HZ33CE Gas Fireplace

MANTEL CLEARANCES

Note:  Ensure the paint that is used on the mantel 

and the facing is "heat resistant" or the 

paint may discolour.

MANTEL LEG CLEARANCES

Combustible mantel leg clearances from side of unit as per diagram:

Top View

0-3

Allowable mantel leg projection

6-3/4"

9"

Side opening of Unit

Due to the extreme heat this fireplace emits, the 

mantel clearances are critical. 

Combustible mantel 

clearances from top of front facing are shown in the 
diagram on the right.

Note:  A non-combustible mantel may be 

installed at a lower height if the framing 

is made of metal studs covered with a 

non-combustible board.

Drywall

Mantel Clearances

2

0

12

6

4

8

10

2

0

12

6

4

8

10

Top opening

of Unit

12" (305mm)

0 - 3-1/2" (89mm)

7-1/2"(191mm)

15-3/4" (400mm)

11-3/4"(298mm)

13-3/4"(349mm)

24-1/4"(616mm)

to floor

3"(76mm)

Standoff

Side View

16

14

Non-combustible material

Содержание HZ33CE

Страница 1: ...d Venting Systems Flex Vent Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro American Metal Products Amerivent Direct Security Secure Vent Selkirk Direct Temp Metal Fab Sure Seal 34 9 16 16 407mm 23 584mm 878mm 26 1 16 662mm 406mm 16 NAILING STRIP 2 1 2 64mm 742mm 29 1 4 21 3 8 543mm 26 660mm 29 7 16 747mm 742mm 29 1 4 76mm 3 Framing Dimensions Description HZ33CE G Fr...

Страница 2: ...ed fires is failure to maintain required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions C F G Clearance Dimension Measured From A Front Floor Clearance min 0 Underside of Unit B Sidewall on one side 9 229mm Side Opening of Unit C Ceiling room and or alcove 30 762mm Top Openin...

Страница 3: ...eme heat this fireplace emits the mantel clearances are critical Combustible mantel clearances from top of front facing are shown in the diagram on the right Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Drywall Mantel Clearances 2 0 12 6 4 8 10 2 0 12 6 4 8 10 Top opening of Unit 12 305mm 0 3 1 2 89mm 7 ...

Страница 4: ...ll cannot extend beyond the metal surface of the unit 5 Tile Finish Option 2 If applying a non combustible finishing material tile slate etc the material can be installed directly onto the metal surface clean front of the unit in the area shown below 29 7 16 747mm 21 3 8 542mm Nailing strip for Tile Finish set back 1 2 Nailing strip for Clean Finish set flush with unit TILE FINISH 1 There are 8 ei...

Страница 5: ...nly to the flanges around the firebox opening Rough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal cornerbead both materials available at your local building or hardware store IMPORTANT Materials used must be NON COMBUSTIBLE CLEAN FINISH 6 If applying a non combustible facing it may be installed over the metal...

Страница 6: ...rtical and offset to vertical terminations using one 90o elbow with rigid pipe vent systems for Propane and Natural Gas Unit must be raised 1 Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles Vent must be supported at offsets Note Must use optional rigid pipe adapter when using rigid vent systems Part 510 994 ...

Страница 7: ...and one 90o elbow two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer Rigid Pipe Venting Systems Section Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the terminationis...

Отзывы: