background image

Regency

®

 L900-1 Direct Vent Gas Fireplace

20

INST

ALLA

TION

Horizontal Venting with Two (2) 90

o

 Elbows

Horizontal Venting with Three (3) 90

o

 Elbows

One 90

o

 elbow = Two 45

o

 elbows.

 Option      V 

         H + H1

     A) 

2'  Min.       4' Max.

     B) 

3'  Min.       6' Max.

     C) 

4'  Min.       8' Max.

     D) 

5'  Min.            9'  Max. 

     E) 

6' Min.       10' Max.

W i t h   t h e s e   o p t i o n s , 
maximum total pipe length 
is 30 feet with minimum 
of 6 feet total vertical and 
maximum 10 feet total 
horizontal.

Please note minimum 1 foot between 90

o

 elbows is 

required.

VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.

INSTALLATION

One 90

o

 elbow = Two 45

o

 elbows.

Option      V 

  H          V + V1   H + H1

     A) 

2' Min.  1' Max.  3' Min.    2' Max.

     B) 

2' Min.  2' Max.  5' Min.   4' Max.

     C) 

3' Min.  2' Max.  7' Min.    5' Max.

     D) 

4' Min.  3 Max.  9' Min.   6' Max.

     E) 

5' Min.  4' Max.  10' Min.   7' Max.

     F) 

6' Min.  6' Max.  11' Min.   9' Max.

With these options, max. 
total pipe length is 30 feet 
with min. of 11 feet total 
vertical and max. 9 feet total 
horizontal.

Please note min. 1 foot 
between 90

elbows is 

required.

VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.

Содержание Liberty L900 Gas Fireplace L900-LP1

Страница 1: ...re department WARNING Iftheinformationintheseinstructionsarenotfollowedexactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation and service must be performed by a qualified installer service agency or the gas supplier 0...

Страница 2: ...EVER WILL CAUSE BURNS GLASS UNTIL COOLED ALLOW CHILDREN TO TOUCH GLASS CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES ESPECIALLY THE FIREPLACE GLASS AND SHOULD STAYAWAYTOAVOIDBURNSORCLOTHINGIGNITION ...

Страница 3: ...24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appliance installation must comply with the manufacturer s installation instructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the c...

Страница 4: ...s 19 Venting Arrangements 22 Allowable Vertical Terminations 22 Unit Installation with Horizontal Termination 23 Unit Installation with Vertical Termination 24 Unit Installation 25 Horizontal Termination 25 with Flex Vent System 25 High Elevation 26 Gas Line Installation 26 Pilot Adjustment 26 Gas Pipe Pressure Testing 26 SIT 829 Valve Description 26 Aeration Adjustment 27 Wiring Diagram 27 Conver...

Страница 5: ... a difference the label on the unit is the correct one COPY OF SAFETY DECAL For the State of Massachusetts installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts For the State of Massachusetts flexible connectors shall not exceed 36 inches in length For the State of Massachusetts the appli ances individual manual shut off must be a t handle typ...

Страница 6: ...ade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon...

Страница 7: ...Regency L900 1 Direct Vent Gas Fireplace 6 INSTALLATION UNIT DIMENSIONS ...

Страница 8: ...Standards to make you aware of the following YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE CLOTHING OR OTHER FLAMMABLE MATERIALSHOULDNOTBEPLACED ON OR NEAR THE APPLIANCE INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON MORE FREQUE...

Страница 9: ... this appliance Have an authorized inspector dealer or installer review your plans before installation Note For vent terminations refer to ExteriorVent TerminationLocations section HEATWAVE DUCT KIT The HeatWave Air Duct Kit increases the effectivenessofyourfireplacebydispersingwarm air from the fireplace to remote locations in the same room or other rooms in your home Up to two kits may be instal...

Страница 10: ...4mm Min Height 84 2134mm Alcove side wall must have a minimum of 15 3 4 400mm clearance on one side IMPORTANT Must install 1 set of brick panels The operation of this unit without brick panels is prohibited Caution Requirements The top back and sides of the fireplace are defined by standoffs The metal ends of the standoff may NOT be recessed into combustible construction WARNING Fire hazard is an ...

Страница 11: ...el clearances from top of front facing are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram ...

Страница 12: ...local installation codes Do not insulate the fireplace itself 3 The unit does not have to be completely enclosed in a chase You must maintain clearances from the vent to combustible materials See Clearances section Combustible materials can be laid against the side and back standoffs and the stove base 4 Finishing material such as tile river rock etc must not pertrude beyond the front facing flang...

Страница 13: ...or an overlap this overlap must not be exceeded or the glass door will no longer open properly Non combustible wall board is installed up to the flanges on all sides of the unit When installing any additional facing material use the Finishing Template included with the unit to ensure that the finishing material does not exceed the allowable overlap The Finishing Template uses two magnets to attach...

Страница 14: ...rictor plate to the required vent restrictor position as per the diagrams shown 6 Oncetheventrestrictorplateisintherequired position secure with screws Door Hinge 1 Remove the right side mesh by gathering the mesh together and lifting the curved end of the rod up and out of the bracket located on the top right of the glass frame Now slide the straight end of the rod out from the bracket located on...

Страница 15: ...nded above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on public property 84 2 1m N Clearance under veranda...

Страница 16: ...ystem Termination Kits include all the parts needed to install the L900 1 using a flexible vent Notes 1 Liner sections should be continuous without any joints or seams 2 Only Flex pipe purchased from FPI may be used for Flex installations 3 Horizontal vent must be supported every 3 feet 4 Awallthimbleismandatoryforallhorizontalterminations due to high temperatures FPI Kit Length Contains 946 615 4...

Страница 17: ...ot be recessed into siding Measure the wall thickness including furring strips If a Vinyl Siding Standoff is required it must be used with vinyl siding measure to outside surface of wall without siding and add 2 inches Alternate Horizontal Termination Caps When using Rigid Vent other than Simpson Dura Vent 3 screws must be used to secure rigid pipe to adaptor The FPI AstroCap XLTM is certified for...

Страница 18: ...WS N A Offset Support 58DVA ES N A from FPI 5DT OS N A N A Wall Thimble Black 58DVA WT 5DT WT 5DWT TE 5DE90 Wall Thimble Support Ceiling Support 58DVA DC N A from FPI N A N A TE 5DE90B Firestop Spacer 58DVA FS 5DT FS 5DFS N A Trim Plate Black 58DAV WFS 5DT TP 5DCP N A 5 X 8 RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed Not all rigid pipe components are a...

Страница 19: ...rd Optional 946 606 Starter collar reducer 5 x 8 to 4 x 6 5 8 946 625 Vinyl Siding Standoff AstroCap XL Note When using Metal Fab Sure Seal Rigid Piping please note that the Adaptor 4DDA must be used in conjunction with FPI Rigid Pipe Adaptor 510 994 Offset Pipe Selection Use this table to determine offset pipe lengths Pipe Length L 5 x 8 Venting For specific instructions on venting components vis...

Страница 20: ...d in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A wall thimble is mandatory for all horizontal terminations due to high temperatures VENT RESTRICTOR SETTING Vent restrictor factory set no adjustment required unless otherwise indicated Refer to the Vent Restrictor Position section for details on ho...

Страница 21: ...mum 1 foot between 90o elbows is required VENT RESTRICTOR SETTING Vent restrictor factory set at Set 1 no adjustment required INSTALLATION One 90o elbow Two 45o elbows Option V H V V1 H H1 A 2 Min 1 Max 3 Min 2 Max B 2 Min 2 Max 5 Min 4 Max C 3 Min 2 Max 7 Min 5 Max D 4 Min 3 Max 9 Min 6 Max E 5 Min 4 Max 10 Min 7 Max F 6 Min 6 Max 11 Min 9 Max With these options max total pipe length is 30 feet w...

Страница 22: ... B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 8 Max 9 Min One 90o elbow Two 45o elbows Withtheseoptions max total pipelengthis30feetwithmin of9feettotalverticalandmax 8 feet total horizontal Please note min 1 foot between 90o elbows is required VENT RESTRICTOR SETTING Vent restrictor factory set at Set 1 no adjustment required ...

Страница 23: ...al Gas Two 45o elbows equal to one 90o elbow Maximum of four 45o elbows allowed Vent must be supported at offsets Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles as listed in the Clearances section Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting of Set 1 to Set...

Страница 24: ...the left side on the left 2 DirectVentpipeandfittingsaredesignedwith special twist lock connections to connect the venting system to the appliance flue outlet A twist lock appliance adaptor is required 3 In conjunction with the Simpson Direct Vent Prosystem installtheadaptoraftertheunitis set in its desired location Put a bead of high temperature silicone inside the outer section of the adapter an...

Страница 25: ... ceiling to the position of the appliance flue exit andmarkthelocation where the vent will penetrate the ceiling Drill a small hole at his point Next drop a plumb bob from the roof to the hole previously drilled in the ceiling and mark the spot where the ventwillpenetratetheroof Determineifceiling joists roof rafters or other framing will obstruct the venting system You may wish to relocate theapp...

Страница 26: ...wall ceiling or at the termination where the use of a firestop or wall thimble reduces the required clearance to 1 1 2 38mm Werecommendframinga11 279mm x 11 279mm inside dimensions hole to give structural rigidity for mounting the termination 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit Locate the centerline of the termination and mark wall accordingly...

Страница 27: ...ion Point HIGH ELEVATION This unit is approved in Canada for altitude 0 to 4500 ft CAN1 2 17 M91 GAS LINE INSTALLATION Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN CGA B149 installation code For USA installations follow local codes and or the current National Fuel Gas Code ANSI Z223 1 When using copper or flex connectors...

Страница 28: ...o be able to access the shutters Minimum Air Shutter Opening NG 1 8 LP 1 2 CAUTION Labelallwirespriortodisconnection when servicing controls Wiring errors can cause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges CAUTION Carbon will be produced if air shutter is tightly closed Note Any damage due to carboning resulting from...

Страница 29: ...ve the burner tube by removing the 2 screws Burner Tube 3 Remove the glass door a Release the 2 door latches on the left and right side at the top of the firebox b Swingthedooroutfromthetopandrelease the hinge on the left side of the door and lift out Latch Latch Location Door Hinge Front Cover Plate Right Side Pin Shown 2 Remove the front cover plate by lifting up off of the pins on the left and ...

Страница 30: ...with completing unit installation NOTE Once the unit has been installed Installer Notice This instructions must be left with the appliance a Turn on the gas supply and check for gas leaks b Check the inlet and outlet pressures c Check operation of flame control using the remote control d Check for proper flame appearance 10 Undo the center wire clip on the side of the firebox 11 Unplug the wire ha...

Страница 31: ...els from the protective wrapping Note The logs must not be in the unit 5 Remove the 2 brick panel clips on the inside top left and top right side of the firebox by removing the screw Latch Location Diagram 1 Diagram 2 Diagram 3 Diagram 4 Diagram 5 Diagram 6 Diagram 7 Screw L676 1 L900 1 Brick Panel Clip 1 Remove the right side mesh by gathering the mesh together and lifting the curved end of the r...

Страница 32: ...0 1 Left Side Brick Panel 7 Install the back brick panel by carefully placing it against the back wall of the firebox as shown Back Brick Panel Burner Orifice Cover Plate 6 FOR L676 1 UNITS ONLY L900 1 units proceed to step 7 Remove the burner orifice cover plate from the log tray by undoing the 2 screws 10 FOR L676 1 UNITS ONLY Re install the burner orifice cover plate NOTE L676 1 Back Brick Pane...

Страница 33: ...eft F Log Cross Right G Log Cross Front Left 902 179 Vermiculite 902 153 Rock Wool 946 669 Platinum Embers supplied with packaged manual The reference numbers i e A are molded into the rear of each log E C B A D 1 Carefully remove the logs from it s packaging and unwrap them The logs are fragile handle with care do not force into position F G 2 Spread vermiculite along the base of the firebox Verm...

Страница 34: ...otch on the bottom left side of log C onto the 3rd grate post and rest the right side of log C on the 4th grate post 6 Fit log D into the pin on the far left side of log A 3rd Grate Post 4th Grate Post A D A D C C 5 Fit log A into the pins on the log tray A INSTALLATION ...

Страница 35: ... the underside log B onto the 1st and 2nd grate post 9 Fit the top of log F into the pin on the far right side of log A and rest the bottom end of of log F on log C 10 Fit log E into the pins on logs A and B as shown B B 1st Grate Post 2nd Grate Post A F C F E A B E INSTALLATION ...

Страница 36: ...Regency L900 1 Direct Vent Gas Fireplace 35 INSTALLATION Completed Log Set Installation G A D C B F E G 11 Rest the cut out in log G onto the notch in log B G B INSTALLATION ...

Страница 37: ...the outer shell 3 Place the curved end of the right side rod thru the bracket located on the top right of the glass frame 4 Place the straight end of the left side rod thru the inner most bracket hole located on the middle inside top of the outer shell Place the curved end of the left side rod thru the bracket located on the top left of the glass frame Inner Most Bracket Hole Completed Mesh Pull S...

Страница 38: ...g G 3 Slide the bracket on the back of the andiron over the 1st grate post 4 Replace Log B see below 5 For the right side slide the andiron bracket over the 4th grate post 6 Reinstall glass door and mesh 5 For the right side slide the andiron bracket over the 4th grate post 6 Reinstall glass door and mesh Log G 1st Grate Post 4th Grate Post Log B Final Installation L900 1 Final Installation L676 1...

Страница 39: ... gas in the combustion chamber to escape 3 Turn the gas control knob counterclockwise sotheindicatorpointstothe PILOT position Depress the gas control knob fully Depress the igniter button until the pilot lights After approximately one minute release the gas control knob The pilot flame should continue to burn Only when the pilot holds without pressure beingappliedtothegascontrolknob re install th...

Страница 40: ... Do not touch Severe Burns may result Due to high surface temperatures keep children clothing and furniture gasoline and otherliquidshavingflammablevaporsaway Keepburnerandcontrolcompartment clean See installation and operating instructions accompanying appliance DO NOT REMOVE THIS INSTRUCTION PLATE WARNING If you do not follow these instructions exactly a fire or explosion may result causing prop...

Страница 41: ...n of caps pipe and fittings It may be caused by having excessive lateral runs too many elbows and exterior portions of the system being exposed to cold weather 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and consequently loosened Also check mechanical supports such as Wall Straps or plumbers tape for rigidity LOG REPLACEMENT The unit should never be used with b...

Страница 42: ...DC Spark Box DC Spark Box 1 Gathertherightsidemeshtogetherandslide over to the center of the glass door to expose the controls on the right side of the firebox DC SPARK BOX BATTERY REPLACEMENT 1 Gathertherightsidemeshtogetherandslide to the center of the glass door to expose the controls on the right side of the firebox 2 RemovethebatterycoverfromtheDCSpark Box 3 Remove AA battery and replace with...

Страница 43: ... at the top of the firebox b Swingthedooroutfromthetopandrelease the hinge on the left side of the door and lift out Latch Latch Location Door Hinge Front Cover Plate Right Side Pin Shown 3 Remove the front cover plate by lifting up off of the pins on the left and right side of the firebox Right Side Rod with Screen Removed 1 Shut off the gas supply to the unit 2 Remove the right side mesh by gath...

Страница 44: ... valve tray 18 Replace the valve tray and reverse steps to re install 19 Turn on the gas supply and check for gas leaks 20 Re install the rear log stand 21 Re install the burner tube 22 Re install the grate 23 Re install the brick panels 24 Re install the log set 25 Re install the glass door 26 Re install the front cover plate 27 Re install the mesh screen 28 Check the inlet and outlet pressures 2...

Страница 45: ...te 14 547 027 Front Cover Plate 15 522 036F Control Arm 16 522 039 Bracket Control Arm 18 522 024F Gas Line Screen Plate 20 547 901 Brick Panel Set Standard Brown 547 902 Brick Panel Set Standard Red Left Side Panel Top Panel Back Panel Right Side Panel Part Description 25 547 038 Black Mini Mesh 26 547 029 Left Side Rod 27 547 030 Right Side Rod 547 930 Log Set 946 669 Platinum Embers 910 570 GTM...

Страница 46: ...Regency L900 1 Direct Vent Gas Fireplace 45 PARTS LIST PARTS LIST ...

Страница 47: ...r Tube 37 547 050 Grate 42 502 065 Pilot Holder 43 W840470 Gasket Pilot Assembly 46 547 007 Valve Tray 47 547 025 Valve Bracket 48 910 578 Valve NG 829 SIT 547 574 P Valve Assembly NG 547 576 P Valve Assembly LP 910 008 Pilot Assembly NG 910 009 Pilot Assembly LP 904 660 NG Orifice 30 904 431 LP Orifice 49 910 073 Spark Generator Battery Holder 910 074 Spark Generator Switch c w Wire ...

Страница 48: ...Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replace...

Страница 49: ...__________________________________________ Printed in Canada Regency Liberty AstroCap HeatWave Heat Release and FireWizard are trademarks of FPI Fireplace Products International Ltd Register your Regency online at http www regency fire com Copyright 2009 FPI Fireplace Products International Ltd All rights reserved Regency fireplaces are designed with reliability and simplicity in mind In addition ...

Отзывы: