background image

REGULUS - PG 500 Compact - www.regulus.eu

1 ESSENTIAL INFORMATION

This UPS of PG Compact series is intended preferably to power supply circulation pumps in heating systems.

THE APPLIANCE OPERATES WITH VOLTAGE DANGEROUS TO HUMAN LIFE. PLEASE STICK TO SAFETY 

INSTRUCTIONS GIVEN IN THIS GUIDE.

DO NOT DISMANTLE THE UPS COVER! THE COVER MAY BE DISMANTLED BY A QUALIFIED PERSON ONLY.

The load shall not exceed the inverter power output of 600 W.

The appliance is designed for indoor use.

It is not designed for outdoor operation, nor for operation in explosive environment.

Never charge very cold batteries (exposed to freezing temperatures).

The unit shall be placed in a sufficiently ventilated space. Ventilation openings shall not be covered and air 

intake shall not be obstructed.

Plug the power supply cable directly to a local wall socket. Do not use any extension cables.

1.1 General Decription

When the unit is power-supplied from the grid, the electricity runs via its internal bypass directly to its 

outlet socket. At the same time, the battery is being charged. In case of a power failure, the inverter turns 

on and the load is fed from the integrated batteries. During charging, the temperature of the unit may rise 

to circa 45 °C (normal operation state).

NOTE! MORE APPLIANCES MAY BE CONNECTED BUT ONLY WITH RESPECT TO THE POWER OUTPUT OF 

THE PUMP. OF COURSE, WITH A HIGHER LOAD CONNECTED, THE BACKUP TIME GETS SHORTER.

The appliance connects to the power supply with a standard power cord with wall plug. The load is power 

supplied via the 230 V socket.

WARNING! WHEN TESTING A PUMP BACKUP, NEVER UNPLUG THE PG 500 COMPACT FROM ELECTRICAL 

SOCKET. DOING SO WOULD INTERRUPT THE PE LINE. DE-ENERGIZING SHALL BE DONE BY A CIRCUIT 

BREAKER OR A FUSE. MAKE SURE THE PUMP IS CONNECTED IN TN-S SYSTEM, i.e. three-wire system 

(L, 

N and PE)

.

When running from the battery, the LED marked “BACKUP” is lit. If the battery voltage falls to a low level, an 

acoustic alarm sounds prior to disconnecting.

WARNING 

– Whenever handling a battery, the unit shall be turned off and disconnected from the power 

supply.

Features of the UPS

Fast automatic line-to-battery switching

Built-in battery charger.

Intelligent charger control with battery overload and overcharge protection.

Protection against overload, battery overcharge and overheating.

LED indications and buzzer alarms.

The backup power supply may be disconnected from the mains only after the batteries are fully 

charged. A battery can be considered fully charged when there were no power cuts for two days. 

Storing a discharged battery will cause its definite destruction!

Содержание PG 500 Compact

Страница 1: ...www regulus eu PG 500 Compact PG 500 Compact EN Installation Wiring and Operation Manual PG 500 Compact Backup Power Supply...

Страница 2: ...3 2 INSTALLATION OPERATION 4 2 1 Description 4 2 2 Position of the unit 4 2 3 Recommended wiring 5 2 4 Commissioning 10 2 5 Turning on PG Compact with no grid power 10 2 6 Battery replacement 10 3 UNI...

Страница 3: ...may rise to circa 45 C normal operation state NOTE MORE APPLIANCES MAY BE CONNECTED BUT ONLY WITH RESPECT TO THE POWER OUTPUT OF THE PUMP OF COURSE WITH A HIGHER LOAD CONNECTED THE BACKUP TIME GETS S...

Страница 4: ...ect sunlight Do not leave the unit in excessively hot environment Do not expose the unit to excessive moisture Do not leave the unit in a dusty place ON OFF push button Red backup battery operation Or...

Страница 5: ...50 Hz CIRCUIT WITHOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation between t...

Страница 6: ...NS 230 V 50 Hz CIRCUIT WITHOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation...

Страница 7: ...0 V 50 Hz CIRCUIT WITHOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation betwe...

Страница 8: ...Backup of a fireplace circulation pump with flue thermostat PG 500 COMPACT BACKUP POWER SUPPLY W INTEGRATED BATTERIES MAINS 230 V 50 Hz PUMP WITH BACKUP FLUE THERMOSTAT 8 REGULUS PG 500 Compact www r...

Страница 9: ...led pump PG 500 COMPACT BACKUP POWER SUPPLY W INTEGRATED BATTERIES MAINS 230 V 50 Hz STDC TRS etc controller PUMP WITH BACKUP PG 500 COMPACT BACKUP POWER SUPPLY W INTEGRATED BATTERIES MAINS 230 V 50 H...

Страница 10: ...l blink twice The unit is then ready for operation Silent mode During battery operation short pressing the ON OFF button will turn on off the buzzer alarms The Weak battery alarm cannot be switched of...

Страница 11: ...e the load Some of the connected devices may be short circuited Check if the power grid voltage corresponds to the values required Contact service staff Red LED is lit and the signal sounds every 8 se...

Страница 12: ...orking temperature 0 40 C Ambient relative humidity 0 90 non condensing Noise level quiet operation no fan 6 MAINTENANCE PG 500 Compact does not require any special maintenance Disconnect it from the...

Отзывы: