20
Regency GF900L-1 Gas Fireplace
installation
Notes:
1) Liner sections should be continuous without any
joints or seams.
2) Only Flex pipe purchased from Regency
®
may be
used for Flex installations
3) Horizontal flue must be supported every 0.9m.
4) Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 3m. If longer runs
are required, rigid pipe must be used.
NOTE: Maximum horizontal run: 3M
FPI Kit #
Length Contains:
#946-515
1.2 m
1)
175mm flexible outer liner (Kit length)
2)
102mm flexible inner liner (Kit length)
3)
spring spacers
4)
thimble
5)
AstroCap
termination cap
6)
screws
7)
tube of Mill Pac
8)
plated screws
9)
S.S. screws #8 x 1-1/2” drill point
#946-516
3 m
FLUEING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
These flueing systems, in combination with GF900L, have been tested and listed as a Direct Vent system by AGA. The location of the termination
cap must conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the GF900L using a flexible vent.
Flue Guard - if required*
(Part #946-506/P)
102mm