L390E / HZI390E Direct Vent Gas Insert
11
INSTALLATION
A
C
B
E
K
D
L
G
Diagram 1
Diagram 2
Note: A noncombustible mantel may be
installed at a lower height if the framing
is made of metal studs covered with a
noncombustible board.
Max
12"
Door
Opening
24" Min
From Top of
24
26
28
30
32
34
36
38
0
2
4
6
8
10
12
14
16
18
20
22
24
Allowable
Mantel Area
)URPERWWRP
RIXQLW
* For every 1" the mantel is above the minimum height,
the mantel can extend out 1 additional inch past the
maximum length of 12". This chart is for illustration only.
The mantel can extend above and beyond this chart,
as long as it complies with this criteria.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Clearance:
Dimension
Measured From:
A: Sides
6" / 152 mm
side of unit
B: Ceiling
60" / 1524 mm
top of unit
C: Mantel (Min. Height)
24" / 610mm
0" out to12" (305mm) deep
D:Min. Hearth Width
14" / 356mm
E: Min. Hearth Length
40"/ 1016mm
G: Max. Mantle Depth
0 -
12" / 305 mm
@ 44" (1118mm) from bottom of unit
K: Min. Alcove Width
54" / 1372 mm
L: Max. Alcove Depth
36" / 914 mm
Notes:
Non-combustible hearth required.
0-