background image

Regency

®

 L676E Direct Vent Gas Fireplace

17

INST

ALLA

TION

INSTALLATION

Description

Simpson

Direct Vent Pro

®

Simpson 

Direct Vent GS

®

Discontinued

Selkirk

 

Direct-Temp™

Metal-Fab

®

Sure Seal

6” Pipe Length, Galvanized

58DVA-06

1208

5DT-6

5D6

6” Pipe Length, Black

58DVA-06B

1208B

5DT-6B

5D6B

9” Pipe Length, Galvanized

58DVA-09

1207

5DT-9

N/A

9” Pipe Length, Black

58DVA-09B

1207B

5DT-9B

N/A

12” Pipe Length, Galvanized

58DVA-12

1206

5DT-12

5D12

12” Pipe Length, Black

58DVA-12B

1206B

5DT-12B

5D12B

18” Pipe Length, Galvanized

58DVA-18

58DVA-18

5DT-18

5D18

18” Pipe Length, Black

58DVA-18B - N/A from FPI

58DVA-18B - N/A from FPI

5DT-18B

5D18B

24” Pipe Length, Galvanized

58DVA-24

1204

5DT-24

5D24

24” Pipe Length, Black

58DVA-24B

1204B

5DT-24B

5D24B

36” Pipe Length, Galvanized

58DVA-36

1203

5DT-36

5D36

36” Pipe Length, Black

58DVA-36B

1203B

5DT-36B

5D36B

48” Pipe Length, Galvanized

58DVA-48

1202

5DT-48

5D48

48” Pipe Length, Black

58DVA-48B

1202B

5DT-48B

5D48B

60” Pipe Length, Galvanized

58DVA-60

58DVA-60

N/A

N/A

60” Pipe Length, Black

58DVA-60B - N/A from FPI

58DVA-60B - N/A from FPI

N/A

N/A

Adjustable Length 3”-10”, Galvanized

N/A

N/A

N/A

5DAL

Adjustable Length 3”-10”, Black

N/A

N/A

N/A

5DALB

Adjustable Length 11”-14”, Galvanized

Disc - See 58DV-08A

Disc - See 58DV-08A

5DT-AJ

N/A

Adjustable Length 11”-14”, Black

Disc - See 58DV-08AB

Disc - See 58DV-08AB

5DT-AJB

N/A

Adjustable Length 17”-24”, Galvanized

Disc - See 58DV-16A

Disc - See 58DV-16A

N/A

N/A

Adjustable Length 17”-24”, Black

Disc - See 58DV-16AB

Disc - See 58DV-16AB

N/A

N/A

Extension Pipe 8-1/2”, Galvanized

58DVA-08A - N/A from FPI

58DVA-08A - N/A from FPI

N/A

N/A

Extension Pipe 8-1/2”, Black

58DVA-08AB

58DVA-08AB

N/A

N/A

Extension Pipe 16”, Galvanized

58DVA-16A - N/A from FPI

58DVA-16A - N/A from FPI

N/A

N/A

Extension Pipe 16”, Black

58DVA-16AB

58DVA-16AB

N/A

N/A

45º Elbow, Galvanized

58DVA-E45

1245

5DT-EL45

N/A

45º Elbow, Black

58DVA-E45B

1245B

5DT-EL45B

N/A

45º Elbow, Swivel, Galvanized

Disc - See 58DVA-E45

1245G

N/A

5D45L

45º Elbow, Swivel, Black

Disc - See 58DVA-E45B

1245BG

N/A

5D45LB

90º Elbow, Galvanized

58DVA-E90

58DVA-E90

5DT-EL90S

N/A

90º Elbow, Black

58DVA-E90B

58DVA-E90B

5DT-EL90SB

N/A

90º Elbow, Swivel, Galvanized

Disc - See 58DVA-E90

Disc - See 58DVA-E90

N/A

5D90L

90º Elbow, Swivel, Black

Disc - See 58DVA-E90B

Disc - See 58DVA-E90B

N/A

5D90LB

90º Starter Elbow, Swivel, Galvanized*

N/A

N/A

N/A

5D90A

Adaptor*

N/A

N/A

N/A

5DDA

Ceiling Support

58DVA-DC

1240

5DT-CS

5DSP

Cathedral Support Box

58DVA-CS

1241

5DT-CSS

5DRS

Wall Support/Band

58DVA-WS

1288

5DT-WS/B

5DWS

Offset Support

58DVA-ES - N/A from FPI

N/A

5DT-OS

N/A

Wall Thimble, Black

58DVA-WT

1247

5DT-WT

5DWT

Wall Thimble Support Box/Ceiling Support

58DVA-DC - N/A from FPI

N/A

N/A

N/A

Firestop Spacer

58DVA-FS

1263

5DT-FS

5DFS

Trim Plate, Black

58DAV-WFS

1242

5DT-TP

5DCP

5” X 8” RIGID PIPE CROSS REFERENCE CHART

Components from different Manufacturers may not be mixed.  Not All Rigid Pipe components are available directly from FPI.

Содержание LIBERTY L676E-LP

Страница 1: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING Iftheinformationintheseinstructionsarenotfollowedexactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation ...

