Regal marathon PPA Series Скачать руководство пользователя страница 5

5

©2020 Regal Beloit Corporation, All Rights Reserved. MCIM20001E • Form# SB0098E

Specific conditions of use for Hazardous Area Motor:

•  WARNING! 

The equipment may present a potential 

electrostatic charging hazard: the user instructions shall 

be followed in order to minimize the risk of electrostatic 

discharge.

•  For arrangements that include a separately motor driven 

cooling fan, these shall be tested to verify that the rating 

of the cooling fan motor is not exceeded.

•  The thermal protection devices, when fitted with the 

motors with Variable Voltage Variable Frequency (VVVF) 

drives, shall be connected into motor control circuit in 

such a manner as to disconnect the source of supply in 

order to prevent the nominated temperature class from 

being exceeded.

•  The stator Resistance Temperature Detector (RTD) and 

thermistors can be connected vis standard industrial 

controller provided that the controller is located in a 

safe area.

•  The plug and socket type DXN1 shall not be used on 

inverter driven motors above 50/60Hz.

•  The plug and socket type DXN1 are limited to use within 

low impact areas.

7.0 CABLE ENTRIES

Cable entries are via appropriate cable glands or conduits 

fitted to the threaded entries in the wall of the terminal box 

or the gland plate attached to it. Cable entries for various 

frame sizes are as per the following table.

Motor 

frame

No. of 

entries

Entry size  

x pitch

Reference drawing 

for Ex motors

80 - 100

M20 x 1.5 or 

M25 x 1.5

B - PPA149

112 - 132

1 or 2

M20 x 1.5 or

M25 x 1.5

B - PPA125 &

B - PPA126A

B - PPA132A

160 - 200

1 or 2

M25 x 1.5 or 

M32 x 1.5 or

M40 x 1.5 or

M50 x 1.5

B - PPA125,

B - PPA127 &

B - PPA133

225 - 315

1 or 2

M40 x 1.5 or 

M50 x 1.5 or

M63 x 1.5

B - PPA125,

B - PPA129A,

B - PPA130A,

B - PPA130B,

B - PPA130C,

B - PPA134 &

B - PPA135

*355 - 400 1 or 2

B - PPA125 &

B - PPA131

*355 and 400 frames are supplied with a blank gland plate for the 

customer to create gland entry holes as appropriate.

Cable glands used by installer on hazardous location 

motors must be of IEC Ex certified type as appropriate to 

the installation requirements. Unused cable entries must 

be blanked off by installer using IEC Ex certified conduit 

stops as appropriate.
Cable glands and conduit stops must be of an IP Rating 

equal to or better than that of main motor as marked on 

the nameplate.

Vibration sensors and shaft encoders when fitted by the 

installer are to be appropriately certified by IECEx or ATEX 

for Zone 1 Group II T3 for Ex e, Zone 2 Group II T3 for 

Ex nA or Zone21 T135oC for Ex t.

7.1 SUPPLY CABLE/ TERMINALS

Supply terminals are located in the terminal box. They are 

suitable for receiving crimped lugs on the supply cables. In 

addition the terminal box also houses an earthing terminal.

Motor frame

Terminal Size

80 – 132

M5

160 – 200

M8

225 – 280

M10

315 - 400

M12

8.0 ELECTRICAL CONNECTION

•  WARNING! 

Ensure all electrical connections are solid 

and continuous.

•  WARNING! 

All circuit breakers, High Rupturing Capacity 

(HRC) fuses or protective devices associated with the 

motor must be rated to suit motor running current and 

starting chatracteristics.

•  WARNING! 

Ensure that proper earthing connection is 

made with all washers as provided.

•  WARNING! 

Check that the cable glands used on 

hazardous location motors are Ex approved by the 

standards organisation. Gland plugs to be of approved type.

•  Check motor starter and overloads for correct rating and 

trip setting.

•  Supply cables must be appropriately selected considering 

the voltage drop.

•   When using long supply cables with VVVF drive, check 

with Regal for proper recommendations to avoid high 

voltage transients occurring at motor terminals.

•  Check the connection diagram on the motor terminal box 

and make sure the supply leads are properly connected 

considering the supply phase sequence.

•  Ensure that the supply cable termination on to the motor 

terminal board is firm, without loss of strands while using 

crimped lugs and all washers are used in the correct 

order as provided.

•  Ensure enough clearances are provided between supply 

cable lugs and to earth especially so in case of hazardous 

location motors.

•  If using conduit for the supply leads, ensure the 

conduit is completely threaded in and seal the threads 

appropriately.

•  If RTDs of hazardous location motors are connected to 

monitor the winding temperature, the maximum voltage 

to the RTDs must be kept to 90V(peak) or below.

•  The thermal protection devices shall be connected 

into the motor control circuit in such a manner as to 

disconnect the source of supply in order to prevent the 

nominated temperature class from being exceeded. The 

stator RTDs and thermistors can be connected via a 

standard industrial controller provided that the controller 

is located in a safe area.

Содержание marathon PPA Series

Страница 1: ...PPA PPC SERIES MOTORS INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...vibration can damage bearings Shaft locking clamps where supplied are fitted securely Remove shaft locking clamps and turn rotor by one full rotation at least once in every two weeks and replace shaf...

Страница 3: ...tools to ensure parallel offset or angular displacement of the pulleys with respect to each other is compliant with permissible limits as recommended by the transmission supplier Correct alignment wi...

Страница 4: ...oup II Temperature class T3 Marking code II 3 G Ex nA IIC T3 Gc IP66 Tamb 20 C to 50 C Dust Excluding Ignition Proof Ex t Zones 21 22 Temperature class T4 Marking code II 2 D Ex tb IIIC T135 C Db IP66...

Страница 5: ...tor as marked on the nameplate Vibration sensors and shaft encoders when fitted by the installer are to be appropriately certified by IECEx or ATEX for Zone 1 Group II T3 for Ex e Zone 2 Group II T3 f...

Страница 6: ...ors make sure that the starting method employed keeps the starting current and duration within the nameplate figures of IA IN ratio and tE time Check that the running current on no load and full load...

Страница 7: ...d 12 2 LOADABILITY CURVE FOR VVVF DRIVE 1 Appliedloadonthemotorshallbewithinthelimitsforthe loadability curve for the motor The standard loadability curve is shown below In special circumstances deter...

Страница 8: ...ring no Bearing size Relubrication Bearing no Relubrication Qty g Interval hours Qty g Interval hours Interval hours 3000 r min 2 Pole 112 6306 30x72x19 7 9000 6306 30x72x19 7 9000 132 6308 40x90x23 1...

Страница 9: ...06 14000 132 6308 40x90x23 11 15000 6308 40x90x23 11 15000 NU308 11000 160 6309 45x100x25 13 14000 6309 45x100x25 13 14000 NU309 8500 180 6310 50x110x27 15 14000 6310 50x110x27 15 14000 NU310 8500 200...

Страница 10: ...10 2020 Regal Beloit Corporation All Rights Reserved MCIM20001E Form SB0098E...

Страница 11: ...lace Wetherill Park NSW 2164 T 1300 888 853 F 61 2 8781 3131 QUEENSLAND 7 Mahogany Court Willawong QLD 4110 T 1300 888 853 F 61 7 3246 3210 PRESENT IN MACKAY SOUTH AUSTRALIA WESTERN AUSTRALIA T 1300 8...

Отзывы: