Horizontal Venting
with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
Option
V
H+ H1
Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1 foot between
90° elbows is required.
A)
0’ Min.
2’ Max.
B)
1’ Min.
3’ Max.
C)
2’ Min.
4’ Max.
D)
3’ Min.
5’ Max.
E)
4’ Min.
6’ Max.
F)
5’ Min.
7’ Max.
F)
6’ Min.
8’ Max.
Horizontal Venting
with Three (3) 90° Elbows
Two 45° elbows = One 90° elbow
Option
V
H
V+ V1
H + H1
Maximum total
pipe: length, of
all sections, must
not exceed 30
feet.
Total horizontal
sections must not
exceed 8 feet.
Minimum of 1
f o o t b e t w e e n
90° elbows is
required.
A)
0’ Min.
1’ Max.
1’ Min.
2’ Max.
B)
1’ Min.
2’ Max.
3’ Min.
3’ Max.
C)
2’ Min.
2’ Max.
5’ Min.
4’ Max.
D)
3’ Min.
2’ Max.
7’ Min.
5’ Max.
E)
4’ Min.
3’ Max.
9’ Min.
6’ Max.
F)
5’ Min.
4’ Max.
10’ Min.
7’ Max.
G)
6’ Min.
5’ Max.
11’ Min.
8’ Max.
H)
7’ Min.
6’ Max.
12’ Min.
9’ Max.
P36 - P36D Gas Fireplace
41
June 2007 Regency Product Specifi cations Book