Clearance:

Dimension

Measured From:

USA Only

Canada Only

A: Mantel 
Height

18” (457mm)

18” (457mm)

Minimum 

(See Page 86)

B: Sidewall

18” (457mm)

24” (610mm)

Side of fi replace 

opening

C: Ceiling

46” (1168mm)

46” (1168mm)

Top of fi replace 

opening

D: Mantel 
Depth

10” (254mm)

10” (254mm)

Maximum 

(See Page 86)

E: Alcove 
Width

N/A

N/A

Approved for Single 

Sidewall only

F: Alcove 
Depth

N/A

N/A

Approved for Single 

Sidewall only

G: Thermal 
Protection 
Height

1/2” (13mm)

1/2” (13mm)

Bottom to top of 

Protection.

H: Hearth 
Width

40” (1016mm)

40” (1016mm)

Edge to Edge of Hearth

I: Hearth 
Depth

18 ” (457mm)

18 ” (457mm)

Front of Hearth to Wall

J: Facing 
Height**

52-1/2” 

(1334mm)

51-1/2” 

(1308mm)

Floor to Facing 

Height**

K: Facing 
Width**

44” (1118mm)

60” (1524mm)

Edge to Edge of 

Facing**

**

Required non-combustible facing.

172

June 2007 Regency Product Specifi cations Book

W

ood Fir

eplaces

Wood Fireplaces

NOTES:

1)   Minimum Chase sizes must be met according to the framing 

directions (page 149).  

US Installations

 will require a minimum 

ventilation with one 30 sq. in. (194 sq. cm.) opening grill (air is 
drawn from within the home not outside).  

2)   Mantel min. Height of 18” (457mm) from top of louver opening to 

underneath mantel or 55 1/2” (1410mm) from bottom of unit.

3)   Minimum non-combustible facing must be installed according to 

the table on this page.  Finishing material to be installed on top of 
this.

4)   Framing is slightly larger than unit dimensions to allow for easier 

installation (50 3/4”, 1289mm h x 44”, 1118mm w)

5)   Must maintain a min. of 46” (1168mm) from top of louver opening 

to fi nished ceiling.

6)   Sidewall clearances, as detailed on this page, must be maintained 

according to your location.

7)   Hearth must be a min. 40” (1016mm) wide x 18” (457mm) deep 

and 1/2” (127mm) thick.

Clearances Requirements

No combustible materials on the face of unit.

Required Hearth must be non-combustible and will require 
thermal protection.  Minimum thermal protection must have 
a "k" factor of 20.07 (in Canada), 0.84 (in US).

R90 Wood Fireplace

R90 Wood Fireplace

Combustibles may not extend to unit face.

Do not notch wallboard around standoffs.

The R90 may be placed on or near  construction  materials.  The 
combustion air kit, fi re stop spacer and roof  fl ashings (not chase 
fl ashings) may be placed directly on or  against normal construction 
materials. The chimney requires a minimum 2" (51mm) clearance.  A 
combustible mantle (to a depth of 10", 254mm) may be installed no 
closer than  18" (457mm) above the warm air vent or 55-1/2" (1410mm) 
from bottom of unit.   

The chimney must be enclosed when installed in or  passing through a 
living area where combustible material or  people may come in contact 
with it.  This is important to prevent  possible personal injury or fi re 
hazard.  

For any further information, please call your dealer.  Special restrictions 
apply to the front and facing of the  fi replace and nearby walls. 

WARNING:

  If insulation is used, do not place the unit against it.  Insulation 

or vapor barriers, if used, must be secured to assure insulation and vapor 
barriers remain in place and do not affect the required air spaces.  

WARNING:

  Do not pack or fi ll required air spaces with insulation or other 

material. No material of any kind is allowed in these areas.

NOTES:

1) 

Do not insulate the chase cavity with blown or fi ll type insulation 
materials.  

2) 

Local codes may not require a fi restop at the ceiling level  for outside 
chase installations; however, it is recommended for safety and the 
reduction of heat loss. 

3) 

We recommend that you insulate at least the fi rst fl oor of the chase 
to prevent heat loss.

4) 

Some local codes require 1 hour fi re rating on one or all sides of 
fi re chases.  Check with your local authorities.