HZ33CE Gas Fireplace

M

L

K

P Q

O

N

Opening for gas

connection

J

I

Floor

DETAIL N

SCALE 1 : 6

2X4 HEADER

N

Non-combustible

Header

(steel stud

on edge)

G

H

I

J

*  Measured from base of unit.

Model

HZ33CE-NG10

HZ33CE-LP10

Fuel Type

Natural Gas

Propane

Minimum Supply Pressure

5” W.C. (1.25 kPa)

11” W.C. (2.73 kPa)

Manifold Pressure - High

3.5” W.C. (0.87 kPa)

10” W.C. (2.48 kPa)

Manifold Pressure - Low

1.6” W.C. (0.41 kPa)

6.4” W.C. (1.59 kPa)

Orifice Size -

Altitude 0-4500 ft.

#47 DMS 

#56 DMS 

Minimum Input  

Altitude 0-4500 ft. (0-1372m)

12,000 BTU/h   

(3.51 kW)

12,500 BTU/h 

(3.66 kW) 

Maximum Input 

Altitude 0-4500 ft. (0-1372m)

17,000 BTU/h 

(4.98 kW)

15,000 BTU/h 

(4.39 kW)

Vent Sizing

4” x 6-7/8” - Flex

4” x 6-5/8” - Rigid

4” x 6-7/8” - Flex

4” x 6-5/8”- Rigid

Approved Venting Systems

Flex Vent Systems:

FPI AstroCap™ Flex Vent

Rigid Pipe Vent Systems:

Simpson Direct Vent Pro®

American Metal Products® Amerivent Direct

Security Secure Vent® 

Selkirk Direct-Temp™

Metal-Fab® Sure Seal

34-9/16"

16

"

40

7m

m

23"

584mm

[878mm]

26

-1

/1

6"

(6

62

m

m

)

(406mm)

16"

NAILING STRIP

2-1/2"

[64mm]

74

2m

m

29

-1

/4

"

21-3/8" 5

43

m

m

26"

660mm

29-7/16"

747mm

74

2m

m

29

-1

/4

"

(76mm)

3"

Framing 

Dimensions

Description

HZ33CE

G

Framing Width

35"(889mm)

H

Framing Height *

31-3/4" (806mm)

I

Framing Rise from Floor

0" (when not using a surround)

2" min (when using Casandra Surround )

3-5/16" min (when using Verona Faceplate)

J *  For Finish with 

Tile Surround

Framing Depth      Vertical
                              Horizontal

22-3/4" (578mm) 

Vertical Rise

19-3/4" (502mm) 

Rigid

 / 16" (406mm) 

Flex

K

Corner Wall Length

38-15/16" (988mm)

L

Corner Facing Wall Width

55-1/2" (1410mm)

M

Framed Chase Ceiling*

36" (914mm) 

Rigid

32" 
(812mm) 

Flex

N

Vent Centerline Height*

30" (762mm) 

Rigid

26" 
(660mm) 

Flex

O

Gas Connection Height*

1 1/2" (38mm)

P

Gas Connection Inset*

7-3/16" (183mm)

Q

Gas Connection Width*

3" (76mm)

Содержание HZ33CE

Страница 1: ...d Venting Systems Flex Vent Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro American Metal Products Amerivent Direct Security Secure Vent Selkirk Direct Temp Metal Fab Sure Seal 34 9 16 16 407mm 23 584mm 878mm 26 1 16 662mm 406mm 16 NAILING STRIP 2 1 2 64mm 742mm 29 1 4 21 3 8 543mm 26 660mm 29 7 16 747mm 742mm 29 1 4 76mm 3 Framing Dimensions Description HZ33CE G Fr...

Страница 2: ...ed fires is failure to maintain required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions C F G Clearance Dimension Measured From A Front Floor Clearance min 0 Underside of Unit B Sidewall on one side 9 229mm Side Opening of Unit C Ceiling room and or alcove 30 762mm Top Openin...

Страница 3: ...eme heat this fireplace emits the mantel clearances are critical Combustible mantel clearances from top of front facing are shown in the diagram on the right Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Drywall Mantel Clearances 2 0 12 6 4 8 10 2 0 12 6 4 8 10 Top opening of Unit 12 305mm 0 3 1 2 89mm 7 ...

Страница 4: ...ll cannot extend beyond the metal surface of the unit 5 Tile Finish Option 2 If applying a non combustible finishing material tile slate etc the material can be installed directly onto the metal surface clean front of the unit in the area shown below 29 7 16 747mm 21 3 8 542mm Nailing strip for Tile Finish set back 1 2 Nailing strip for Clean Finish set flush with unit TILE FINISH 1 There are 8 ei...

Страница 5: ...nly to the flanges around the firebox opening Rough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal cornerbead both materials available at your local building or hardware store IMPORTANT Materials used must be NON COMBUSTIBLE CLEAN FINISH 6 If applying a non combustible facing it may be installed over the metal...

Страница 6: ...rtical and offset to vertical terminations using one 90o elbow with rigid pipe vent systems for Propane and Natural Gas Unit must be raised 1 Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles Vent must be supported at offsets Note Must use optional rigid pipe adapter when using rigid vent systems Part 510 994 ...

Страница 7: ...and one 90o elbow two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer Rigid Pipe Venting Systems Section Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the terminationis...

Отзывы: