Controller
50 — English
Reflexomat with Touch controller — 06.07.2016 - Rev. B
9.3.3
Messages
t
The messages are impermissible deviations from the normal state. They can be output either via the RS-485 interface or via two floating
message contacts.
The controller displays the messages with a help text.
Message causes can be eliminated by the operator or a specialist workshop. If this is not possible, contact the Reflex Customer Service.
Note!
When the cause for the message is eliminated, you must acknowledge the fault with "OK" at the controller's operator
panel.
Note!
Floating contacts, setting in the Customer menu, see chapter 9.3 "Configuring settings in the controller" on page 46 .
To reset a fault message, proceed as follows:
1. Touch the display.
800l
25%
2.9 bar
System
0l
NSP
0l
2 Fault message
– The current fault messages are displayed.
2. Touch a fault message.
Current messages
01 Minimum pressure
02. 1 Insufficient water switch
2 Fault message
– The system displays the possible causes for the fault.
3. When the fault is eliminated, confirm the fault with "OK".
Current messages
02.1 Insufficient water
Possible causes
– Dry-running protection during pump 1 operation
– Make-up not excluded
– Dirt trap in make-up line clogged
– Make-up solenoid valve does not open
– Large gas quantities in the system
– Fault has been eliminated and can be
acknowledged.
0.4 bar
29 %