Technical Data
Power supply
CR123A 3V lithium battery x 2
Battery life
5 years
1
Frequency
868 MHz
Protection class
IP54
Measuring range, temperature
-40…+50 °C
Measuring range, temperature (ex-
ternal PT1000)
-50…+75 °C
Accuracy, temperature
±0.2 K
Dimensions (WxHxD)
90 x 85 x 35 mm
1. Battery life is calculated with 288 wake-ups and 120 value updates per day.
Installation
1. Open the cover by pressing the locking tab carefully with a
screwdriver.
2. Insert two CR123A lithium batteries in the battery compartments.
3. Pair the receiver and sensor if necessary. See description in the
variable list for the receiver RCW-M32.
4. Ensure that the receiver and sensor are paired by pressing the
Test
button
shortly while studying the LED indications. See
5. Make a signal strength test as described under
.
6. Connect the external PT1000 sensor if used.
7. Mount the sensor on a wall using the mounting holes.
8. Snap on the cover.
Number
Description
1
Battery compartments
2
Mounting holes
3
Test button
4
LED light
5
DIP switches
6
Terminal for external PT1000 sensor
Wiring
DIP switch
Description
1
Frequency
OFF = 868.6375 MHz (used in Europe)
ON = 868.2375 MHz (used in China)
2
Internal/external sensor
OFF = Internal
ON = External
Settings
The temperature is measured at an adjustable time interval called
wake
up time
. If a measured value changes more than the specified limit it will
send a signal to the receiver. The sensor will always send a signal to the
receiver every 95 - 110 minutes. If the receiver does not receive a signal
from the sensor within a specified time interval it will indicate
out of
signal
.
For default time values, limits and how to modify them see the variable
list for the receiver.
N
No
ottee!! Changing the time intervals will influence the battery life time.
Handling
Signal strength test
Test the signal strength to optimise the installation:
1. Push the
Test button
(approx. 7 s) on a paired sensor until the LED
first shines with a solid light. After that the LED behaviour will
depend on the connection quality.
– Long flash with short pause = Very good connection
(-20…-50 dB)
– Short flash with short pause = Good connection (-50…-90 dB)
– Flash with long pause (1 s) = Bad connection (< -90 dB)
– No LED = Out of range or time-out for test sequence
2. Test in different locations to optimise the connection before
installing the unit.
The test sequence lasts for 1 minute.
LED indications
– 3 flashes (when
Test button
is pressed): The sensor is not paired with
the receiver.
– Flashing (when
Test button
is pressed): The sensor is paired with the
receiver.
– Flash every 4 seconds: Batteries need to be replaced.
Function
The outdoor temperature sensor is designed to work together with
Regin's wireless receiver RCW-M32 with Modbus communication.
This product carries the CE-mark. More information is available at
www.regincontrols.com.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]
1
+
-
+
-
6
ON
2 (x4)
3
4
5
1
2
TG-R6EW
1