  Installation 

The REHAU room unit is designed as an electronic temperature controller of 
warm water heating systems and serves to control electrothermal actuators 
or other electrical devices as appropiate.  The maximum switching current 
indicated in the technical data must be observed! REHAU cannot accept any 
liability for any form of misuse.

The electrical installation must be carried out in accordance to the current 
wiring regulations in force and must be in accordance with the connection 
plan.  Only approved certifi ed professionals may carry out the installation. 
Further more the installation is always to be carried out with the power supply 
disconnected.

Position the room unit such that it is not covered by curtains, pieces of furni-
ture or other objects. The control should not be installed close to heat sources 
(i.e. lamps, fi replaces/chimneys, direct sunlight etc.) and positioned away from 
draughts. Ensure that it is fi tted on a fl at, solid surface that is non-conductive 
between 1.2 - 1.5m off  the ground fl oor. This allows the room temperature to 
be exactly measured and correspondingly precisely controlled.

  Wall mounting

Before mounting the wall unit, take off  the housing cover from the base plate. 
1. Remove the screw on the underside 
2. Open the housing by lifting the housing cover on the bottom edge 
    and then lifting it.
Now fi rmly mount the base plate on the wall or the fl ush-mounted socket with 
the screws provided.

  Connection

Wire the room unit in accordance with the following connection plan:

REHAU Star 30       230 V version

Terminals

 

temperature Setback

N

Neutral conductor supply feed

L

230 V AC supply

Switching output (valve actuator, terminal strip)

Jumper settings

Diff erent REHAU Star 30 features can be switched ON or OFF using the jump-
ers shown:

REHAU Star 30 jumpers

Switch

Feature

ON

OFF

VP

Valve protection feature

PWM

Pulse-Width-Modulation

 

Temperature reduction

The unit comes factory supplied with all jumpers set to ON.  You can change 
the settings in accordance with your requirements, by moving the jumpers 
onto contact pins as above, ensure that jumpers are fi tted i.e. in the correct 
notation, and not removed.

 Replace the cover in the reverse order to above.

Operation

The REHAU Star 30 Digital room controller is used for regulating the tem-
perature in dry, enclosed rooms with a normal environment and maximum 
humidity of 95% (non condensing). 
The desired temperature can be quickly and easily adjusted with the push 
buttons. This electronic control system ensures that the set room tempera-
ture is maintained without fl uctuation and when required a time signal input  
automatically activates a reduction in temperature (night setback).

Each time you press any button, the display’s illumination will automatically 
switch on.  If there is no adjustment made then after 5 seconds, the illumina-
tion will switch off  again automatically. 
Pressing the + or – buttons this will take you to the display of the desired 
temperature setpoint.  Here you can modify this temperature by pressing 
the + or – button repeatedly, in steps of 0.5K, until you reach your desired 
setpoint temperature. 

Note:- It is not possible to set temperatures of below 10°C or above 
35°C.

If there is no activity for more than 5 seconds, the controller will automati-
cally adopt the amended desired temperature and will revert to the standard 
display.
If a timer is connected and temperature set back is active, this will be dis-

played by a

symbol in the display.  If the controller calls for heat because 

the actual temperature is below the desired temperature set, 

this will be indicated by

symbol in the display. 

 

REHAU Star 30 Symbol

Meaning

 

Temperature setback active

Heat required

  

 

     

blinking

Frost protection mode active

Cleaning 

Never use anything other than a soft, dry cloth to clean the unit. Never use 
any cleaning agents containing solvents or any sharp objects to clean the 
unit.

Technical Data

230V

Article No:

206028

Operating Voltage:

230VAC / 50Hz

Max. switching current:

10 (3) A

Hysteresis:

0.5K

Protection Rating:

IP 30

Dimensions W/H/D:

75mm/75mm/30.5mm

Temperature range:

10°C to 35°C

Storage temperature:

-25°C to 65°C

CE Approved

UK & IRELAND SALES OFFICES

London, 

REHAU Ltd, The Building Centre, 25 Store Street, London WC1E 7BT 

Slough

, Units 5 J & K, Langley Business Centre, Station Road, Langley, Slough SL3 8DS Phone: 

01753 588500 Fax: 01753 588501 

Glasgow,

 Phoenix House, Phoenix Crescent, Strathclyde Business Park, Bellshill, North Lanarkshire ML4 3NJ Phone: 01698 503700 Fax: 

01698 503701 

Dublin

, 9 St. Johns Court, Business Park, Swords Road, Santry, Dublin 9 Phone: 00353 (0)1 8165020 Fax: 00353 (0)1 8165021

Отзывы: