Figure 4 UIx as temperature input

Settings

Communication settings can be viewed and changed either via the menu
system or through Modbus communication. All other settings are
accessed and modified via Modbus. The joystick is used to manoeuvre
within the menu system (see

Table 1

).

Pressing the joystick briefly results in entering the

viewing mode

. When in

viewing mode all configured universal inputs and outputs, including
pressure and flow sensor values, can be viewed.

To enter the

settings mode

, press the joystick for at least 5 s when the

display is inactive.

Table 1 Navigate the menu system

Joystick movements

Action

○ (push in)

Accept/select
Long press for settings mode (> 5 s)
Short press for viewing mode

Select next

Select previous

Back / cancel

Getting started

How to view and modify settings in the menu system:

1. Enter into viewing or setting mode by pressing and releasing the

joystick (long or short press) when the display is inactive

2. Navigate through the different sub menus by moving the joystick up

or down

3. Select a sub menu by pressing and releasing the joystick

4. If in setting mode, select a value to modify by pressing and releasing

the joystick

5. Change the value by moving the joystick up or down

6. Confirm the setting by pressing and releasing the joystick, or move

the joystick left to discard the changes

7. Move the joystick left to return to the previous menu

N

Noottee!! The last configuration entered into the transmitter is always valid,

regardless of whether it was performed using the menu system or via
Modbus.

Viewing mode menu

Sub menu

Description

P.#

Pressure value
P.1 = sensor 1 / P.2 = sensor 2

F.#

Flow value
F.1 = sensor 1 / F.2 = sensor 2

d.#

UI: Value in digital mode
d.1 = UI1 / d.2 = UI2

u.#

UI: Value in 0-10 V mode
u.1 = UI1 / u.2 = UI2

t.#

UI: Value in temperature mode (°C)
t.1 = UI1 / t.2 = UI2

L.#

UO: Value in digital mode
L.1 = UO1 / L.2 = UO2

U.#

UO: Value in 0-10 V mode
U.1 = UO1 / U.2 = UO2

Two digits can be shown at a time in the display. Therefore, several
subsequent views are used to display a longer value.

Example:

A pressure

value of 2350 Pa on sensor 1 is shown with three views, i.e.

1)

P.1

2)

23

3)

50. The measuring unit for the displayed value is set via Modbus.

N

Noottee!! The K-factor has to be set via Modbus to be able to view correct

flow values. Information regarding flow calculation is found in the variable
list.

Settings mode menu

Settings related to the communication can be changed in the settings
mode menu via the display.

Sub menu

Description

.A

Modbus address (1-247), given as hexa-
decimal numbers (1-F7)

.b

Modbus baud rate (see

Table 2

)

.C

Modbus settings (see

Table 3

)

Table 2 Settings in the sub menu .b

Modbus baud rate

Description

12

1200 bps

24

2400 bps

96

9600 bps (factory setting)

19

19200 bps

38

38400 bps

57

57600 bps

Table 3 Settings in the sub menu .C

Modbus settings

Description

n1

8 bytes, 1 stop bit, no parity (factory setting)

n2

8 bytes, 2 stop bits, no parity

E1

8 bytes, 1 stop bit, even parity

E2

8 bytes, 2 stop bits, even parity

o1

8 bytes, 1 stop bit, odd parity

o2

8 bytes, 2 stop bits, odd parity

When the transmitter is connected to Regin’s Corrigo controller, it is
configured as an expansion unit. When configuring the unit for Regin's
freely programmable products the addressing can be set via Modbus. See
the Corrigo manual and the PDTX…-C variable list for more
information.

N

No

ottee!! All documentation can be downloaded from www.regincontrols.

com

Handling

LEDs

Three LEDs are available to show different states.

t

PT1000 or
Ni1000-DIN

1   2   3   4   5   6   7   8   9  10 11

Sensor 1

Sensor 2 (when available)

Status LEDs

Push-button

Display

Joystick

t

A
B

24V AC/DC

+

-

RS485

Modbus

Presigo

3 (18)

Содержание PDTX C Series

Страница 1: ...inH2O Working range flow 0 65000 m3 h factory setting 0 31000 l s 0 65000 Ft3 min Cable glands 2 x M20 cable diameter 5 12 mm 1 x M16 cable diameter 3 5 10 mm Max overvoltage 18 V on any terminal not...

Страница 2: ...st pressure and the inlet marked with to the one with the lowest pressure N No ot te e A straight cut off nipple must be used for mounting in the ventila tion duct For optimal measuring results measur...

Страница 3: ...2 UI2 u UI Value in 0 10 V mode u 1 UI1 u 2 UI2 t UI Value in temperature mode C t 1 UI1 t 2 UI2 L UO Value in digital mode L 1 UO1 L 2 UO2 U UO Value in 0 10 V mode U 1 UO1 U 2 UO2 Two digits can be...

Страница 4: ...ntrols com O Ob bs se er rv ve er ra a L s och f rst instruktionen innan du anv nder produkten O Ob bs se er rv ve er ra a Se till att installationen uppfyller lokala s kerhetsbest mmelser O Ob bs se...

Страница 5: ...till plint 3 A och 4 B Anv nd v nster kabelgenomf ring f r matningssp nning och kommunikation 3 Sp nningss tt enheten G r de kommunikationsinst llningar som nskas i menyn se Inst llningar Notera att t...

Страница 6: ...joysticken till v nster f r att avf rda ndringarna 7 F r joysticken till v nster f r att terg till f reg ende meny N No ot te er ra a Den senast gjorda inst llningen i transmittern g ller alltid oavse...

Страница 7: ...n ut f rs L t enheten v rma upp i 10 minuter innan ett f rs k till nollpunktska librering g rs Fabriks terst llning Ett l ngt tryck p tryckknappen mer n 10 sekunder utf r en fabriks terst llning av an...

Страница 8: ...e 24 V AC oder DC 2 A kontinuierlich Ausgang Spannungsversorgung Max 2 A gesamt UO1 UO2 Kommunikation ber Datenschnittstelle Kommunikationsschnitt stellen 1 Schnittstellentyp RS485 Unterst tzte Protok...

Страница 9: ...rbunden mit Klemme 1 7 GND Intern verbunden mit Klemme 2 8 UO2 Universalausgang 2 Klemme Name Beschreibung 9 UI1 Universaleingang 1 10 GND Intern verbunden mit Klemme 2 11 UI2 Universaleingang 2 Verwe...

Страница 10: ...den mehrere aufeinanderfolgende Anzeigen verwendet um einen l ngeren Wert darzustellen Beispiel Ein Druckwert von 2350 Pa am F hler 1 wird mit drei Anzeigen dargestellt d h 1 P 1 2 23 3 50 Die Ma einh...

Страница 11: ...tallation est conforme aux normes de s curit locales A At tt te en nt tiio on n Avant de proc der l installation ou la maintenance de l ap pareil il convient de couper l alimentation lectrique Les op...

Страница 12: ...et 4 B Utiliser l entr e la plus gauche pour l alimentation et la communication 3 Mettre le r gulateur sous tension R gler les param tres de communication partir du menu voir R glages Note Adresse Mod...

Страница 13: ...par un mouvement vers la gauche 7 Manette vers la gauche pour un retour l cran pr c dent N NB B La derni re configuration entr e dans le transmetteur est toujours valide ind pendamment de la configura...

Страница 14: ...ression R initialisation Un appui long sur le bouton poussoir plus de 10 secondes lance la r initialisation aux param tres usine Tableau 4 indique les param tres restaur s Tableau 4 R glages usine Des...

Страница 15: ...Lunghezza del cavo Max 100 m Modelli Articolo Numero di sensori Max pressione di sovraccarico kPa Campo di misura pressione Pa PDTX12 C 1 25 0 1250 PDTX25 C 1 50 0 2500 PDTX75 C 1 120 0 7500 PDTX12 2...

Страница 16: ...ualizzate e modificate tramite il sistema di menu o tramite Modbus Tutte le altre impostazioni sono accessibili e modificabili tramite Modbus Il joystick viene utilizzato per spostarsi all interno del...

Страница 17: ...bps Tabella 3 Impostazioni nel sottomenu C Impostazioni Modbus Descrizione n1 8 byte 1 bit di stop nessuna parit impo stazione di fabbrica n2 8 byte 2 bit di stop nessuna parit E1 8 byte 1 bit di sto...

Страница 18: ...u www industrietechnik it Documentazione La documentazione pu essere scaricata da www industrietechnik it Contatti AB Industrietechnik SRL Via Julius Durst Str 50 I 39042 Bressanone BZ Tel 39047283062...

Отзывы: