Controller for constant supply air control

or room temperature control, one 3-position 

output and active frost protection

AQUA24TF is intended for constant supply air temperature control 
or room temperature control in  water heated air handling units.
Settable for use with internal or external sensor. It has one three-
position output, active frost protection and shut-down control.

Installation

Remove the front. The cover retaining screw is behind the setpoint 
knob.
Mount the unit vertically with the setpoint knob at the lower right 
hand corner.
Use screws with a maximum head diameter of 5.5 mm.
The mounting holes have a c:c distance of 60 mm to fi t onto a stan-
dard size wallbox.
If the AQUA24TF is to be used with the built-in sensor, mount it ap-
proximately 5 ft above fl oor level in a location with a representative 
temperature and good air circulation.
Protection class 

IP20

Function switches

AQUA24TF can be confi gured either for single sensor control 
(supply air control or room temperature control using room sensor 
only) or for cascade control. Use the function switches to set the 
desired control function:

Single main sensor control, 
CF must be set to 1

Cascade control

Sensors

Main sensor

For supply air control the main sensor is placed in the supply air 
duct after the heater. Wire, and set the sensor switches according to 
fi gure 2 if the built in setpoint is used, otherwise according to fi gure 
3 or 4 depending on which setpoint device is chosen.
For room temperature control the main sensor, or the AQUA24TF if 
the built-in sensor is to be used, is placed in the room at a suitable 
location. Wire, and set the sensor switches according to fi gure 2 if 
the built in setpoint is used, otherwise according to fi gure 6.

If the built-in sensor is used, set the switches as in fi gure 5.

Limiting sensor, cascade control

For room temperature control the AQUA24TF can be confi gured 
as a cascade controller with the main sensor in the room and a 
limiting sensor in the supply air duct. A room temperature devia-
tion results in  a shift of the duct temperature controller’s set-
point. The size of the shift is determined by the cascade factor 
CF.
When using cascade control, the supply air temperature can be 
minimum limited.
Wire the limiting sensor according to fi gure 7

Frost protection sensor

The frost protection sensor is placed, either as a strap-on sensor 
(TG-A130), on the heater return water pipe or, as an immersion 
sensor (TG-D130), in the heater or the return water pipe.
Should the temperature at the frost protection sensor fall below 
10°C the frost protection controller will force the valve to open. 
Should the temperature fall below 5°C the alarm relays will trip. 
The frost protection alarm is reset by pushing the button RESET 
on the left hand side of the unit.
Relay 1: 2 A, 240 V AC is for stopping the fan. 
Relay 2: 2 A, 24 V is for alarm indication.
Wire the frost protection sensor according to fi g.8

Other wiring

Supply voltage and outputs

Supply voltage: 24V AC +/-15% 50-60Hz.
Power consumption 5VA maximum
Terminal 13 = Phase.
Terminal 14 = System neutral.

Output: 24V AC, 7VA maximum
Terminal 17 =Common pole
Terminal 18 = Increase heat
Terminal 19 = Reduce heat
Proportional band = 20K
Pulse period = 4 seconds
(A small temperature offset will generate a short pulse every 4 
seconds on the output that will counteract the offset. If the offset 
increases the pulse will grow longer. A 20K offset will generate a 
continuous output signal).

N.B. Always connect the actuator to these three terminals 
only. Terminal 17 is NOT neutral.