Страница 2: ...ed Home Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appliance installation must comply with the manufacturer s installation instructions and local codes if any In the absence of local codes follow the curre...

Страница 3: ...ents 19 Allowable Horizontal Terminations 19 Venting Arrangements 22 Allowable Vertical Terminations 22 Unit Installation with Horizontal Termination 23 Unit Installation with Vertical Termination 24 Horizontal Termination with Flex Vent System 25 High Elevation 26 Gas Line Installation 26 Pilot Adjustment 26 Gas Pipe Pressure Testing 26 SIT 845 Valve Description 26 Aeration Adjustment 26 Back Up ...

Страница 4: ...the unit and if there is a difference the label on the unit is the correct one COPY OF SAFETY DECAL For the State of Massachusetts installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts For the State of Massachusetts flexible connectors shall not exceed 36 inches in length For the State of Massachusetts the appli ances individual manual shut off ...

Страница 5: ...de directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon ...

Страница 6: ...Regency L676E Direct Vent Gas Fireplace 6 INSTALLATION UNIT DIMENSIONS ...

Страница 7: ... of the following YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE CLOTHING OR OTHER FLAMMABLE MATERIALSHOULDNOTBEPLACED ON OR NEAR THE APPLIANCE INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON MORE FREQUENT CLEANING MAY BE REQUIRED...

Страница 8: ...E Direct Vent Gas Fireplace is approved for alcove installations see Clearances section for details 6 We recommendthatyouplanyourinstallation on paper using exact measurements for clearances and floor protection before actually installing this appliance Have an authorized inspector dealer or installer review your plans before installation Note For vent terminations refer to ExteriorVent Terminatio...

Страница 9: ...mm from top of front facing Side Wall to Unit 15 381mm Horizontal Vent Clearances to Combustibles Top 3 76mm Side 2 51mm Bottom 2 51 mm Vertical Vent Clearances to Combustibles All Sides 2 51mm Alcove Clearances Min Depth 36 914mm Min Width 84 2134mm Min Height 84 2032mm Alcove side wall must have a minimum of 15 381mm clearance on one side Caution Requirements The top back and sides of the firepla...

Страница 10: ...ram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram 4 Allowable mantel leg projection 9 229mm 11 279mm 15 381mm Side wall ...

Страница 11: ...ader must be metal stud 2 For exterior walls insulate the enclosure to the same degree as the rest of the house apply vapour barrier and drywall as per local installation codes Do not insulate the fireplace itself 3 The unit does not have to be completely enclosed in a chase You must maintain clearances from the vent to combustible materials See Clearances section Combustible materials can be laid ...

Страница 12: ...off securely to the top with 2 screws per standoff on opposite corners Side Nailing Strips shown folded out FINISHING TEMPLATE In order to maintain a clean face the L676E allows for a 1 8 in overlap of finishing material such as rock or tile on both the left and right hand sides of the unit top and bottom sides do not allow for an overlap this overlap must not be exceeded or the glass door will no ...

Страница 13: ...chimney Note These flue pipes must not be connected to any other appliance The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas burning appliance Eachdirectventgasappliancemustuseit sown separate vent system Common vent systems are prohibited Vent Restrictor Plate To set the vent restriction...

Страница 14: ...lator J Clearance to service regulator vent outlet min 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet min 72 1 8m 3 91cm above if within 10 3m horizontally M Clearance above paved sidewalk or a paved driveway located on public property min 84 2 1m N Clearance under ver...

Страница 15: ...stall the L676E using a flexible vent Notes 1 Liner sections should be continuous without any joints or seams 2 Only Flex pipe purchased from FPI may be used for Flex installations 3 Horizontalventmustbesupportedevery 3 feet 4 A wall thimble is mandatory for all horizontal terminations due to high temperatures INSTALLATION FPI Kit Length Contains 946 618 6 Feet 1 8 flexible liner Kit length 2 5 flexi...

Страница 16: ...s required it must be used with vinyl siding measure to outside surface of wall without siding and add 2 inches Alternate Horizontal Termination Caps The FPI AstroCap XLTM is certified for installations using FPI venting systems as well as Simpson Dura Vent Direct Vent GS and Selkirk Direct Temp AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direc...

Страница 17: ...h 17 24 Galvanized Disc See 58DV 16A Disc See 58DV 16A N A N A Adjustable Length 17 24 Black Disc See 58DV 16AB Disc See 58DV 16AB N A N A Extension Pipe 8 1 2 Galvanized 58DVA 08A N A from FPI 58DVA 08A N A from FPI N A N A Extension Pipe 8 1 2 Black 58DVA 08AB 58DVA 08AB N A N A Extension Pipe 16 Galvanized 58DVA 16A N A from FPI 58DVA 16A N A from FPI N A N A Extension Pipe 16 Black 58DVA 16AB ...

Страница 18: ... Fab Sure Seal Round Support Radiation Sheild N A N A N A N A Flat Flashing N A N A N A N A Attic Insulation Shield 12 58DVA IS N A from FPI 58DVA IS N A from FPI N A N A Basic Horizontal Termination Kit A N A N A 5DT HKA N A Horizontal Termination Kit B 58DVA KHA N A 5DT HKB N A Vertical Termination Kit 58DVA VCH 1291 5DT VKC N A High Wind Vertical Cap N A N A N A N A High Wind Horizontal Cap DIS...

Страница 19: ...h floor level and whenever passing through a wall A wall thimble is mandatory for all horizontal terminations due to high temperatures VENT RESTRICTOR SETTING NG Units Vent restrictor at Set 0 factory set no adjustment required unless otherwise indicated LP Units Vent restrictor at Set 1 factory set no adjustment required unless otherwise indicated Refer to the Vent Restrictor Position section for ...

Страница 20: ...te minimum 1 foot between 90o elbows is required One 90o elbow Two 45o elbows Option V H V V1 H H1 A 2 Min 1 Max 3 Min 2 Max B 2 Min 2 Max 5 Min 4 Max C 3 Min 2 Max 7 Min 5 Max D 4 Min 3 Max 9 Min 6 Max E 5 Min 4 Max 10 Min 7 Max F 6 Min 6 Max 11 Min 9 Max With these options max total pipe length is 30 feet with min of 11 feet total vertical and max 9 feet total horizontal Please note min 1 foot b...

Страница 21: ...ical and max 10 feet total horizontal Please note min 1 foot between 90o elbows is required Option V H H1 V V1 A 2 Min 2 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 8 Max 9 Min One 90o elbow Two 45o elbows Withtheseoptions max total pipelengthis30feetwithmin of9feettotalverticalandmax 8 feet total horizontal Please note min 1 foot between 90o elbows is required VE...

Страница 22: ...es section Referto VentRestrictorPosition sectionfor details on how to change the vent restrictor to Set 1 Set 2 or Set 3 if required Note Mustuseoptionalflueadapterwhenusing Rigid Pipe Part 770 994 INSTALLATION The shaded area in the diagram shows all allowable combinationsofstraightverticalandoffsettovertical terminations using two 90o elbows with Rigid Pipe Venting Systems for Propane and Natura...

Страница 23: ...edwith special twist lock connections to connect the venting system to the appliance flue outlet A twist lock appliance adaptor is required 3 In conjunction with the Simpson Dura Vent Direct Vent GS system Install the adaptor after the unit is set in its desired location Put a bead of high temperature silicone inside the outer section of the adapter and a bead of Mill Pack on the inner collar Slip ...

Страница 24: ...mtheceiling to the position of the appliance flue exit andmarkthelocation where the vent will penetratetheceiling Drill a small hole at his point Next drop a plumb bob from the roof to the hole previously drilled in the ceiling and mark the spot where the ventwillpenetratetheroof Determineifceiling joists roof rafters or other framing will obstruct the venting system You may wish to relocate theapp...

Страница 25: ...n where the use of a firestop or wall thimble reduces the required clearance to 1 1 2 38mm Werecommendframinga11 279mm x 11 279mm inside dimensions hole to give structural rigidity for mounting the termination 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the left Locate the centerline of the termi...

Страница 26: ...not use open flame for leak testing Note Ifyouhaveanincorrectflamepattern contact your Regency dealer for further instructions Incorrect flame pattern will have small probably yellow flames not coming into proper contact with the rear burner or flame sensor Periodically check the pilot flames Correct flame pattern has three strong blue flames 1 flowing around the pilot 1 flowing around the flame sensor and 1...

Страница 27: ...Shield 8 Re install the heat shield 2 Remove the plastic pin protectors from the battery 5 Pull out the black and red battery wires from the right side of the firebox 1 Unsecure the battery from the outer firebox base flange by cutting the cable tie and remove from protective wrapping Battery Wires 6 Connect the red and black wires to the battery accordingly 7 Place the battery into position at the b...

Страница 28: ...release the hinges on the left and right side of the door by lifting them up Latch c Place the door on a soft surface to prevent scratching 2 Unwrap the brick panels from the protective wrapping Note The logs must not be in the unit 3 Remove the 2 brick panel clips on the inside left and right side of the firebox by removing the screw Hinge Door Latch Location Screw Brick Panel Clip 4 Place the 2 ...

Страница 29: ... slot of the exterior base brick panel The top of the brick panel is held in place by a magnet that sits against the bracket as shown in the image below Repeat for left side exterior brick panel Outerbox of Firebox Tab Bracket Exterior Brick Panel Installation L e f t Side Brick Panel Base Brick Panel Slot Top Brick Panel Top Brick Panel Right Side Brick Panel Brick Panel Clip 6 Place the top bric...

Страница 30: ...he logs from the box and unwrap them The logs are fragile handle with care do not force into position 2 Place log 03 25 on the rear log support pins The 03 reference numbers i e 03 25 are molded into the rear of each log 3 Place log 03 27 on the front left side of the burner Place the right end of the log into the pin and rest the left end of the log inbetween the rear and front burner tubes 03 28...

Страница 31: ... tube and the grate as shown Separateplatinumembersandplaceontheembersaroundtheburner tube and inbetween the front burner tube and grate Avoid stacking platinum embers 03 25 03 27 03 26 03 28 Complete Log Set Installation 7 Spreadthevermiculiteonthebasebrickpanelcoveringtheremaining exposed base brick Embers on bottom brick panel Embers in between front burner tube and grate ...

Страница 32: ... prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges Black Orange Black Green Reset Button Lockout Led NEUTRAL white LIVE black red black J7 ECS MODULE A B D E C 2 1 NG LP jumper B Flame Sensor Spark Ignitor yellow green white white black orange BURNER REAR ...

Страница 33: ...to differentiate one Remote Control Handset from another so that only the control box with a matching ID code will respond to the appropriate Remote Control Handset To ensure the remote control is matched to the receiver correctly please follow the steps below 1 Install the 2 x AAA alkaline batteries into the Remote Control 2 Unplug and re plug the power cord The power cord is located on the left ...

Страница 34: ...ds You should also be aware that as there are temperature changes within the unit these sounds will likely re occur Again this is normal for steel fireboxes Pilot Flame While the pilot flame is on it can make a very slight whisper sound Gas Control Valve As the gas control valve turns ON and OFF a dull clicking sound may be audible this is normal operation of a gas regulator or valve Unit Body Fireb...

Страница 35: ...ure gasoline and otherliquidshavingflammablevaporsaway Keepburnerandcontrolcompartment clean See installation and operating instructions accompanying appliance DO NOT REMOVE THIS INSTRUCTION PLATE WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Improper installation adjustment alteration service or mainte...

Страница 36: ...r other foreign material 3 Check for evidences of excessive condensation suchaswaterdropletsforming in the inner liner and subsequently dripping outthejoints Continuouscondensationcan cause corrosion of caps pipe and fittings It may be caused by having excessive lateral runs too many elbows and exterior portions of the system being exposed to cold weather 4 Inspect joints to verify that no pipe sec...

Страница 37: ...ting off the velcro and bring out from the side of the firebox CONTROL BOX REPLACEMENT 1 Remove the exterior brick panels 2 Remove the glass door a Release the 2 door latches on the left and right side at the top of the firebox b Swing the door out from the top and release the hinges on the left and right side of the door by lifting them up Hinge Door Latch Latch Location 3 Loosen the 2 screws that ...

Страница 38: ... side of the firebox 6 Disconnect the wire harnesses from the control board labelled A C D E F Do not disconnect the the jumper cables labelled B 7 Disconnect the spark cable and flame sensor wires from the control board 8 Remove the cable tie from control box to release the wires Do not discard cable tie 9 Remove the ground screw from the side of the control box Do not discard the ground screw F A ...

Страница 39: ... left and right side of the door by lifting them up Hinge Door Latch Latch Location VALVE TRAY REPLACEMENT 3 Remove the log set 4 Remove the interior brick panels 5 Remove the grate by undoing the 2 screws on the left and right side Grate 6 Remove the front burner by removing the screw Front Burner Front Burner Removed 7 Remove the back burner by removing the screw Back Burner 8 Remove the rear lo...

Страница 40: ...ect both sources of power the power cord located on the left hand side of the firebox and the wires connected to the back up battery located on the right side of the firebox Back up Battery shown 13 Disconnect the inlet gas line from the valve 14 Disconnect the 2 connectors from the modulating coil and the wire harness Connectors Wire Harness Wire Harness Disconnected 15 Remove the control box by ca...

Страница 41: ...Replace the valve tray and reverse steps to re install Ensure to check the gasket around the valve tray opening 20 Turn on the gas supply and check for gas leaks 21 Plug in the power source 22 Re install the grate 23 Re install the interior brick panels 24 Re install the log set 25 Re install the glass door 26 Check the inlet 12 WC and outlet 10 WC 27 Re install the right heat shield 28 Check oper...

Страница 42: ...e Faceplate 15 521 079 Valve Heat Shield 16 910 950 Control Box with Igniter Battery Backup IPI 910 075 Backup Battery 17 521 075 Outer Control Box Cover 20 521 901 Brick Panel Set Standard Brown 521 902 Brick Panel Set Standard Red Left Side Panel Interior Top Panel Interior Back Panel Interior Right Side Panel Interior Right Side Panel Exterior Base Panel Exterior Left Side Panel Exterior 521 93...

Страница 43: ...0 521 063 Bracket Log Position 41 502 061 Pilot Shield 42 380 013 Pilot Holder 43 W840470 Gasket Pilot Assembly 46 521 007 Valve Tray 521 034 Valve Tray Gasket 47 521 025 Valve Bracket 48 910 480 Valve 845 SIT Electric 521 574E P Valve Assembly NG 521 576E P Valve Assembly LP 910 952 Pilot Assembly NG 910 953 Pilot Assembly LP 904 617 NG Orifice 34 904 622 NG Orifice 48 904 241 LP Orifice 56 904 345 ...

Страница 44: ...Regency L676E Direct Vent Gas Fireplace 44 NOTES ...

Страница 45: ...Regency L676E Direct Vent Gas Fireplace 45 NOTES ...

Страница 46: ...Regency L676E Direct Vent Gas Fireplace 46 NOTES ...

Страница 47: ...he authorized selling dealer is responsible for all in field service work carried out on your Regency product FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to FPI by authorized selling dealers It is essential that ...

Страница 48: ...__________________________________________ Printed in Canada Regency Liberty AstroCap HeatWave Heat Release and FireWizard are trademarks of FPI Fireplace Products International Ltd Register your Regency online at http www regency fire com Copyright 2008 FPI Fireplace Products International Ltd All rights reserved FPI fireplaces are designed with reliability and simplicity in mind In addition our in...

Отзывы: