background image

 

-  Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other 

appliance.

 

- WHAT TO DO IF YOU SMELL GAS

 • 

Do not try to light any appliance.

 

•  Do not touch any electrical switch: do not use any phone in your building.

 

  Leave the building immediately.

 

•  Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's 

 

instructions.

 

• If you cannot reach you gas supplier, call the fire department.

 

 

 

- Installation and service must be performed by a qualified installer, service agency or the gas supplier.

     WARNING

FIRE OR EXPLOSION HAZARD

F

ailure to follow safety warnings exactly could result in serious

injury, death, or property damage.

 

REGENCY FIREPLACE PRODUCTS.  6988 Venture St., Delta, BC  Canada, V4G 1H4

919-399

01.26.15

P36  Zero  Clearance

Direct  Vent  Gas  Fireplace

Owners & Installation Manual

Tested by:

Installer

: Please complete the details on the back cover 

and leave this manual with the homeowner.

Homeowner:

 Please keep these instructions for future reference.

MODELS:    P36-NG10 Natural Gas     P36-LP10  Propane

P36 Video

Содержание P36-LP10

Страница 1: ...ire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage REGENCY FIREPLACE PRODUCTS 6988 Venture St Delta BC Canada V4G 1H4 919 399 01 26 15 P36 Zero Clearance Direct Vent Gas Fireplace Owners Installation Ma...

Страница 2: ...with all the warmth and charm of a wood fireplace at the flick of a switch The model P36 has been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regenc...

Страница 3: ...ructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI NFPA 70 in the U S A and the current CAN CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22 1 in Canada ThisRegencyMobile ManufacturedHomeListedappliance comes factory equipped with a means to secure the unit ...

Страница 4: ...bustible Mantel Leg Clearances 12 Framing and Finishing 13 Finishing 14 Wall mount On Off Switch Receiver Installation 15 Unit Assembly Prior To Installation 16 Venting Introduction 16 Exterior Vent Termination Locations 17 Venting 18 4 x 6 5 8 Rigid Pipe Cross Reference Chart 19 Rigid Pipe Venting Arrangements 21 Venting Arrangements Vertical Termination 24 Vertical Termination Co linear Flex Sys...

Страница 5: ...ocal codes if any if none follow the National Fuel Gas Code ANSI Z223 1 or Natural Gas and Propane Installation Code CSA B149 1 This appliance must be installed in accordance with the Standard CAN CSA Z240 MH Mobile Housing in Canada or with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or when such a standard is not applicable ANSI NCSBCSA225 1...

Страница 6: ... directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon in...

Страница 7: ...replace 7 7 dimensions UNIT DIMENSIONS WITH VIGNETTE FACEPLATE 36 1 16 30 1 2 36 33 1 8 12 13 16 32 3 8 2 3 16 15 841mm 914mm 775mm 916mm 381mm 325mm 56mm 813mm 34 3 16 864mm 28 15 16 Optional 3 sided finishing trim not shown 38 W x 33 3 4 H ...

Страница 8: ...n and any repairs to this appliance should be done by a qualified service person A professional service person should be called to inspect this appliance annually Make it a practice to have all of your gas appliances checked annually 13 Do not slam shut or strike the glass door 14 Under no circumstances should any solid fuels wood paper cardboard coal etc be used in this appliance 15 The appliance...

Страница 9: ...llowing the fireplace to be operated with less heat entering the room The kit may be used on either the left or right side The HeatWave Duct Kit has different clearanceandframingrequirements check the HeatWave manual for details INSTALLATION CHECKLIST 1 Locate appliance Refer to the following sections a Locating Your Gas Fireplace b Clearances c Combustible Mantel Clearances d Framing Finishing e ...

Страница 10: ...s Clearance to Combustibles from Back 0 0mm Side 0 0mm Floor 0 0mm NOTE The minimum floor clearance must be maintained from the top surface of the carpeting tile etc Minimum Clearance from Top of Unit to Ceiling from top of unit 32 1016mm Side Wall Clearances 6 152mm Measured from edge of unit Horizontal Vent Clearances Top 2 51mm Side 1 1 2 38mm Bottom 1 1 2 38mm Vertical Vent Clearances 1 1 4 32...

Страница 11: ...emits the mantel clearances are critical Combustible mantel clearances from top of unit are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Note Mantel starts at 1 deep and end at 12 deep Note Ensure the paint that is used on the mantel and the facing is heat resistant or the pain...

Страница 12: ...12 P36 10 Zero Clearance Direct Vent Gas Fireplace 12 installation REGENCY MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Maximum 1 1 2 projection at 2 minimum clearance ...

Страница 13: ...unit must not be closer than 32 813mm to the ceiling Note 40 1 2 1029mm is the minimum height for both flex termination or rigid pipe venting All other framing may be of combustible materials i e 2 x 4 2 x 6 Note The unit does not have to be completely enclosed in a chase The clearance on top of the unit is 0 to thestandoffssocombustiblebuilding materials can be laid directly on top of the standof...

Страница 14: ...el or higher than the finished hearth height Diagram 3 Shown with optional finishing trim Note All non combustible and combustible facing material should butt up cleanly to the flanges around the firebox opening Rough edges will be visible from the front view with the Vignette faceplate if not using the optional finishing trim To maintain a clean finished edge it is recommended to install the comb...

Страница 15: ...junction box to the framing at desired location within 10 ft from fireplace 2 Feed the 12 pin connector through the opening at back of junction box 3 Connect the 12 pin connector to the back of the receiver 4 Install the Receiver in the Low Voltage Junction box 5 Insert the 4 AA type batteries in the battery compartment with the correct polarity 6 Place the slider into the cover plate 7 Put the Re...

Страница 16: ...amber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney Note These flue pipes must not be connected to any other appliance The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas burning appliance Eachdirectventgasappliancemustuseit sown ...

Страница 17: ... extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on pu...

Страница 18: ...termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 1 6 7 8 dia flexible liner 10 ft length 2 4 dia flexible liner 10 ft length 3 spring spacers 7 4 thimble 2 5 AstroCap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 Iflongerrunsareneeded theRegencyDirect Vent sy...

Страница 19: ...stable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N A SV4LA12 TC 4dLSI Adjustable Length 12 Black N A N A 4D12A N A SV4LBA12 TC 4dLSIB Extension Pipe 16 Galvanized 46DVA 16A N A N A N A N A N A Extension Pipe 16 Black 46DVA 16AB N A N A...

Страница 20: ... Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK TM4 HTK Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK TM4 HTK Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigid piping 946 208 P Vent Guard Optiona...

Страница 21: ...at Wall Installation Wall Thickness inches Vent Length Required inches 4 5 1 2 6 7 8 1 2 9 10 1 1 2 12 9 14 1 2 11 14 5 8 Adj Pipe 15 23 1 2 17 24 Adj Corner Installation Wall Thickness inches Vent Length Required inches 3 1 4 6 3 4 11 14 5 8 Adj Pipe 7 3 4 16 1 4 17 24 Adj Pipe 7 1 4 8 3 4 6 12 9 9 4 1 4 5 3 4 6 9 This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conju...

Страница 22: ...pe adaptor Part 510 994 when using Rigid Pipe venting systems All Rigid Pipe Systems 4 inner diameter 6 5 8 outer diameter RegencyFlex Vent 4 inner diameter 6 7 8 inner diameter Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the termination is lowe...

Страница 23: ...0o elbows is required A 0 Min 2 Max B 1 Min 3 Max C 2 Min 4 Max D 3 Min 5 Max E 4 Min 6 Max F 5 Min 7 Max G 6 Min 8 Max Lengths do not include elbow indicated Option V H V V1 H H1 With these options max total pipe lengthis30feetwith min of 12 feet total vertical and max 9 feet total horizontal Please note min 1 foot between 90o elbows is required A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Max...

Страница 24: ...opane and Natural Gas Diagram 1 The P36 is approved for a 40 ft straight vertical with rigid pipe vent systems for Propane and Natural Gas as per the diagram 1 The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum two 45o elbows allowed Vent must be supported at off...

Страница 25: ...5 25 installation Vent must be supported at offsets Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles Note Must use optional rigid pipe adaptor when using rigid vent systems Part 510 994 ...

Страница 26: ...Min 2 Max 1 Min B 1 Min 4 Max 2 Min C 2 Min 5 Max 3 Min D 3 Min 6 Max 4 Min E 4 Min 7 Max 5 Min F 5 Min 8 Max 6 Min Lengths do not include elbow indicated For additional vertical venting with 2 x 90o elbows refer to next page Option V H H1 V V1 With these options max totalpipelength is 30 feet with min of 10 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elb...

Страница 27: ...asonry chimneys may take various contours which the flexible liner will accommodate However keep the flexible liner as straight as possible avoid unnecessary bending The Air Intake pipe must be attached to the inlet air collar of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit which con...

Страница 28: ...aded area in the diagrams show the allowable vertical terminations 8 Min 40 1 2 30 Max 30 Horizontal Distance Feet Vertical Height feet 2 max VENTING ARRANGEMENTS VERTICAL TERMINATION with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces ...

Страница 29: ...t lock procedure Four indenta tions located on the female ends of pipes and fittings are designed to slide straight onto the male ends of adjacent pipes and fittings by orienting the four pipe indentations so they match and slideintothefourentryslotsonthemale ends Diagram1 Pushthepipesections completely together then twist lock one section clockwise approximately one quarter turn until the two sec...

Страница 30: ...on between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe section See Diagram 6 9 Install wall thimble in the center of the 10 square and attach with wood screws 3 A Firestop spacer must be installed in the floor or ceiling of e...

Страница 31: ...T SYSTEM FLEX INSTALLATION PROCEDURES 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the left Locate the center ww wwwwline of the termination and mark wall accordingly Cut a 10 254mm hole in the wall inside dimension Note A 2 clearance at the top and 1 1 2 clearance around the liner must be mainta...

Страница 32: ...ck for gas leaks with a soap and water solution or gas leak detec tor Do not use open flame for leak testing HIGH ELEVATION This unit is approved in Canada for altitude 0 to 4500 ft CAN1 2 17 M91 with the orifice supplied P36 NG10 System Data For 0 to 4500 feet altitude Burner Inlet Orifice Sizes 37 Max Input Rating 30 000 Btu h Min Input Rating 15 500 Btu h Supply Pressure min 5 0 w c Manifold Pr...

Страница 33: ...ressureiscontrolledbyaregulator built into the gas control and should be checked at the pressure test point Note To properly check gas pressure both inlet and manifold pressures should be checked using the valve pressure ports on the valve 1 Make sure the valve is in the OFF position 2 Loosen the IN and or OUT pressure tap s turning counterclockwise with a 1 8 wide flat screwdriver 3 Attach manome...

Страница 34: ...rifice 52 1 904 529 5 32 Allen Key 1 918 590 Decal Converted to LPG 1 908 528 Red LPG label 1 910 037 LPG Injector Pilot Orifice 1 910 582 Stepper Motor 1 919 472 Instruction Sheet Installation of LPG Conversion Kit 10 Remove NG stepper motor by removing 3 screws in locations shown below re place with LP stepper motor secure in place with 3 screws Remove NG Stepper motor and replace with LP Steppe...

Страница 35: ...s Note The logs must not be in the unit 3 Insert the back brick panel first by carefully slipping it between the back wall of the firebox and the rear log bracket 4 Put the side panels in next Slide them in from the front and push them flat up against the wall Be very careful not to scratch them on the firebox hardware 5 Install the 2 brick retaining clips one on each side OPTIONAL BRICK PANELS ...

Страница 36: ...og h 902 156 Embers i 902 179 21 Vermiculite j 946 669 Platinum Embers supplied w packaged manual 4 Place Log 02 51 on the front right side of the burner Push the back of the log against the 2 brackets with the notch on the bottom right side of the log fitting into the right side of the grate Notch Bracket Bracket 3 Place Log 02 49 on the rear log support pins with the flat side to the back 02 49 ...

Страница 37: ... of the log against the 2 front brackets with the notch on the bottom of the log fitting into the first grate tab Notch 02 55 02 50 02 54 5 Position Log 02 53 across the cutouts in Logs 02 49 and 02 51 with the notch on the left side of the log fitting into the 2nd grate tab Cutouts 2nd Grate Tab 02 53 02 49 02 51 02 49 02 51 02 53 02 49 02 51 02 53 02 55 02 53 02 50 02 55 02 53 02 50 02 55 02 53 ...

Страница 38: ...ween Logs 02 51 and 02 49 and on the indentation on Log 02 54 The bottom right end sits behind the rear grate tab 10 Place the embers on the front of the burner tray in the places shown on the photo Separateplatinumembersandplaceonthefrontburneron and around the embers Avoid stacking platinum embers Platinum embers may be placed over burner ports 11 Test fire to ensure proper light off make sure f...

Страница 39: ...2 The standard flush door comes with a black frame To install the frame simply hook the top door flange onto the top of the unit and swing the door towards the unit see Diagram 1 Be careful that the glass gasket does not roll up there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit see Diagram 2 Diagram 1 STANDARD FLUSH DOOR To remove the flush d...

Страница 40: ...safety screen installation 1 Hook the outer Vignette frame onto the unit Brackets on the frame hook on to tabs in the unit Note Use the inner slots for the P36 P36E units and the outer slots for the P36D P36D P36 P36E Tab Slot 2 Slot the tabs on the inner Vignette frame with safety screen into the corresponding slots in the outer Vignette frame as shown below ...

Страница 41: ...e trim with the holes in the firebox side 2 Secure with one screw per side on top the bottom screw is installed after the Vignette faceplate bracket is in place P33 P33E only 3 Loosen the 3 screws in the top inside edge of the firebox 4 Slide the Finishing Trim Top over the Side Trim pieces and fit the bottom bracket slots over the screws Tighten the 3 screws to secure 5 Hook Vignette Faceplate br...

Страница 42: ... but any 250 750 millivolt rated non anticipator type thermostat that is CSA ULC or UL approved may be used CAUTION Do not connect millivolt wall thermostat wires to 120V wire Recommended Maximum Lead Length Two Wire When Using Wall Thermostat CP 2 System Wire Size Max Length 14 GA 50 Ft 16 GA 32 Ft 18 GA 20 Ft 20 GA 12 Ft 22 GA 9 Ft Thermostat Wire Table Install the supplied battery into the DC S...

Страница 43: ...s needed for the fan blower operation Do not cut the ground terminal off under any circumstances NOTE Even if the fan is not purchased with the unit it is still a good idea to bring power to the receptacle box provided with the unit in case the fan is installed at a later date Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges CAUTION Labelallwires prior to d...

Страница 44: ...o wiring diagram 5 Slide the thermodisc cover assembly on to the bracket clip on the underside of the firebox Thermodisc Clip 6 Install the Fan Control Module FCM on the base of the unit to the left of the gas valve Plug the FCM into the outlet 7 Plug in the fan power cord to the Fan Control Module into the outlet marked Fan Plug the FCM COM wire from the remote control wiring harness into the loc...

Страница 45: ...h from ON to Remote or OFF IMPORTANT The remote control system sup plied with this appliance has several options for starting operating the appliance please readtheremotecontroloperatinginstructions packed with remote control to understand how to operate this remote system Option to download remote functions video with QR code below Proflame video LIGHTING PROCEDURE Important If the pilot does not...

Страница 46: ... injury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qualified installer service agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages des blessures ou la mort Une install...

Страница 47: ...ndismadeofadifferent gauge material from the rest of the firebox and body Therefore thevaryingthicknessesofsteel will expand and contract at slightly different rates which can cause ticking and cracking sounds You should also be aware that as there are temperature changes within the unit these sounds will likely re occur Again this is normal for steel fireboxes Blower Thermodisc When this thermall...

Страница 48: ...ct purchase your replacement from an authorized Regency dealer only and follow our step by step instructions for replacement CAUTION Wear gloves when removing damaged or broken glass FLUSH GLASS REPLACEMENT Remove the flush door front see the Standard Flush Door section Remove the 4 glass clips from each corner Slide in the new replacement glass Push the 4 glass clips back onto the frame The glass...

Страница 49: ... check for proper flame appearance and glow on logs REMOVING VALVE 1 Shut off the gas and electrical supply 2 Remove the faceplate 3 Remove the safety screen and glass door 4 Remove the logs 5 Remove the burner grate assembly by remov ing the two screws and then lift the burner assembly out Diagram 1 Remove the left and right screws and then lift out the burner grate assembly 6 Remove the rear log...

Страница 50: ... Panel Back 34 Brick Panel Left 35 Brick Panel Right 511 031 Brick Clips each Part Description Burner 438 917 Fan Assembly 120V 42 910 331 P Fan Motor 120 V 50 510 994 Rigid Pipe Adaptor 946 556 Heat Wave Duct Kit Optional 89 946 004 Junction Box 90 946 000 Round Duct Adaptor 91 946 002 Round to Oval Adaptor 92 946 001 Oval Duct Adaptor 93 946 007 Angle Bracket 94 946 517 P Fan Assembly Heat Wave ...

Страница 51: ...P36 10 Zero Clearance Direct Vent Gas Fireplace 51 51 parts list MAIN ASSEMBLY ...

Страница 52: ...bly Gasket 904 240 Orifice 37 Natural Gas 904 390 Orifice 52 Propane 936 170 Orifice Gasket 910 036 Pilot Orifice NG 910 037 Pilot Orifice LP 79 512 535 Burner Assy 82 511 030 Burner Grate Assy 83 430 101 Rear Log Support Bracket 84 Deflector 85 512 930 Log Set 910 341 Thermopile 910 386 Thermocouple 910 432 Pilot Tube w nuts 910 096 Pilot Hood 910 030 Spark electrode 910 572 Remote receiver 911 1...

Страница 53: ...36 10 Zero Clearance Direct Vent Gas Fireplace 53 53 parts list VIGNETTE FACEPLATE AND FINISHING TRIM Part Description 515 923 Vignette Black Chrome 515 924 Vignette Black 515 926 Vignette Tuscan Sunset ...

Страница 54: ...54 P36 10 Zero Clearance Direct Vent Gas Fireplace 54 notes ...

Страница 55: ...o the distributor or agent Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced replacement parts and is...

Страница 56: ...__________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all your registered products Request automatic email notification of new product updates Stay informed about the current promotions events and special offers on related pro...

Отзывы: