L676-1 Direct Vent Gas Fireplace
9
INST
ALLA
TION
INSTALLATION
Caution Requirements
The top, back and sides of the
fi
replace are de
fi
ned by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fi
replace and vent system be installed only in
accordance with these instructions.
IMPORTANT
If converting this unit to LP, it is highly recommened
the conversion be done BEFORE the unit is slid into
position for ease of conversion. See "Conversion
from NG to LP" section for instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related
fi
res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this
fi
replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel
min. 16-1/2" (419mm)
Ceiling
52"
(813mm) from top of front facing
Side Wall to Unit:
14-3/4"*
(375mm)
Horizontal Vent Clearances to Combustibles:
Top
3" (76mm)
Side
2" (51mm)
Bottom
2" (51
mm)
Vertical Vent Clearances to Combustibles:
All Sides
2" (51mm)
Alcove Clearances:
Min. Depth
36"
(914mm)
Min. Width*
84"
(2134mm)
Min. Height
84"
(2032mm)
* Alcove side wall must have a minimum of 14-3/4" (375mm) clearance on one side.
IMPORTANT:
Must install 1 set of brick panels. The operation of this unit without brick panels is prohibited.
NOTE:
Only materials such as, but not limited to durarock,
wonderboard and concrete board may be put on the front face
of this appliance. See speci
fi
c requirements under "Framing
and Finishing" section.