background image

INSTRUCTION

i

Read this instruction before installation  

of the product

TG-R5W

1

   

2

3

4

1

+

-

+

-

2

 

Pairing the sensor with the receiver

Look in the receiver instruction for information on how to pair the sensor 
with the

 

receiver.

Pairing/connection test

The connection to the receiver must be tested before mounting the sen-
sor.

1.  Place the receiver and the sensor at the desired locations.

2.  For RCW-M: Put the receiver into 

Programming

 mode 

For RCW-M32: Push the 

Test button

 to activate the display.

3.  Perform a

 Walk test

: Press the 

Test button

 on the sensor to see if the 

location is within signal range of the receiver. The LED light will indi-

cate if the sensor is paired with the receiver or not. There will also be 

a long beep from the receiver when the sensor is paired successfully.

LED light

3 flashes

 (

When 

Test button

 is pressed):  

The sensor is not paired with the receiver.

Flashing (When 

Test button

 is pressed):  

The sensor is paired with the receiver.

Flash every 4 seconds

:

  

Batteries need to be replaced.

Mounting the sensor

The sensor should be mounted in an open space with good air circulation, 

and at a height of 1.2 to 1.4 meters.

1.  Use the screw holes to mount the sensor on the wall

2.  Snap on the cover

TG-R5W

Wireless room temperature sensor

TG-R5W is a wireless room temperature sensor that monitors tem-
perature and sends a signal to a Regin Modbus receiver.

Commissioning

For optimal temperature monitoring, the sensor should be mounted in 

an open space with good air circulation, and at a height of 1.2 to 1.4 
meters.
The sensor must be paired with the receiver before it can be used.

Installation of batteries

1.  Open the cover by pressing the locking tab carefully with a 

screwdriver

2.  Insert two 1.5 V L91 Lithium batteries

Other functions

Temperature detection

The sensor monitors the temperature at a preset time interval (factory 
setting is 2 minutes), and if the temperature has changed by more 
than ± 0.2°C it will send a signal to the receiver. If the temperature is 
stable, the sensor will transmit a signal every 95-115 minutes.

Self test

The sensor

 

will automatically send a supervisory signal to the receiver 

at an interval of 95 to 115 minutes to test the signal. 
The receiver will indicate “out of signal” if it has not received the 
signal at a preset interval.

Technical data

Power supply 

 

1.5 V L91 Lithium x 2

Battery lifetime 

 

10 years

Frequency 

 

868 MHz

Operating temperature 

-10...+50°C

Operation humidity  

Max. 85 % RH (non-condensing)

Protection class   

IP30

Dimensions (HxWxD) 

86 x 86 x 30 mm

 

This product carries the CE mark. For more information, see  
www.regincontrols.com. 

Product documentation 

All documentation can be downloaded from www.regincontrols.com

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

1281

1E

 

MAR 19

EN

Number Description

1

Battery  
compartments

2

Screw holes

3

Connection/
Test button

4

LED light

Отзывы: