Regin CTRTA Скачать руководство пользователя страница 2

11979G JUN 22

CTRTA(-D)

2

INSTRUCTION CTRTA(-D)

CO

2

 and temperature transmitter for wall 

mounting

Room transmitters for measuring carbon dioxide concentration in 
indoor environments. The transmitter has a built-in CO

2

 sensor with 

measuring range 0…2000 ppm and output signal 0…10 V, as well 
as built-in 0…10 V and PT1000 temperature sensors (measuring 
range 0…50°C).
-D models have an LCD display showing CO

2

 concentration and 

temperature in an alternating series.

 

 

Technical data

Supply voltage 

 

24 V AC/DC (21.6…26.4 V AC /  

 

 

 

15…35 V DC)

Power consumption 

< 2.5 W

Energy consumption         < 0.5 Wh
Transformer power  

5 VA

Electrical connection  

Screw terminals max. 1.5 mm

2

  

     (AWG 16)
Ambient temperature 

0…50°C

Ambient humidity   

10…90 % RH non-condensing

Storage temperature 

-25…+60°C

Protection class   

IP30

Dimensions (WxHxD) 

85 x 100 x 30.5 mm

CO

2

Output signal CO

2

   

0...10 V DC referring to 0…2000 ppm

Measuring range   

0…2000 ppm

Accuracy at 20°C   

< ± (50 ppm + 2 % of the measured  

     value)

Temp. influence   

Typically 5 ppm / K

Long term stability  

Typically 20 ppm / year

Time constant 

 

< 90 s

Warmup time 

 

< 5 min

Temperature (0...10 V)

Temperature sensor 

0…10 V DC referring to 0…50°C

Measuring range   

0…50°C

Accuracy  ±0.4°C

Temperature (PT1000)

Temperature sensor  

PT1000 class DIN B

Measuring range    

0…50°C

Accuracy  

 

±0.3°C

Installation

The transmitter should be mounted in a location with good air 
circulation where it can be expected to give a representative reading. 
It may be mounted on a wallbox or directly on the wall. 
To remove the front cover, press the locking tongue in the lower part 

of the casing using a 3 mm flat-blade screwdriver (

figure 1

). Press 

and twist the screwdriver and at the same time pull the bottom part 
of the front outwards (

figure 2-4

). When the bottom end of the front 

is free from the bottom part of the casing, slide the cover towards the 
top of the casing to free the hooks holding the upper edge of the front 
cover (

figure 5

).

 

Perform the connections according to the electrical wiring diagram 
(

figure 7

). Note: GND and G0 are internally connected.

Screw the bottom part of the casing to the wall.

Regin CO

2

 Background Calibration (RCBC)

The Regin CO

2

 Background Calibration function, or RCBC, is a 

function that can be activated to get a more stable CO

2

 level in a 

room that is not used for parts of a day.
The lowest reading each day is saved, and every 7 days these 
readings are checked and may be adjusted up or down depending on 
the CO

2

 level.

In order for the function to work properly, the room must be well 
ventilated and should be empty for atleast 4 hours per day.
The RCBC function should not be used for rooms that are in use 24 
hours a day, like greenhouses and hospital rooms.

Startup

After applying power to the transmitter, it will be a few minutes before 
it starts to show correct CO

2

 values.

Note! 

The PT1000 sensor is not compensated for internal warm-up. 

The passive temperature output must be calibrated with a controller.

Calibration

The transmitter is calibrated before delivery and does not need to be 
calibrated at installation. It is calibrated automatically, which means 

that manual recalibration is not required during the lifetime of the 
transmitter. 

Configuration of RCBC

Use dip switch 1 and 2 to select which action to perform. Changing 
dip switch position creates an action for the RCBC algorithm. 
The unit is delivered with the dip switches in position OFF. The 
RCBC algorithm is not activated and the parameters are reset.  

To activate the RCBC algorithm, put both dip switch 1 and 2 in 
position ON.

1

2

ON

Fig. 9

To deactivate the RCBC algorithm, put dip switch 2 in position OFF 
and do not touch dip switch 1.

1

2

ON

Fig. 10

To reset the RCBC parameters and deactivate the RCBC algorithm, 
put both dip switch 1 and 2 in position OFF.

1

2

ON

Fig. 11

Note!

 if the RCBC algorithm is deactivated (see Fig. 10), the 

current correction is not applied to the CO

2

 reading, but the value 

is still in the memory and saved in the EEPROM. As soon as 
the RCBC algorithm is activated again, the correction is applied 
immediately at the next sensor reading.

 

This product carries the CE mark.  
More information is available at www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden

 

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

i

i

Read this instruction before installation and wiring of the 
product. Subject to change without notice.

EN

Caution! 

The CO

2

 sensor must not be subjected to any 

kind of mechanical impact as this will cause the sensor 
to give faulty readings.  

Содержание CTRTA

Страница 1: ...CTRTA D 11979G JUN 22 CTRTA D 1 2 3 mm 1 2 3 4 5 6 7 8 C F JP6 JP6 1 2 RCBC 0 10 V GND 1 2 3 4 5 6 7 8 T CO2 V G0 G T 15 35 V DC 24 V AC GND 0 10 V SENS SENS 1 ...

Страница 2: ...function or RCBC is a function that can be activated to get a more stable CO2 level in a room that is not used for parts of a day The lowest reading each day is saved and every 7 days these readings are checked and may be adjusted up or down depending on the CO2 level In order for the function to work properly the room must be well ventilated and should be empty for atleast 4 hours per day The RCB...

Страница 3: ... under delar av dygnet Det lägsta uppmätta värdet varje dag sparas och var 7 e dag kontrolleras dessa värden och kan justeras upp eller ned beroende på rummets CO2 nivå För att funktionen ska fungera måste rummet ha god ventilation och vara tomt minst 4 timmar per dygn RCBC funktionen ska inte användas i rum som används dygnet runt som växthus eller sjukhusrum Uppstart Efter spänningstillslag dröj...

Страница 4: ...der zeitweise nicht genutzt wird Der jeweils niedrigste Messwert pro Tag wird gespeichert und alle 7 Tage werden diese Messwerte überprüft und können abhängig vom CO2 Wert nach oben oder unten angepasst werden Damit die Funktion richtig funktioniert muss der Raum gut belüftet sein und sollte mindestens 4 Stunden pro Tag leer stehen Die RCBC Funktion ist nicht für Räume geeignet die 24 Stunden am T...

Отзывы: