background image

Regin product information

Regin product information

RU-FO

Room unit with fan switch and forced 
ventilation for use with RCP

•  Awarded design
•  Simple installation

•  Built-in temperature sensor
•  Cable for connection between the room unit and the   

 

RCP controller is available as accessory

RU-FO is a room unit from the Regio series. It has a 
switch for controlling a three-speed fan (fan coil). It 
should be connected to one of the Regio Maxi controllers 
RCP100F, RCP100FT, RCP200F or RCP200FT.

Regio

Regio is a wide series of controllers which handle heating 
and cooling. 
The controllers are divided into three different series, 
Mini, Midi and Maxi. Mini are pre-programmed, 
stand-alone controllers. The Midi controllers are pre-
programmed with communication. The Maxi group, to 
which RU-FO belongs, consists of freely programmable 
controllers with communication.  

Applications

The Regio controllers are suitable in buildings where you 
want optimal comfort and low energy consumption, for 
example offices, schools, shopping centres, airports, hotels 
and hospitals etc.

Design

The room units have a modern design. The 
design has been awarded the 2007 “iF product 
design award”. 

Sensor

The room unit has a built-in sensor.

Easy to install

The modular design with a separate bottom plate for 
wiring makes the whole Regio series easy to install and 
commission. The bottom plate can be put into place 
before the electronics are installed. Mounting is directly 
on the wall or on an electrical connection box.  

Connection to RCP

The room unit is connected to the RCP-unit with an 
RJ12-cable, max length 30 m. Regin has two cables as 
accessories, RU-CBL3 (length 3 m) and RU-CBL10 
(length 10 m).

product

design

award

2007

RU-FO is a room unit intended for use together with 

Regio Maxi controllers.

 

revision

 

 

09  2009

Содержание RU-FO

Страница 1: ...ely programmable controllers with communication Applications The Regio controllers are suitable in buildings where you want optimal comfort and low energy consumption for example offices schools shopping centres airports hotels and hospitals etc Design The room units have a modern design The design has been awarded the 2007 iF product design award Sensor The room unit has a built in sensor Easy to...

Страница 2: ... Occupied mode the controller operates from a heating setpoint FS 22 C or a cooling setpoint FS 24 C that can be changed centrally or locally using the dipswitches on RU FO The setpoint can be adjusted up and down FS 3 C with the knob on the front of the room unit Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requiremen...

Страница 3: ...ength 10 m This product conforms with the requirements of European EMC standards CENELEC EN 61000 6 1 and EN 61000 6 3 and the requirements of European LVD standard IEC 60 730 1 It carries the CE mark Inputs and outputs In RCP Terminal blocks in RCP So called lift type for cable cross section 2 1 mm2 Setpoint settings via Regio Tool Basic heating setpoint 5 40 C Basic cooling setpoint 5 50 C Setpo...

Страница 4: ...Wiring Terminal Designation Operation 10 33 No function 40 5 V 5 V supply voltage from RCP 41 N 0 V 0 V supply voltage from RCP 42 A RU Bus A 43 B RU Bus B Dimensions Product documentation Document Type Regio Maxi Manual Manual for the controllers from the Regio Maxi series Installation instruction Regio RU FO Installation instruction for RU FO All product documentation is available on www regin s...

Отзывы: