36
|
Bellavista
®
B36XTCE-10 Gas Fireplace
|
36
installation
VENTING ARRANGEMENTS FOR VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
(MUST USE REDUCER PART # 946-606 & 770-994 RIGID PIPE ADAPTOR)
The shaded area in the Diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90
o
elbows, with
Rigid
Pipe Venting Systems
for Propane and Natural Gas. Two 45
o
elbows equal to one 90
o
elbow. Maximum of four 45
o
elbows allowed.
• Vent must be supported at offsets.
• Firestops are required at each floor level and whenever passing through a wall.
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting to 2-1/4"
opening ,1-5/8"opening and to 1-1/16" opening.
Note: Must use optional flue adapter when using Rigid Pipe (Part # 770-994).
Maximum:
35.5
ft.
(10.
m)8
Minimum
8’
(2.4m)
Min.
49
”
(1.2m)
Maximum:
25
ft.
(7.6m)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
V
ertical
Height
(Feet)
32
34
36
38
6
8
Horizontal (Feet)
2
0
4
10
12
Restrictor 1-1/16” Open
No Restrictor
Maximum 10’ Centerline to Centerline
Restrictor 1-5/8” Open
Maximum 8’ Centerline to Centerline
Restrictor 2-1/4” Open
Set 2
Set 3
Set 1
Option V
H + H1 V + V1
A)
0' Min. 2' Max. 2' Min.
B) 1' Min. 2' Max. 3' Min.
C) 2' Min. 3' Max. 4' Min.
D) 3' Min. 4' Max. 6' Min.
E) 4' Min. 5' Max. 7' Min.
F)
5' Min. 6' Max. 8' Min.
G) 6' Min. 7' Max. 9' Min.
H) 7' Min. 8' Max. 10' Min.