12
Control mode 2, CO
2
control
D
P
/
CO
2
CO
2
The output signal will increase when the CO
2
-value rises above the setpoint value.
The CO
2
-sensor must have a 0...10 V DC output for example:
CO2RT, CO2RT-D
Room sensors
CO2DT
Duct sensor
The transmitter range cannot exceed 5000 ppm at 10 V DC output.
DI1, Start signal
Normal control will only be activated when this input is activated, closed. When the start
signal is deactivated the controller will set the output to 0.
Note: This input must always be wired since it controls the starting and stopping of normal
control.
24 V AC
Damper
Frequency
converter
CO
2
transmitter
G
G0
DI+
DI1
UI+
UI1
A
GND
AI1
1
2
3
41
42
43
44
50
51
20
21
22
A
GND
AO1
AO2
G0
G
Y
G0
G
Y
20
21
22
A
GND
AO1
AO2
-
+