Technical Data

Power supply

CR123A 3V lithium battery x 2

Battery life

5 years

1

Frequency

868 MHz

Protection class

IP54

Measuring range, temperature

-40…+50 °C

Measuring range, temperature (ex-
ternal PT1000)

-50…+75 °C

Accuracy, temperature

±0.2 K

Dimensions (WxHxD)

90 x 85 x 35 mm

1. Battery life is calculated with 288 wake-ups and 120 value updates per day.

Installation

1. Open the cover by pressing the locking tab carefully with a

screwdriver.

2. Insert two CR123A lithium batteries in the battery compartments.

3. Pair the receiver and sensor if necessary. See description in the

variable list for the receiver RCW-M32.

4. Ensure that the receiver and sensor are paired by pressing the

Test

button

shortly while studying the LED indications. See

Handling

.

5. Make a signal strength test as described under

Handling

.

6. Connect the external PT1000 sensor if used.

7. Mount the sensor on a wall using the mounting holes.

8. Snap on the cover.

Number

Description

1

Battery compartments

2

Mounting holes

3

Test button

4

LED light

5

DIP switches

6

Terminal for external PT1000 sensor

Wiring

DIP switch

Description

1

Frequency
OFF = 868.6375 MHz (used in Europe)
ON = 868.2375 MHz (used in China)

2

Internal/external sensor
OFF = Internal
ON = External

Settings

The temperature is measured at an adjustable time interval called

wake

up time

. If a measured value changes more than the specified limit it will

send a signal to the receiver. The sensor will always send a signal to the
receiver every 95 - 110 minutes. If the receiver does not receive a signal
from the sensor within a specified time interval it will indicate

out of

signal

.

For default time values, limits and how to modify them see the variable
list for the receiver.

N

No

ottee!! Changing the time intervals will influence the battery life time.

Handling

Signal strength test

Test the signal strength to optimise the installation:

1. Push the

Test button

(approx. 7 s) on a paired sensor until the LED

first shines with a solid light. After that the LED behaviour will
depend on the connection quality.

– Long flash with short pause = Very good connection

(-20…-50 dB)

– Short flash with short pause = Good connection (-50…-90 dB)

– Flash with long pause (1 s) = Bad connection (< -90 dB)

– No LED = Out of range or time-out for test sequence

2. Test in different locations to optimise the connection before

installing the unit.

The test sequence lasts for 1 minute.

LED indications

– 3 flashes (when

Test button

is pressed): The sensor is not paired with

the receiver.

– Flashing (when

Test button

is pressed): The sensor is paired with the

receiver.

– Flash every 4 seconds: Batteries need to be replaced.

Function

The outdoor temperature sensor is designed to work together with
Regin's wireless receiver RCW-M32 with Modbus communication.

This product carries the CE-mark. More information is available at
www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]