Controller
Master/Slave Operation — 24.09.2015
English — 17
15. Specify the value for the maximum pressure deviation for the
device.
– This parameter is meaningless in the master and can be
ignored.
– Define the parameter in the slaves.
– Setting range 0.1 – 5.0 bar.
– Use the buttons to enter the parameter value.
– Press "OK" to confirm.
Settings>Service>Master/Slave
(243) Max. pressure deviation
1.0
2.9 bar
0 %
16. Press "Activation delay“.
– The activation delay determines the activation
behaviour of the optional second pump, compressor or
overflow valve.
Settings>Service>Master/Slave
(244) Activation delay
5s
(245) Max. level deviation
5%
(246) Block message 29 PFK?
No
2.9 bar
0 %
17. Specify the value for the activation delay for the device.
– This parameter is meaningless in the master and can be
ignored.
– Define the parameter in the slaves.
– Setting range 0 – 240 seconds.
– Use the buttons to enter the parameter value.
– Press "OK" to confirm.
Settings>Service>Master/Slave
(244) Activation delay
_5s
2.9 bar
0 %
OK
OK