FLUEING
INTRODUCTION
The P121/P121LC/P121RC/P131 uses the
"balanced fl ue" technology Co Axial system.
The inner liner fl ue products of combustion to
the outside while the outer liner draws outside
combustion air into the combustion chamber
thereby eliminating the need to use heated
room air for combustion and losing warm room
air up the chimney.
Note: These
fl ue pipes must not be con-
nected to any other appliance.
The gas appliance and fl ue system must be
fl ueed directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct fl ue gas appliance must use it's own
separate fl ue system. Common fl ue systems
are prohibited.
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped
into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from the fi replace
top.
2) Take each standoff and bend into the cor-
rect shape. Bend up at the bend lines until
the screw holes in the standoff and the
pre-punched screw holes on the fi replace
top line up.
3) Attach the standoff securely to the top
with 4 screws per standoff (on opposite
corners).
FACING & FINISHING REQUIREMENTS
This fi replace is supplied with a 3" metal extension trim above the fi replace. The extension trim may be replaced if the framing is faced with a non-
combustible material placed fl ush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)