FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.  6988 Venture St., Delta, BC  Canada, V4G 1H4

918-521d

10/28/13

P36  Zero  Clearance

Direct  Vent  Gas  Fireplace

Owners & Installation Manual

Tested by:

Installer: Please complete the details on the back cover 

and leave this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

MODELS:    P36-NG4 Natural Gas     P36-LP4  Propane

WARNING:  
If the information in these instructions are not followed exactly, a fi re 
or explosion may result causing property damage, personal injury or 
loss of life.  

FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and liquids in the 
vicinity of this or any other appliance.

Installation and service must be performed by a qualifi ed installer, service 
agency or the gas supplier.

FOR YOUR SAFETY
What to do if you smell gas:

Do not try to light any appliance

Do not touch any electrical switch: do not 
use any phone in your building.

Immediately call your gas supplier from 
a neighbour's phone. Follow the gas 
supplier's instructions.

If you  cannot reach your gas supplier, 
call the fi re department.

P36 Video

Содержание P36-LP4 Propane

Страница 1: ...xactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this...

Страница 2: ...ide you with all the warmth and charm of a wood fireplace at the flick of a switch The model P36 has been approved by Warnock Hersey for both safety and efficiency As it also bears our own mark it pro...

Страница 3: ...the manufacturer s installation instructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI N...

Страница 4: ...ons 49 MAINTENANCE Maintenance Instructions 49 General Vent Maintenance 49 Log Replacement 50 Thermopile Thermocouple 50 Glass Gasket 50 Door Glass 50 Flush Glass Replacement 50 Removing Valve 51 Inst...

Страница 5: ...PI P36 4 Zero Clearance Direct Vent Gas Fireplace 5 5 TABLE OF CONTENTS Finishing Trim 53 PARTS LIST Main Assembly 54 Burner Assembly Log Set 55 Regency Flush Front Accessories 56 WARRANTY Warranty 59...

Страница 6: ...Btu h 8 79kW This appliance must be installed in accordance with local codes if any if none follow the National Fuel Gas Code ANSI Z223 1 or Natural Gas and Propane Installation Code CSA B149 1 This a...

Страница 7: ...directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT...

Страница 8: ...8 FPI P36 4 Zero Clearance Direct Vent Gas Fireplace DIMENSIONS UNIT DIMENSIONS 32 1 2 826mm 36 940mm 30 1 2 775mm 12 3 4 324mm 36 914mm 33 1 4 838mm 36 914mm...

Страница 9: ...done by a qualified service per son A professional service person should be called to inspect this appliance annually Make it a practice to have all of your gas appliances checked annually 13 Do not s...

Страница 10: ...ing the full width and depth of the appliance 4 The P36 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A B C D See Diagram 1 Note For vent terminat...

Страница 11: ...ned from the top surface of the carpeting tile etc Minimum Clearance from Top of Unit to Ceiling from top of unit 32 1016mm Flush Front 6 152mm Full Screen Doors 6 152mm Measured from Surround or Fron...

Страница 12: ...12 FPI P36 4 Zero Clearance Direct Vent Gas Fireplace INSTALLATION REGENCY CLEARANCES TRIPOLI ARCH DOOR CLEARANCES Clearances for Flush Front Full Screen Doors Note No Hearth Required...

Страница 13: ...SERIES COMBUSTIBLE MANTEL CLEARANCES These drawings are to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is...

Страница 14: ...mantel clearances are critical Combustible mantel clearances from top of unit are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of...

Страница 15: ...rch Door a non combustible material 12 305mm above the unit and 6 153mm on each side must be used See diagram 2 For complete framing dimensions see page 57 in this manual The Tripoli Arch Door also re...

Страница 16: ...4 36 1 4 12 3 4 46 921mm 921mm 324mm 1168mm D is Minimum height to combustible mate rials including the Minimum 2 51mm Top clearance to the Horizontal Vent 12 3 4 3 1 2 4 2 40 1 2 36 32 1 2 10 dia hol...

Страница 17: ...combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney Note These flue pipes must not be connected to any other appliance The gas...

Страница 18: ...extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any oth...

Страница 19: ...ermination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 1 6 7 8 dia flexible liner 10 ft length 2 4 dia flexible liner 10 ft length 3 sprin...

Страница 20: ...N A N A Adjustable Length 3 10 Galvanized N A N A N A 4DAL N A TC 4DLT Adjustable Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable L...

Страница 21: ...ontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHT...

Страница 22: ...Wall Installation Wall Thickness inches Vent Length Required inches 4 5 1 2 6 7 8 1 2 9 10 1 1 2 12 9 14 1 2 11 14 5 8 Adj Pipe 15 23 1 2 17 24 Adj Corner Installation Wall Thickness inches Vent Leng...

Страница 23: ...diameter 6 7 8 inner diameter Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall NOTE If...

Страница 24: ...elbows is required A 0 Min 2 Max B 1 Min 3 Max C 2 Min 4 Max D 3 Min 5 Max E 4 Min 6 Max F 5 Min 7 Max G 6 Min 8 Max Lengths do not include elbow indicated Option V H V V1 H H1 With these options max...

Страница 25: ...in 2 Max 1 Min B 1 Min 4 Max 2 Min C 2 Min 5 Max 3 Min D 3 Min 6 Max 4 Min E 4 Min 7 Max 5 Min F 5 Min 8 Max 6 Min Lengths do not include elbow indicated For additional vertical venting with 2 x 90o e...

Страница 26: ...learances to combustibles Note Must use optional rigid pipe adaptor when using rigid vent systems Part 510 994 RIGID PIPE VENTING ARRANGEMENTS VERTICAL TERMINATIONS Propane Natural Gas The shaded area...

Страница 27: ...s as per the diagram 1 The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural G...

Страница 28: ...chimneys may take various contours which the flexible liner will accommodate However keep the flexible liner as straight as possible avoid unnecessary bending The Air Intake pipe must be attached to...

Страница 29: ...ded area in the diagrams show the allowable vertical terminations 8 Min 40 1 2 30 Max 30 Horizontal Distance Feet Vertical Height feet 2 max VENTING ARRANGEMENTS VERTICAL TERMINATION with Co linear Fl...

Страница 30: ...rocedure Four indenta tions located on the female ends of pipes and fittings are designed to slide straight onto the male ends of adjacent pipes and fittings by orienting the four pipe indentations so...

Страница 31: ...n the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect th...

Страница 32: ...o Offset Chart DIRECT VENT SYSTEM FLEX INSTALLATION PROCEDURES 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the le...

Страница 33: ...tu h Minimum Output with blower Off 11 500 Btu h Supply Pressure min 5 0 w c Manifold Pressure High 3 8 0 2 w c Electrical 120 V A C System Circulation Fan variable speed 130 CFM Log Set Ceramic fibre...

Страница 34: ...closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 45 kPa Disconnect piping from valve at press...

Страница 35: ...910 037 LPG Injector Pilot Orifice 1 918 481 Instruction Sheet 5 Remove the 2 screws holding the Burner Assembly to the firebox base Push the Burner Assembly to the left and lift out DC Sparker Kit Co...

Страница 36: ...and connect it to the DC Sparker Piezo Ignitor Ignitor Wire Piezo Ignitor Ignitor Wire DC Sparker 18 Reverse steps 6 1 Fig 1 11 Remove the black protection cap by hand from the hi low knob Fig 1 Fig...

Страница 37: ...and outlet pressures 37 Check operation of flame control 38 Check for proper flame appearance and glow on logs NOTE The battery in the DC Sparker Box will need to be replaced an nually 25 Locate the g...

Страница 38: ...in the unit 2 Insert the back brick panel first by carefully slipping it between the back wall of the firebox and the rear log bracket 3 Put the side panels in next Slide them in from the front and pu...

Страница 39: ...miculite j 946 669 Platinum Embers supplied w packaged manual 4 Place Log 02 51 on the front right side of the burner Push the back of the log against the 2 brackets with the notch on the bottom right...

Страница 40: ...front brackets with the notch on the bottom of the log fitting into the first grate tab Notch 02 55 02 50 02 54 5 Position Log 02 53 across the cutouts in Logs 02 49 and 02 51 with the notch on the l...

