cover Item No 242767 001 see Fig 5 36 while laying the control cable into the cavity of the plaster cove...

Страница 33: ...lls When connecting the pipeline from the front Make an opening with a width 165 mm and height 95 mm for the vacuum pipe and use the enclosed cover blind see Fig 5 38 Fig 5 38 Connection of vacuum pip...

Страница 34: ...l cable to the contact plug and fasten it with screws Plug the control module into the earthed socket outlet see Fig 5 43 Plug the contact plug into the control module bottom and fastened it with scre...

Страница 35: ...5 44 Block diagram control cable 1 Cable connection e g through lamp wire connectors A Under roof floor 2 Suction socket B Upper level 3 Control cable 2 core C Ground floor 4 Control module D Cellar l...

Страница 36: ...vacuum unit is equipped with a suction relief valve for safety purposes i e to prevent excessive suction in the system The check light LED on the radio receiver unit may not illuminate Safety functio...

Страница 37: ...wn remove clog if necessary then switch on again Central vacuum unit does not start Central vacuum unit is not switched on Switch on central vacuum unit Battery of radio sender unit empty Replace batt...

Страница 38: ...38...

Страница 39: ...h a way that the handle is aligned centrally horizontally Close securing clamp and lock clamping lever Reattach emptied waste container at housing and secure it by closing the latch closures Warning R...

Страница 40: ...via your dealer or public collection facilities 7 5 Checking and cleaning the suction sockets and wall vacuum connection Vac Pan Regularly remove dirt which clings inside the suction sockets and Vac P...

Страница 41: ...surement voltage without allowing for tolerances 28 32 32 Maximum volumetric flow1 m3 h 220 240 2 x 240 Thermal cut out Yes Yes Yes Vacuum valve Yes Yes Yes Running hours meter No Yes Yes Cyclone filt...

Страница 42: ...42...

Страница 43: ...are free from residue Check that suction socket covers close completely Check list for suction hose Check that suction hose is not cracked 3 Deficiencies established and rectified Servicing conducted...

Страница 44: ...Ontario L7M 1K5 Tel 9 05 3 35 32 84 Vancouver 26620 56th avenue Unit 102 Langley BC V4W 3X5 Tel 6 04 6 26 46 66 Winnipeg 11 Plymouth Street Unit 100 Winnipeg Manitoba R2X 2V5 Tel 2 04 6 97 20 28 GB B...

Отзывы: