Technical data
14 — English
Variomat 1 — 06.07.2016 – Rev. B
5
Technical data
5.1
Control unit
Note!
The following values apply for all control units:
– Permissible flow temperature:
– Permissible operating temperature:
– Permissible ambient temperature:
120 °C
70 °C
0 °C – 45 °C
Type
Power
output
(kW)
Power supply
(V / Hz , A)
Degree of
protection
Number of RS-
485 interfaces
I/O
module
Electrical voltage
control unit
(V, A)
Noise level
(dB)
Weight
(kg)
VS 1
0.75
230 / 50, 3
IP 54
1
No
230, 2
55
25
Содержание Variomat VS 1