Страница 41: ...and on the indentation on Log 02 54 The bottom right end sits behind the rear grate tab 10 Place the embers on the front of the burner tray in the places shown on the photo Separateplatinumembersandp...

Страница 42: ...The standard flush door comes with a black frame To install the frame simply hook the top door flange onto the top of the unit and swing the door towards the unit see Diagram 1 Be careful that the gl...

Страница 43: ...SWITCH OPTIONAL 1 Run the wire through the right or left side inlet opening Be careful not to damage wire Note We recommend a maximum of 15 of wire but if you wish to go with a longer run use the Ther...

Страница 44: ...ptional remote control thermostat will continue to operate However a 120V A C power supply is needed for the fan blower operation Do not cut the ground terminal off under any circumstances NOTE Even i...

Страница 45: ...use by stove fan only 120 Volts 60 Hz Copper Ground White Neutral Black Hot P36 E lectrical Connection Alternative Scheme B Power at Switch Wall Junction Box Speed Control S witch with lead wires Wire...

Страница 46: ...36 4 Zero Clearance Direct Vent Gas Fireplace INSTALLATION For PROPANE Units and Units Equipped with DC Spark Boxes For installation of the DC Spark Box refer to the LP Conversion instructions in this...

Страница 47: ...ainst the valve tub ing Diagram 1 8 Secure the two boxes together with one screw 10 Remove the control box assembly and push the hold downclipontothelouver Bend the tab until it is at 90o to the louve...

Страница 48: ...ses of steel will expand and contract at different rates resulting in some cracking and ticking sounds will be heard throughout the cycling process IMPORTANT Gas on off knob cannot be turned from PILO...

Страница 49: ...the flames are steady not lifting or floating If there is a problem call a qualified service person 5 The appliance and venting system must be inspected before use and at least annually by a qualifie...

Страница 50: ...h 3 Disconnect thermocouple by loosening nut from the valve with a 9mm wrench Dis connect thermopile by loosening 2 screws marked TP on the valve 4 Drop the thermocouple or thermopile down from the br...

Страница 51: ...m wrench 6 Reconnect the pilot tube nut with a 7 16 wrench 7 Scrapeofftheoldgasketfromthefloorofthe firebox and from the valve tray assembly 8 Install a new gasket and reinstall the valve tray assembl...

Страница 52: ...er has a hinge that is attached 2 screws per hinge to the lip on bottom of the unit 3 Open the bottom louver Pull the Burner ON OFF control box from inside the bottom of the fireplace and position the...

Страница 53: ...rim with the holes in the firebox side 2 Secure with 2 screws per side 3 Loosen the 3 screws in the top inside edge of the firebox 4 Slide the Finishing Trim Top over the Side Trim pieces and fit the...

Страница 54: ...ick Panel Back 34 Brick Panel Left 35 Brick Panel Right 511 031 Brick Clips each 432 967 Burner On Off Switch Assy 38 910 241 Switch Burner On Off 910 899 Wire Harness Valve to Burner 432 917 F a n A...

Страница 55: ...b 56 910 190 Piezo Ignitor 57 910 478 SIT Valve NG LPG 58 Valve Bracket 59 Firebox Base 66 910 038 Pilot Assy S I T 3 Flame NG 910 039 Pilot Assy S I T 3 Flame LP 67 Pilot Holder 68 W840470 Pilot Asse...

Страница 56: ...ers Gold Black 510 922 Flush Louvers Black 510 923 Flush Louvers Steel Black 133 Flush Louver Assy Top 134 Flush Louver Assy Bottom 135 940 090 P Glass Flush 136 936 155 Glass Gasket Tadpole 904 691 U...

Страница 57: ...FPI P36 4 Zero Clearance Direct Vent Gas Fireplace 57 NOTES...

Страница 58: ...58 FPI P36 4 Zero Clearance Direct Vent Gas Fireplace NOTES...

Страница 59: ...gent Transportation Prepaid if requested Porcelain Enamel Absolute perfectionisneither guaranteednor commercially possible Any chips must be reported and inspected by an authorized dealer within three...

Страница 60: ...r your product online today View and modify a list of all your registered products Request automatic email notification of new product updates Stay informed about the current promotions events and spe...

Отзывы: