INSTRUCTION AL230A

Room temperature controller

AL230A is a room temperature controller for use in air handling or 
demand-controlled ventilation applications.  
It controls a 0...10 V output signal with a PI algorithm in direct or 
reverse action. The output signal is applied to an air handling unit, 
e.g. a ventilator such as an EC fan or damper.

Technical data

Supply Voltage 

 

110...240 V AC, 50/60 Hz

Power consumption 

Max. 0.46 W

Operating temperature 

0...50°C, 10...90 % RH

 

 (non-condensing)

Outputs 

 

1 analogue output 0...10 V (max. 1 mA)

Working range 

 

0...50°C

Manual activation   

Min. 600 cycles

Automatic activation 

> 100 000 cycles

Dimensions (WxHxD) 

85 x 100 x 30.5 mm

Installation 

 

*Wall mounting

Impulse voltage   

2,5 kV

Pollution degree   

2

Classification of unit 

Type 1

Protection class   

IP30

Insulation class   

Class II

*The unit must be installed exclusively in contact with a wall.  
Installation with a spacer that would allow access to the back of the 
unit is forbidden.

Installation

Place the device in a location that has a temperature representative 

for the room. A suitable location is approx. 1.6 m above floor level in 

a place with unobstructed air circulation.To remove the front cover, 

use a 3 mm flatblade screwdriver to depress the locking tongue in 

the lower part of the casing (

picture 1

). Press and twist the screw-

driver, and at the same time pull the bottom part of the front outwards 
(

pictures 2-4

). When the bottom end of the front cover is free from 

the bottom part of the casing, slide the cover towards the top of the 
casing to free the hooks holding the upper edge of the front cover 
(

picture 5

). Perform the connections according to electrical wiring 

diagram. Cables must be fixed using the 2 cable ties supplied as indi

-

cated in 

picture 6

. Screw the bottom part of the casing to the wall.

Disconnection

AL230A should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the 
controller and within easy reach of the operator, and should be 
marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the 
mains supply during maintenance of the EC fan or damper.

Settings

The direction of the output signal is set using the JP1 jumper  
(

picture 8

):

SW1: Temperature proportional band (0.5...8.0°C)
JP1 closed 1-2: Heating
JP1 closed 2-3: Cooling
R23: Temperature setpoint (5...30°C)
R28: EC fan min. limit speed
R29: EC fan max. limit speed

 P-band and I-time are set using rotary switch 

SW1

.

SW1

0

1

2

3

4

5

6

7

P-band (°C)

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

I-time (s)

1800

1700

1600

1500

1400

1300

1200

1100

SW1

8

9

A

B

C

D

E

F

P-band (°C)

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

I-time (s)

1000

900

800

700

600

500

400

300

The range of the voltage applied to the ventilator is defined using the 
MIN and MAX knobs. MIN is used to define the minimum applicable 
voltage to the ventilator (0...5 V), while MAX defines the maximum 

voltage (5...10 V). The PI controller will then operate between the 
relevant MIN and MAX values.

Example 1:

If the MIN value is set to the minimum position and MAX to the 
maximum position, the PI controller will work from 0...10 V.

Example 2:

If MIN is set to 2 V and MAX is set to 7 V, the PI controller works 
from 2 to 7 V.

 

This product carries the CE mark.  
For more information, see www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.se, [email protected]

i

Read this instruction before installation and wiring of the 
product. Subject to change without notice.

Consult documentation in all cases where this symbol is 

used, in order to find out the nature of the potentional 

hazards and any actions to be taken. All installation, 

setting or maintenance of this unit must be performed with the 

supply voltage switched off and without any external loads on the 

unit! These operations should only be carried out by skilled 
workers. The manufacturer is not responsible for any damages 
caused by inadequate skills during installation and/or by any safety 
devices having been removed or tampered with.

EN