4. Set the system-specific values for the individual areas.
– Use the "Left" and "Right" buttons to select the display
value.
– Use the "Up" and "Down" buttons to change the display
value.
– Confirm your entries with "OK".
Press "i“ to display a help text for the selected area.
Press "X“ to cancel your input without saving the new
settings. The controller automatically opens again the list.
Settings > Customer
(002) Time
11:14
2.9 bar
0 %
9.3.2
Default settings
The device controller is shipped with the following default settings. Use the Customer menu to adjust these values to local conditions. In
specific cases, it is possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language
EN
Display language.
Minimum operating pressure "P
0
"
1.8 bar
see chapter 7.2 "Determining the P
pressure for the controller" on page 35 .
Next maintenance
12 months
Time left to the next due maintenance.
Floating alarm contact
YES
see chapter 9.3.3 "Messages" on page 50 .
Make-up
Make-up “ON”
8 %
Make-up “OFF”
12 %
Maximum make-up quantity
0 Litres
Only if make-up has been selected in the customer menu
with “With water meter Yes”.
Maximum make-up time
30 minutes
Maximum make-up cycles
6 cycles within 2 hours
Softening (Only if "With softening Yes")
Lock make-up
No
In the case of soft water residual capacity = 0
Hardness reduction
8°dH
= Target – Actual
Maximum make-up quantity
0 Litres
Soft water capacity
0 Litres
Cartridge replacement
18 months
Replace cartridge.