RECEIVING AND CHECKING EQUIPMENT
INSTALLATION
I D E N T I F Y U N I T
The unit model number and serial number are located
on the unit identification label (located on the left side
of the unit). Check this information against shipping
papers and job requirements.
I N S P E C T S H I P M E N T
Upon receipt of a DVS Series Air Handler, the packaging
should be checked for peripheral signs of transportation
damage while unit is still in the shipping package. If unit
appears to be damaged or is torn loose from its anchorage,
the unit shall be immediately examined by the receiving
party before removal. If damage is found, the receiving
party must sign the driver’s delivery receipt noting all
damage (i.e. carton damage and/or product damage) as
well as contact the last carrier immediately, preferably in
writing, requesting inspection by the carrier’s agent. All
claim papers MUST be forwarded to your local distributor
for processing. In general, upon receipt of product, be
sure to check all items against shipping list; if items are
found to be missing, it should be noted as such on the
driver’s delivery receipt; and the receiving party shall
also immediately notify the area distributor. To prevent
loss or damage, leave all parts in original packages until
installation.
The DVS Series Air Handler needs to be
installed and commissioned by a knowledgeable
qualified professional.
NOTES:
1. This Air Handler is approved for upflow, downflow,
and horizontal configurations.
2. Clearance arrows do not change with Air Handler
orientation.
3. This Air Handler is for indoor installation only.
4. Unit(s) shall be installed in such a way as to ensure
that the electrical components are protected from
any contact with water.
5. Unit(s) shall not be installed directly on any combustible
material other than wood flooring.
6. This unit is designed to be used with an air distribution
system (ductwork). Refer to the Air Distribution
Ductwork section.
7. The installer shall provide ample space for servicing
and cleaning. Always comply with minimum fire
protection clearances shown in Figure 1.
8. The DVS units are designed to be installed vertically
or horizontally on the floor; units may also be hung
from the ceiling or wall. Be sure to allow appropriate
clearances for wiring, piping and servicing.
R E D Z O N E
T M
D V S S E R I E S A I R H A N D L E R M A N U A L
WARNING
Do not install this unit if the unit is damaged.
Do not install this unit if any part or all of unit has
been under water. Refer to the Receiving and Checking
Equipment section.
TOP/PLENUM
zero
SIDE
zero
BACK
zero
SIDE
zero
FRONT
zero
BOTTOM
zero
SERVICING
24” (610 mm)
F I G U R E 1 Minimum Clearance to Combustible Construction