Commissioning
46 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
7.10
Starting Automatic mode
Start Automatic mode to complete the commissioning process. These prerequisites must be met for starting Automatic mode:
•
System and device are filled with water.
•
Servitec and the facility system are vented.
– If necessary, repeat the "Filling the device with water" process see chapter 7.4 "Filling the device with water and venting" on
page 39 .
To start the Automatic mode, proceed as follows:
•
Touch the "AUTO" button.
Servitec-35
System
NSP
9.5 bar
Continuous degassing
Notice!
The "ST" dirt trap in the "DC" degassing line must be cleaned after the expiry of the continuous degassing time at the
latest, see chapter 10.2.1 "Cleaning the dirt trap" on page 69 .
Note!
The commissioning process is now concluded.