Description of the device
4 — English
Fillcontrol Auto Compact — 20.10.2020 - Rev. D
4
Description of the device
4.1
Description
The device is a makeup station for heating or cooling water systems with a pump
and a system separator vessel. The device controller controls the freshwater
makeup for the plant system.
You can select from two makeup variants for this device:
•
Freshwater makeup for plant systems with a diaphragm expansion tank.
•
Freshwater makeup for plant systems with a pressurisation station.
4.2
Overview
1
Control Basic controller
2
Position of the "LS" insufficient water switch in the mains separator
tank
3
"BT" mains separator tank
4
"PIS" pressure transducer
5
Pump "PU"
OC
Overflow from the mains separator tank
WC
Fresh water make-up line to the device
DC
Make-up line to the system circuit
4.3
Identification
4.3.1
Nameplate
The nameplate provides information about the manufacturer, the year of
manufacture, the manufacturing number and the technical data.
Information on the type plate
Meaning
Type
Device name
Serial No.
Serial number
min. / max. allowable pressure P
Minimum/maximum permissible
pressure
max. continuous operating
temperature
Maximum temperature for continuous
operation
min. / max. allowable temperature
/ flow temperature TS
Minimum / maximum permissible
temperature / TS flow temperature
Year built
Year of manufacture
min. operating pressure set up on
shop floor
Factory set minimum operating
pressure
at site
Set minimum operating pressure
max. pressure saftey valve
factory - aline
Factory set actuating pressure of the
safety valve
at site
Set actuating pressure of the safety
valve
4.3.2
Type code
No.
Type code (example)
1
Device designation
2
Auto Compact
Fillcontrol Auto Compact AC 8,5
3
Maximum working
pressure (in bar)
1
2
3
4.4
Function
1
"FQIRA" contact water meter (optional accessory)
2
Fillsoft (optional accessory)
3
Fillcontrol Auto Compact
PIS Pressure sensor
WC Fresh water make-up line to the device
LS Signal line for insufficient water switch
DC Make-up line to the system circuit
LIS External signal line from a pressurisation unit
The device controller uses the pump to regulate the make-up with fresh water
for the system circuit.
The controller monitors the following parameters:
•
Make-up time
•
Make-up cycles
•
Make-up quantity, if an optional contact water meter is installed
The controller will detect small leaks in the system. When a leak is detected, the
controller interrupts the make-up with as soon as the make-up time or the make-
up cycles are exceeded. An integrated insufficient water protection sensor
deactivates the pump to prevent it from running dry.
You can select from two make-up variants for this device. These variants depend
on the system circuit.
•
Water make-up to system circuits with a diaphragm expansion vessel.
–
The pressure transducer sends a signal to the controller if the
pressure drops below the minimum working pressure of the system
circuit. The controller activates the pump. The system circuit is
replenished with fresh make-up water from the mains separator
tank. For calculating the filling pressure in the system circuit, see
chapter 7.2 "Determining the P
minimum operating pressure for the
•
Water make-up using a pressurisation unit.
–
Pressurisation units are equipped with filling level monitors. When
the filling level falls below the minimum level, the pressurisation unit
sends a signal to the device controller. The controller activates the
pump. The system circuit is replenished with fresh make-up water
from the mains separator tank.
Note!
The make-up variant is set in the Customer menu, see chapter 9.2.1
"Customer menu" on page 12 .