Operating Instructions
NOTE:
.Read.and.understand.all.
warning
.and.
precaution
.statements.
listed.in.the.safety.section.of.this.operation.manual.prior.to.using.this.
meter..Set.the.function.select.switch.to.the.OFF.position.when.the.
meter.is.not.in.use.
AC/DC Current Measurements
WARNING:
.Ensure.that.the.test.leads.are.disconnected.from.the.meter.
before.making.current.clamp.measurements.
1..Set.the.Function.switch.to.the..
600 or 400A
.range..If.the.range.of.the..
measured.is.not.known,.select.the.
higher range first then move to the
lower.range.if.necessary.
2..Select.AC.or.DC.with.the.AC/DC..
button..Press.the.zero.button.to.zero.
the.meter.in.the.DCA.mode.only.
3..Press.the.trigger.to.open.jaw..Fully.en-
close.one.conductor.to.be.measured.
4..The.clamp.meter.LCD.will.display.the.
reading.
AC/DC Voltage Measurements
1..Insert.the.black.test.lead.into.the..
negative.
COM
.terminal.and.the.red.test.lead..
into.the.positive.
V
.terminal.
2..Set.the.function.switch.to.the.
V
.position.
3..Select.AC.or.DC.with.the.
AC/DC
.button..
4..Connect.the.test.leads.in.parallel..
to.the.circuit.under.test.
5..Read.the.voltage.measurement..
on.the.LCD.display.