Controller 

 

 

 

Fillcontrol Plus 

 19.10.2020 - Rev. C 

 

English  

 11 

 

Indication on the 
display 

Meaning 

Disable make-up? 
YES 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

YES: The system stops the make-up process when 
the set soft water capacity is exceeded. 

 

NO: The system does not stop the make-up 
process. The system displays the "Softening" 
message. 

Hardness reduction 
10 °dH 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Hardness reduction is calculated from the 
difference of the overall water hardness GH

actual

 

and the target water hardness GH

target

Hardness reduction = GH

actual

-GH

target

l °dH 

Enter the value in the controller. Consult the 
manufacturer information for third-party products. 

Cap. soft water 
05000 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
The attainable soft water capacity is calculated from the 
type of softening used and the specified hardness 
reduction. 

 

Fillsoft I, soft water capacity ≤ 6000/hardness red. l

 

 

Fillsoft II, soft water capacity ≤ 12000/hardness 

red. l 

Enter the value in the controller. Consult the 
manufacturer information for the values of third-party 
products. 

Remaining cap. soft 
w. 
000020 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Available soft water capacity. 

Replacement 
18 months 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Manufacturer specification for the replacement 
interval of the softening cartridges, regardless of 
the calculated soft water capacity. The system 
displays the "Softening" message. 

Next maintenance 
012 months 

Recommended maintenance messages. 

 

Off: Without maintenance recommendation. 

 

001 

 060: Maintenance recommendation in 

months. 

Floating fault 
contact 
YES 

For the output of messages to the floating contact, see 
chapter 9.3 "Messages" on page 11 . 

 

YES: Output of all messages. 

 

NO: Output of all messages identified with 

"xxx"

 

("01", for example). 

Fault memory

˃

 

Switch to the "Fault memory" sub-menu. 

 

Press "OK" to open the menu. 

 

Use the "

▼▲

" buttons to open the sub-menu. 

ER 01…xx

 

The last 20 alarms are stored with fault type, date, time, 
and fault code. 
See the chapter "Messages" for more information about 
the ER... messages. 

Parameter 
memory

˃

 

Switch to the "Parameter memory" sub-menu. 

 

Press "OK" to open the menu. 

 

Use the "

▼▲

" buttons to open the sub-menu. 

P0 = xx.x bar 
Date | Time 

The last 10 entries of the minimum working pressure are 
stored with date and time. 

V0.60 

Information about the software version 

 

 

9.2.1

 

Customer menu 

The device controller is shipped with the following default settings. Use the 
Customer menu to adjust these values to local conditions. In special cases, it is 
possible to further adjust the values in the Service menu.

 

 

Parameter 

Setting 

Comment 

Language 

EN  

Display language 

Fillcontrol XX 

Magcontrol  For systems with diaphragm-type 

expansion vessel 

Minimum operating 
pressure P

1.5 bar 

Only Magcontrol 
see chapter 7.2 "Determining the P

0

 

minimum operating pressure for 
the controller" on
 page 8  

Safety valve, pressure  

3.0 bar 

Tripping pressure for the safety 
valve at the heat generator in the 
system 

Next maintenance 

12 months 

Time left to the next due 
maintenance 

Volt-free contact 

NO 

Only the messages marked in the 
"Messages" list 

Make-up 
Maximum make-up volume  5000 litres 

Only if controller with "With water 
meter yes" 

Maximum make-up time  

20 minutes  Magcontrol 

Maximum make-up cycles  3 cycles 

within 2 
hours  

Magcontrol 

Softening (Only if "With softening yes") 
Shut off make-up 

NO 

In the event of soft water residual 
capacity = 0 

Hardness reduction 

8°dH 

= Setpoint 

 Actual 

Maximum make-up volume  0 litres 

Attainable make-up quantity 

Soft water capacity 

0 litres 

Attainable water capacity 

Cartridge replacement 

18 months 

Replace cartridge 

 
9.2.2

 

Service menu 

This menu is protected with a password. It can be accessed only by the Reflex 
Customer Service. A partial summary of the settings stored in the Service menu is 
proved in the Chapter Default settings. 
 
Service menu 

Parameter 

Setting 

Remarks 

 
Makeup 

 

 

Pressure differential, 
"NSP" makeup 

0.2 bar  

Only Magcontrol 

Pressure differential, 
filling pressure PF 

 P

0

  

0.3 bar  

Only Magcontrol 

Water quantity for each 
contact 

10 l / K 

Only if a water meter is 
installed. 

Maximum filling 
contacts 

OFF 

Limits the filling volume. 
Only if a water meter is 
installed. 

 

9.3

 

Messages 

Messages with ER codes are displayed at the controller. 

 

Use the arrow keys at the controller operating panel to select the 
messages. 

 

By selecting the "Fault memory" main menu in the Customer menu, you 
display the last 20 alarms. 

 

Alarm causes can be eliminated by the operator or a specialist workshop. 

 

If required, please contact the Reflex Customer Service. 

 

Содержание Fillcontrol Plus

Страница 1: ...Fillcontrol Plus 19 10 2020 Rev C GB Operating manual Original operating manual...

Страница 2: ...ion 6 6 4 Switching and make up variants 6 6 5 Electrical connection 7 6 5 1 Terminal diagram 7 6 5 2 RS 485 interface 8 6 6 Installation and commissioning certificate 8 7 Commissioning 8 7 1 Requirem...

Страница 3: ...n combination with the signal word Warning indicates imminent danger failure to observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in...

Страница 4: ...ing system 3 Fillcontrol Plus LIS Filling level monitoring for level dependent make up External signal line to the controller PIS Pressure transducer for pressure dependent make up Internal signal lin...

Страница 5: ...warning signs in the vicinity of the device CAUTION Risk of injury due to falls or bumps Bruising from falls or bumps on system components during installation Wear personal protective equipment helme...

Страница 6: ...r selecting the make up variants see chapter 6 4 Switching and make up variants on page 6 6 4 Switching and make up variants Example of a pressure dependent make up with Fillcontrol Plus 1 Fillset 2 F...

Страница 7: ...after the device has been physically isolated from the power supply by pulling out of the mains plug Before you remove the covers completely isolate the device controller from the power supply Verify...

Страница 8: ...g the power plug into a corresponding outlet The controller is in Stop mode 7 2 Determining the P0 minimum operating pressure for the controller The P0 minimum working pressure for the device is used...

Страница 9: ...er Press Auto for automatic operation The Auto LED at the operator panel illuminates to visually signal automatic operation Note The commissioning process is now concluded 8 Operation 8 1 Operating mo...

Страница 10: ...me Adjust the Hour Minute and Second display when each begins to flash This time is used for entries in the fault memory Date Adjust the Day Month and Year display when each begins to flash This date...

Страница 11: ...r memory Switch to the Parameter memory sub menu Press OK to open the menu Use the buttons to open the sub menu P0 xx x bar Date Time The last 10 entries of the minimum working pressure are stored wit...

Страница 12: ...value for the maximum pressure has been exceeded Safety valve defective Insufficient dimensioning of the pipeline to the system Check the actuating pressure of the safety valve Replace the safety val...

Страница 13: ...g regulations CAUTION Risk of injury due to pressurised liquid If installation removal or maintenance work is not carried out correctly there is a risk of burns and other injuries at the connection po...

Страница 14: ...n the vicinity of the device CAUTION Risk of injury due to pressurised liquid If installation or maintenance work is not carried out correctly there is a risk of burns and other injuries at the connec...

Страница 15: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 16: ...SI1417enC 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: