2
Drawing No. LP1140
Effective 08 2021
GENERAL METER SPECIFICATIONS
Note:
The
PM-50 4.3 inch host accepts a maximum of 5
modules while the 3.5 inch host accepts a maximum of 3.
Only one module from each function type (i.e. communication,
relay, analog output) can be installed.
1.
POWER
: The meter is intended to be powered by NEC/CEC
class 2, IEC/EN/UL 60950-1 LPS or UL/CSA 601010-1
Limited Energy power source.
MODEL
4.3-INCH
3.5-INCH
Input Voltage (Volts)
10-30 VDC
10-30 VDC
Max Power PM-50 only
4.6 W
4.6 W
Max Power PM-50, with modules
12 W
12 W
Host Isolation: 500 Vrms for 1 min. to all inputs and outputs.
2.
DISPLAY
:
4.3" or 3.5" Color TFT display with resistive analog
touch screen
SIZE
4.3-INCH
3.5-INCH
TYPE
TFT
TFT
COLORS
262,144
262,144
PIXELS
480 X 272
320 X 240
BRIGHTNESS
420 cd/m
2
540 cd/m
2
LED BACKLIGHT LIFE
*
30,000 HR TYP.
30,000 HR TYP.
* Lifetime at room temperature (25°C)
3.
SENSOR POWER
:
+24 VDC, ±5% @ 50 mA max.
4.
COUNTER DISPLAYS
: 9 digits available
Display Range: -99,999,999 to 999,999,999
Over Range Display: Overrange
Under Range Display: Underrange
Display Designators: Cnt-A, Cnt-B, Cnt-C
Maximum Count Rates: 50% duty cycle
If Setpoints Disabled: 35 KHz for all modes except Quadrature
x4 (32 KHz)
If Setpoint(S) Enabled: 20 KHz for any mode except
Quadrature x1 (19 KHz), Quadrature x2 (17 KHz) and
Quadrature x4 (10 KHz)
5.
RATE DISPLAYS
: 6-digit
Maximum Frequency: 50 KHz
Minimum Frequency: 0.001 Hz
Display Update Time: 0.1 to 999.9 seconds
Accuracy: ±0.01%
6.
SIGNAL INPUTS (INPUT A and INPUT B)
:
Software configurable input types including switch contacts,
TTL outputs, magnetic pickups and all standard RLC
sensors. Inputs are configurable for current sinking or
current sourcing outputs with input filtering for low
frequency signals or switch contact debounce. Not isolated
from the sensor input common.
Logic: Input trigger levels V
IL
= 1.2 V max.; V
IH
= 3.75 V min.
Sink: Adds internal 7.8 KΩ pull-up resistor to +5 VDC, 0.7
mA max
Source: Adds internal 3.9 KΩ pull-down resistor, 7.3 mA
max. at 28 VDC, V
MAX
= 30 VDC
Magnetic Pickup:
V
IN_PK
= 200 mV; V
IN_HSYS
= 100 mV; Must also have SRC
selection turned on through software
V
MAX
= ± 40 V
PEAK
or 28 Vrms
Dual Count Modes:
When any dual count mode is used, then User Inputs 1 and/
or 2 will accept the second signal of each signal pair. The user
inputs do not have the Logic/Mag, HI/LO Freq, and Sink/
Source software selections. The user inputs are inherently a
logic input with no low frequency filtering implemented in
software. The user input may only be selected for sink/
source by the User Input Active parameter.
7.
USER INPUTS
: Two programmable user inputs
Max. Continuous Input: 30 VDC
Isolation to Sensor Input Common: Not isolated.
Logic State: User programmable for sink/source (Lo/Hi)
INPUT STATE
LO/SINK
HI/SOURCE
20 KΩ pull-up to +3.3 V
20 KΩ pull-down
Active
V
IN
< 0.9 VDC
V
IN
> 2.4 VDC
Inactive
V
IN
> 2.4 VDC
V
IN
< 0.9 VDC
8.
MEMORY
: Nonvolatile memory retains all programmable
parameters and display values.
Memory Card: microSD slot accepts up to 32 GB capacity
cards in FAT16/FAT32 format.
9.
RS485 SERIAL PORT:
Uses Modbus protocol
Baud Rate: Up to 115,200
Data Format: 7/8 bit; odd, even, or no parity; 1 or 2 stop bits
Isolation: 500 Vrms to sensor, user power and digital inputs.
Not isolated to solid state outputs
10.
Wi-Fi CAPABILITIES:
Wi-Fi: Power output up to 20.5 dBm
Frequency:
TECHNOLOGY
CHANNELS
FREQUENCIES
Wi-Fi
1-13
2412-2484 MHz
Note: Channel/frequency limitation is enforced based on
configured country/region code.
Wi-Fi Compliance: TCP/IP; 802.11 b/g/n
11.
ON-BOARD DUAL SSR OUTPUTS:
Both outputs must be
used either in SINKING or in SOURCING mode together.
Sinking Mode:
Type: Switched DC, N-channel open drain MOSFET
Max Sink Current: 100 mA
V
DS
ON: 0.3 V @ 100 mA
V
DS
MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max
Sourcing Mode:
Type: Switched DC, P-channel open source MOSFET
Max Source Current: 100 mA
V
DS
ON: 0.3 V @ 100 mA
V
DS
MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max
12.
ENVIRONMENTAL CONDITIONS
:
Operating Temperature Range: -10 to 55 °C
Storage Temperature Range: -20 to 60 °C
Operating and Storage Humidity: 0 to 85% max. RH non-
condensing
Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 68-2-27: Operational 20 g (10 g relay)
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/
EN 60664-1.
13.
CERTIFICATIONS AND COMPLIANCES
:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
FCC ID#: 2AC7Z-ESP32WROOM32U
UL Hazardous: File # E317425
Type 4X Indoor/IP65 Enclosure rating (Face only) for all models
IP20 Enclosure rating (Rear of unit)
14.
CONNECTIONS
: High compression spring-clamp terminal
block