A mains socket or circuit breaker shall be located close to the appliance and shall be easily accessible.
•
Never disconnect the 230 V power supply to PG 600 SX when it is running - the earth protection of both
PG 600 SX and the connected load would be interrupted.
•
Check that when all loads are connected, the total earth leakage current does not exceed 2.7 mA (EN
62040-1-1).
•
After PG 600 SX gets connected to the power grid, the battery recharging starts. At this point also the
cooling fan starts. After the battery is fully charged and the inner temperature in PG 600 SX does not
rise any more, the fan will not start again
.
•
In case of a power supply breakdown, the fan turns on, cooling the inverter if needed.
•
When power supply is restored, the timer turns on and the cycle is repeated.
3.
OPERATING STATES OF PG 600 SX
Power grid operation
The input voltage is shown on the screen, the battery is being recharged or is already fully charged.
Battery operation
The screen shows no power grid voltage. The symbol of battery operation is shown. PG 600 SX will provide backup
until either power supply is restored or the battery completely discharged. When the threshold of 24% is reached, the
battery starts making intermittent alarm sound. From the moment on, the PG 600 SX may turn off any time depending
on the load level. After the power supply is restored, it takes at least 12 hours (preferably 24) to fully charge the battery.
Alarm
The alarm symbol is shown and PG 600 SX makes a sound. When overloaded, PG 600 SX will disconnect the output
and make a continuous sound. Until the load is disconnected and PG 600 SX turned off and on again, it will not fulfil its
backup function. The sound alarm will start when the battery level falls to 24%.
4.
TROUBLESHOOTING
Situation
Cause
Solution
The screen is not lit
●
PG 600 SX
is off.
●
No grid power, discharged battery.
●
Defect battery
.
●
Press and hold ON push button,
switching PG 600 SX on
.
●
Restore power supply and let the battery
recharge. Eventually check the fuse.
●
Replace the battery
.
The screen is lit but the
connected load (pump) is not
running
●
PG 600 SX
has been switched off,
disconnecting the load.
●
Fault
●
Check battery condition and connection
●
Contact service staff
Grid voltage is present but PG
600 SX displays zero grid
voltage and works in the battery
mode.
●
PG 600 SX gets no grid power.
●
Electrical socket is defect
●
Check the circuit breakers/fuses.
●
Check the el. Socket.
●
Faulty fuse
●
Replace the fuse
PG 600 SX
does not serve
the expected backup time
Battery capacity may be reduced:
●
Too long storage time
●
Overload
●
Battery lifetime over
●
Repeated frequent power
failures when the battery
does not get fully charged
again
●
Let the battery charge for about 8 hours
●
Disconnect excess load
●
Replace the battery
Sound alarm (signal)
sounds every 0.5 sec.
●
Overload
●
Check what is connected to PG 600 SX
and disconnect excess load.
Sound alarm (signal)
sounds continuously and
then PG 600 SX turns off
●
Discharged battery
●
Restore power supply and let the battery
recharge.