INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

MTIBL90H

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

MTIBL90H

Boiler thermostat

MTIBL90H is a high quality electro-mechanical thermostat for use in 

boiler systems. 

Technical data

Sensor element   

Liquid-filled copper bulb

Contacts 

 

Dust-tight microswitches with SPDT  

 

 

 

 

contacts (heat/cool)

Breaking capacity   

16 (6) A, 24…250 V AC

Temperature range 

0…90°C

Hysteresis 

 

4±1 K

Max. bulb temperature 

120 °C

Ambient temperature 

-35…+65°C

Ambient humidity   

10…90 % RH (non-condensing)

Housing  

   

Bayblend

®

 base, ABS cover

Protection class   

IP54, class 1

Weight   

 

560 g

Before installation or maintenance, the power supply must first be discon

-

nected in order to prevent potentially lethal electric shocks!  Installation or 
maintenance of this unit should only be carried out by skilled professio

-

nals.

Installation

The unit can be mounted in any position. Unscrew both screws on the 
cover. Use the supplied screws when mounting on wall or other surface. 

 

Set desired temperature range by turning the screw under the cover.

60

90

30

I

I

I    I  I

 

Wiring

Heating: Connect to terminal 2 and 3. The contact will open when the 
temperature rises.

Cooling: Connect to terminal 1 and 2. The contact will open when the 
temperature drops.

1 2 3

<T

Logic-activation

Reset

The set range may be reset by carefully turning the screw under the 

cover.

 

 

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low 
Voltage Directive (LVD) 2014/35/EU through product standards 
EN 60335-1.

RoHS

This product conforms to the Directive 2011/65/EU of the European 

 

Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden

 

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50

 

www.regincontrols.com, [email protected]

12890C

 

DEC 17  

EN

ON

ON

OFF

OFF

Δ

NS

Δ

NS

Heating

Contacts 2 - 3

Cooling        

Contacts 1 - 2

ΔNS: Hysteresis

TSET: Setting setpoint

ON: Closed contact

OFF: Open contact