Regin RU-FO Скачать руководство пользователя страница 3

Regin product information

Regin product information

3

Technical data

Supply voltage 

 

  Fed from RCP 

Ambient temperature 

 

  0...50°C 

Storage temperature 

 

  -20...+70°C 

Ambient humidity 

 

  Max 90% RH 

Protection class 

 

  IP20 

Communication 

 

  Same as RCP 

Built-in temperature sensor 

  NTC type, measuring range 0...50°C, ac/-0.5°C at 15...30°C 

Material, casing 

 

  Polycarbonate, PC 

Weight 

 

  110 g 

Colour 

 

  Cover: Polar white RAL9010 

 

 

  Bottom plate: Light gray 

Cable for connection between RU and RCP  Type RJ12, max length 30 m.  
   Cables that can be ordered from Regin     RU-CBL3 (length 3 m) 
 

 

  RU-CBL10 (length 10 m) 

 

 

  This product conforms with the requirements of European EMC standards  

 

 

  CENELEC EN 61000-6-1 and EN 61000-6-3, and the requirements of    

 

 

  European LVD standard IEC 60 730-1. It carries the CE mark.

Inputs and outputs
In RCP
 
Terminal blocks in RCP   

  So-called lift type for cable cross-section 2.1 mm

2

Setpoint settings via Regio Tool

©

Basic heating setpoint 

 

  5...40°C 

Basic cooling setpoint 

 

  5...50°C 

Setpoint displacement 

 

  +/-0...10°C (FS = +/-3°C)

Basic heating setpoint, setting with dipswitches
The ON-position is marked on the dipswitch. The cooling setpoint is 2°C higher.

Basic setpoint, heating (°C)

SW1

SW2

20

OFF

OFF

22 (FI)

OFF

ON

24

ON

OFF

26

ON

ON

Other dipswitches

ON

OFF

Comment

SW3

Stand-by

Occupied (FI)

Preset operating mode

SW4

-

-

Not used

Содержание RU-FO

Страница 1: ...ely programmable controllers with communication Applications The Regio controllers are suitable in buildings where you want optimal comfort and low energy consumption for example offices schools shopping centres airports hotels and hospitals etc Design The room units have a modern design The design has been awarded the 2007 iF product design award Sensor The room unit has a built in sensor Easy to...

Страница 2: ... Occupied mode the controller operates from a heating setpoint FS 22 C or a cooling setpoint FS 24 C that can be changed centrally or locally using the dipswitches on RU FO The setpoint can be adjusted up and down FS 3 C with the knob on the front of the room unit Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requiremen...

Страница 3: ...ength 10 m This product conforms with the requirements of European EMC standards CENELEC EN 61000 6 1 and EN 61000 6 3 and the requirements of European LVD standard IEC 60 730 1 It carries the CE mark Inputs and outputs In RCP Terminal blocks in RCP So called lift type for cable cross section 2 1 mm2 Setpoint settings via Regio Tool Basic heating setpoint 5 40 C Basic cooling setpoint 5 50 C Setpo...

Страница 4: ...Wiring Terminal Designation Operation 10 33 No function 40 5 V 5 V supply voltage from RCP 41 N 0 V 0 V supply voltage from RCP 42 A RU Bus A 43 B RU Bus B Dimensions Product documentation Document Type Regio Maxi Manual Manual for the controllers from the Regio Maxi series Installation instruction Regio RU FO Installation instruction for RU FO All product documentation is available on www regin s...

Отзывы: